![Emerson Micro Motion 5700 Installation Manual Download Page 39](http://html.mh-extra.com/html/emerson/micro-motion-5700/micro-motion-5700_installation-manual_104641039.webp)
Figure 4-29: Channel A active (internal) and Channel D passive (external) power
A. Channel A mA Output
B. Channel D mA Input
C. Terminals
D. 820 ohm maximum loop resistance including 100 ohms (H) for mA Input (250–600 ohm
for HART communications)
E. Signal device
F. Terminal compartment
G. External to the 5700
H. 100 ohm input resistance
Installation Manual
Wiring the channels
MMI-20027478
February 2020
Installation Manual
39