background image

1.

Position the flange medallion upside down on a
soft, clean surface. Place the blade with the
decorative side facing down onto the flange
medallion. Attach the flange assembly to the blade
and flange medallion using the four #10-32 x
22mm oval head screws as shown in Figure 2.
Repeat for the four remaining blades.

NOTE: Take care not to scratch fan housing when
installing blades.

2.

The flange assemblies have interlocking tabs, be
sure that the flanges are installed in a clockwise
manner to engage the interlocking feature. Be sure
all the flanges are properly engaged and then
tighten the flange screws. If one of the flanges do
not seat properly on the motor hub, loosen the
adjacent flange screws, re-engage and reseat the
flanges, then tighten the screws again.

3.

Attach the blade/flange assembly using two
1/4-20 x 12mm oval head screws (Figure 3). Install
the remaining four fan blades assemblies using the
same procedure.

4.

Gently snug all flange screws to the motor
housing, working around the housing in a
clockwise sequence. Failure to follow this
procedure could result in fan wobble. This
completes the blade installation.

SHIPPING 
RETAINERS (5)

FAN BLADE

#10-32 x 22mm OVAL 
HEAD BLADE SCREW 
(4 per blade/flange)

FLANGE MEDALLION 
ASSEMBLY

FAN FLANGE

Figure 2

If your fan is to replace an existing ceiling light fixture,
turn electricity off at the main fuse box at this time
and remove the existing light fixture.

Turning off wall switch is not sufficient. To avoid
possible electrical shock, be sure electricity is turned
off at the main fuse box before wiring. All wiring must
be in accordance with national and local codes and
the ceiling fan must be properly grounded as a
precaution against possible electrical shock.

WARNING

!

Your new ceiling fan will require a grounded electrical
supply line of 120 volts AC, 60 Hz, 15 amp circuit.

The outlet box must be securely anchored and
capable of withstanding a load of at least 50 pounds.

To reduce the risk of fire, electric shock, or personal
injury, mount fan to outlet box marked “Acceptable
for Fan Support of 50 lbs. or Less”, and use screws
supplied with outlet box. Most outlet boxes
commonly used for support of light fixtures are not
acceptable for fan support and may need to be
replaced. Consult a qualified electrician if in doubt.

WARNING

!

Electrical Requirements

Ceiling Fan Assembly

Procedures

To avoid possible fire or shock, follow all wiring
instructions carefully. Any electrical work not
described in these instructions should be done or
approved by a licensed electrician.

WARNING

!

4

IMPORTANT: Your ceiling fan is supplied with an
Fan/Light Dual Slide Wall Control (transmitter).
This allows you to regulate your ceiling fan speed,
airflow direction, and light intensity. Optional
Emerson Electric Remote and Wall Control may
also be used, see store or catalog.

IMPORTANT: Your ceiling fan will not function
properly and may be damaged, if used with any
wall dimmer switch or control other than the
Emerson controls listed above.

IMPORTANT:  Remove the five motor retainers
from the motor hub and discard the retainers and
retainer screws before installation of flange/blade
assembly (Figure 1).

U.L. Model No.: CF830

Figure 1

Summary of Contents for MONACO CF830GES

Page 1: ...READ AND SAVE THESE INSTRUCTIONS Part No F40BP74050000 Form No BP7405 U L Model No CF830 Net Weight 35 3 Lbs Model Number MONACO 60 Ceiling Fan Owner s Manual CF830GES00 Golden Espresso ...

Page 2: ...ownrod 10 furnished with the ceiling fan provides the minimum recommended floor to fan blade clearance for a 9 foot ceiling The 4 5 downrod supplied is to be used for shorter ceilings 5 The fan must be mounted with the fan blades at least 7 feet from the floor to prevent accidental contact with th fan blades 6 Follow the recommended instructions for the proper method of wiring your ceiling fan If ...

Page 3: ...product by Emerson Electric Co could result in personal injury or property damage WARNING WARNING 1 Open styrofoam unit containing fan Remove upper and center sections of styrofoam unit Remove parts and check to see that you have received the following a One Fan Motor and Housing Assembly b One Ceiling Cover c Five Fan Blades d Five Flange Assemblies e Five Flange Medallion Assemblies f One Coupli...

Page 4: ...l shock be sure electricity is turned off at the main fuse box before wiring All wiring must be in accordance with national and local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock WARNING Your new ceiling fan will require a grounded electrical supply line of 120 volts AC 60 Hz 15 amp circuit The outlet box must be securely anchored and capabl...

