UPS Specifications
35
5.4.1 Input Rectifier
Battery
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Device
Rating
Bolt
Size
Maximum Recommended Lug
(Thomas & Betts Part Number)
Compression
2-Hole;
3/8" bolt
Mechanical
2-Hole;
40
82 at 480VDC
98 at 400VDC
70
8M
54106
ADR21
60
122 at 480VDC
146 at 400VDC
110
8M
54107
ADR21
80
163 at 480VDC
195 at 400VDC
150
8M
54152-TB
ADR21
100
204 at 480VDC
244 at 400VDC
175
8M
54157
ADR21
120
244 at 480VDC
293 at 400VDC
225
8M
54167
ADR50
1. Nominal (Nom) current is based on full rated output load.
2. Maximum (Max) current (125% of nominal) is short duration for battery recharge conditions.
3. UPS input and bypass cables must be run in separate conduit from output cables.
4. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
5. OCPD = Overcurrent Protection Device. Recommended AC input and AC output overcurrent protection represents 125% of nominal full
load current (continuous) per NEC 215.
6. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. Neutral conductors to
be sized for full capacity per NEC 310-15 (b)(4). References are per NEC 1999.
7. Wiring requirements:
a. AC Input: 3-phase, 4-wire, plus ground output.
b. AC Output: 3-phase, 3- or 4-wire, plus ground
8. All wiring is to be in accordance with national and local electric codes.
Table 9
Rectifier input power
Rated Power kVA
40
60
80
100
120
Rated Voltage, VAC
480
Supply
3-phase, 3-wire plus ground
Input Voltage Tolerance, VAC
(without derating)
384-552
Frequency, Hz
57-66
Power Factor
> 0.99 at full load; >0.98 at half load
Harmonic Current
Less than 3% at full rated UPS output load
See
Table 8
for current ratings.
Overload capacity of input current:
100% Imax <I<125% Imax: 60 min
125% Imax <I<150% Imax: 10 min; >150% load, less than 200msec
Table 10
Input voltage window with derating
Input Voltage Window
(L-L Voltage)
Percentage
of Nominal
Inverter Load,
Percentage
Charger Load,
Percentage
432VAC to 552VAC
90-115
100%
100%
431VAC to 384VAC
80-89
100%
30%
383VAC to 360VAC
75-79
100%
0%
359VAC to 288VAC
60-74
80%
0%
Table 11
Liebert approved replacement batteries
Battery Manufacturer
Models Supplied
Enersys Yuasa
HX205
—
—
C&D Dynasty
UPS12-100MR
UPS12-150MR
UPS12-210MR
Table 8
UPS terminal (continued)