5.2
Measuring ranges and sensitivity
Sensor
PR 6422
PR 6423
PR 6424
PR 6425
PR 6426
Nominal
measuring
range, static
measurement
s
±0,5 mm
±1,0 mm
±2,0 mm
±2,0 mm
±4,0 mm
Nominal
measuring
range,
dynamic, peak
−
peak
(recommende
d)
25 ... 250 µm
50 ... 500 µm
100 ... 1000
µm
100 ... 1000
±m
---
Sensitivity for
42 Cr Mo 4
16 V/mm
8 V/mm
4 V/mm
4 V/mm
2 V/mm
Approximate
value for
nominal
distance at the
center point of
converter
output signal *
approx. 0,8
mm
approx. 1,5
mm
approx. 2,7
mm
approx. 2,6
mm
approx. 5,5
mm
Basic air gap * approx.
0,15 ... 0,35
mm
approx. 0,4 ...
0,7 mm
approx.
0,55 ... 0,95
mm
approx. 0,5 ...
1,0 mm
approx. 1,2 ...
1,8 mm
* With standard measuring ranges (not valid for use of extended measuring ranges)
The sensor PR 6423 corresponds to the API 670 / DIN 45670 standard.
Calibration: If no other material was stated, sensor and converter are adjusted on the
standard material (42 Cr Mo 4), refer to section
Measuring chain and material of
.
Technical data
Installation Guide
January 2020
MHM-97857
24
MHM-97857, Rev 1.5
Summary of Contents for Machinery Health PR 642 Series
Page 4: ...Contents Installation Guide January 2020 MHM 97857 iv MHM 97857 Rev 1 5 ...
Page 10: ...Safety Instructions Installation Guide January 2020 MHM 97857 10 MHM 97857 Rev 1 5 ...
Page 12: ...Application and Design Installation Guide January 2020 MHM 97857 12 MHM 97857 Rev 1 5 ...
Page 32: ...Drawings Installation Guide January 2020 MHM 97857 32 MHM 97857 Rev 1 5 ...
Page 36: ...Order Matrix Installation Guide January 2020 MHM 97857 36 MHM 97857 Rev 1 5 ...
Page 37: ...8 Certificates Installation Guide Certificates MHM 97857 January 2020 MHM 97857 Rev 1 5 37 ...
Page 38: ...Certificates Installation Guide January 2020 MHM 97857 38 MHM 97857 Rev 1 5 ...
Page 39: ...Installation Guide MHM 97857 January 2020 MHM 97857 Rev 1 5 39 ...