Page 5: ...ing adapter to the fan motor housing by reinstalling the previously removed screw into the remaining hole Tighten the three screws at this time To reduce the risk of personal injury do not bend the blade flange when installing the blade flanges balancing the blades or cleaning the fan Do not insert foreign objects in between rotating fan blades WARNING To avoid possible fire or shock do not pinch ...

Page 6: ...g the 4 5 downrod proceed to Step 16 and then onto Step 21 If installing ceiling fan on a minimum recommended floor to fan clearance for a 9 foot ceiling using the 10 downrod proceed to Step 17 16 4 5 Downrod Installation Be sure the grommet is properly installed in the coupling cover then slide the coupling cover on the downrod until it rests on the motor housing Be sure that the coupling cover i...

Page 7: ...ghten the decorative upper scroll to the 10 downrod using the supplied 2mm hex wrench Figure 10 22 Reinstall the hanger ball on the downrod as follows Route the motor leads through the hanger ball and slide the hanger ball over the downrod Figure 12 Install the pin through the holes at the top of the downrod and slide the hanger ball up the downrod aligning the ball so the pin is captured in the g...

Page 8: ...OX HANGER BRACKET TAB OUTLET BOX Figure 15 To reduce the risk of fire electric shock or personal injury mount fan to outlet box marked Acceptable for Fan Support of 50 lbs or Less and use screws supplied with outlet box Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced Consult a qualified electrician if in doubt WARNING 2 C...

Page 9: ...te wire to the supply white neutral wire using wire connector supplied Figure 17 Securely connect the fan motor black wire to the control black wire using wire connector supplied Figure 17 Securely connect light lead blue and light lead yellow wires to blue of fan control After connections have been made turn leads upward and carefully push leads into the outlet box with the white and green leads ...

Page 10: ...ling Fan Dual Slide Wall Control 1 Remove the wall plate and screws from the existing wall switch Pull switch out from wall outlet box 2 Disconnect wire from existing fan wall switch Figure 19 5 Attach the fan light control to the outlet wall box using two 6 32 x 3 4 screws supplied Figure 21 Install the wall plate using two 6 32 x 1 4 screws supplied 6 Installation of the ceiling fan is now compl...

Page 11: ... W GROUND WIRE BETWEEN CEILING AND WALL OUTLET BOXES GREEN WHITE BLACK BLUE 120V AC SUPPLY SOURCE BLACK WHITE GROUND BLUE BLACK FAN LIGHT CONTROL BLACK WHITE CEILING OUTLET BOX BLUE D L YELLOW U L Schematic B CONNECTIONS REQUIRED WHEN SUPPLY VOLTAGE IS FED INTO WALL OUTLET BOX NOTE Refer to Schematic A or B depending upon the location of your 120V AC supply source Figure 22 NOTE This wiring config...

Page 12: ...knob up to operate your light on low to high settings See Figure 23 4 To turn the lights off position the knob below the number bottom setting 4 3 2 1 EMERSON Figure 23 REVERSE SWITCH Figure 24 12 U L Model No CF830 5 All fans are shipped from the factory with the reversing switch positioned to circulate air downward If airflow is desired in opposite direction turn your fan OFF and wait for the bl...

Page 13: ...fan could result in fire shock and personal injury WARNING Trouble Shooting TROUBLE PROBABLE CAUSE SUGGESTED REMEDY 1 Fan will not start 1 Fuse or circuit breaker blown 1 Check main and branch circuit fuses or circuit breakers WARNING Make sure main power is turned off 2 Loose power line connections to the fan 2 Check line wire connections to fan 3 Fan Light Wall Control is OFF 3 Turn ON Fan Light...

Page 14: ...14 U L Model No CF830 Repair Parts 7 1 2 15 3 9 8 17 18 16 14 6 13 26 22 11 19 21 20 12 24 25 23 4 3 2 1 10 5 4 ...

Page 15: ...ive Upper Scroll 1 763956 GES 18 Decorative Lower Scroll 1 763957 GES 19 Flange Assembly 5 per set 763963 GES 20 Flange Medallion Assembly 5 per set 763965 GES 21 Blade Assembly 5 per set 763967 22 Adapter Switch Housing 1 763962 23 Harness Wiring Reverse Switch Aux Capacitor 1 763969 24 Housing Switch 1 763970 GES 25 Nut Finial 1 763972 GES 26 Transmitter Dual Slide Wall Control 1 761974 1 27 Dow...

Page 16: ...an authorized service center call 1 800 654 3545 for the address of the nearest authorized service center You will be responsible for all insurance freight or other transportation charges to our factory or authorized service center Your Emerson Air Comfort Ceiling Fan should be properly packed to avoid damage in transit since we will not be responsible for any such damage What Is Not Covered The g...

Reviews: