10H52200GM60 – Rev. 5 – 06/2014 

2

 

10B

UPS

 

C

ONTROLS AND 

C

ONNECTIONS

 

Figures 1 – Front Panel LEDs 

 

 

Figure 2 – Rear Panel 

 

 

UPS Status, Alarm Conditions and Alerts 

Condition LED 

Color 

Solid/Flashing 

Audible 

Alarm 

Normal mode 

LED 1 

Green 

Solid   

(none) 

Battery mode 

LED 1 

Green 

Flashes   

Every 10 seconds 

Load level at Normal mode 

LED 3-6 

Green 

Solid 

Overload: every 0.5 second 

Battery level at Battery mode 

LED 3-6 

Green 

Solid 

Low battery: every second 

Fault 

LED 2 

Red 

Solid 

Continuous until UPS shuts down 

Battery replacement 

LED 2 

Red 

Solid 

Every 2 seconds 

 

9B

T

ROUBLESHOOTING

 

If the UPS malfunctions during operation, check the following chart for proper adjustment. For further assistance, please contact your local 

Emerson Network Power representative. 

Problem Possible 

Causes 

Solutions 

Utility is normal, but LED is not 

illuminated.  

 

Battery capacity may be low. 

 

The UPS battery reached end of life.

 

 

 

The UPS may not be turned on. 

 

Recharge the UPS at least 6 hours. 

 

Properly trained and qualified service personnel 

replace the battery with the same type of 

battery ,do not attempt to replace the battery 

yourself.  

 

Press the On/Off button to turn on the UPS. 

Alarm buzzer beeps continuously 

although utility power is normal.   

 

The UPS may be overloaded.   

 

Disconnect some equipment from the UPS. 

UPS does not provide expected 

backup time. 

 

The UPS may be overloaded 

 

Battery voltage may be low. 

 

The UPS battery reached end of life. 

 

Disconnect some equipment from the UPS. 

 

Recharge the UPS at least 6 hours. 

 

Properly trained and qualified service personnel 

replace the battery with the same type of 

battery ,do not attempt to replace the battery 

yourself.  

Utility is normal, but UPS status 

LED flashes. 

 

The power cord may not be 

connected properly. 

 

Connect the power cord securely into a wall outlet. 

 

3B

S

PECIFICATIONS

 

Model   

Liebert itON 1500 

Liebert itON 2000 

Capacity (VA/W) 

1500/900 

2000/1200 

Net Weight, lb. (kg) 

24 (11.1) 

25 (11.5) 

Dimensions – W x D x H (mm) 

146 x 391 x 205 

Line Input Nominal Voltage 

220 - 240VAC 

Line Input Voltage Range ** 

170 - 280VAC 

Line Frequency 

50Hz / 60Hz (auto sensing) 

Output Voltage (Utility Power Normal) 

230VAC 

Output Voltage (Battery Operation) 

±

10% 

On-Battery Wave Form 

Stepped sinewave 

Battery Type – VDC x Ah x Quantity 

12V x 9 Ah x 2 

12V x 9 Ah x 2 

Typical Recharge Time 

4 hours to 90% 

Battery Run Time* – Half Load 

5 minutes 

3 min 10 Sec 

Operating Temperature, 

°

F (

°

C) 

32 to 104 (0 to 40) 

Storage Temperature, 

°

F (

°

C) 

-4 to 122 (-20 to 50) 

Operating /Storage Relative Humidity 

0 – 90%, non-condensing 

 

*Battery run time may vary depending on load. 

** Depending of output load.

 

Emerson and Business-Critical Continuity are trademarks of Emerson Electric Co. or one of its affiliated companies.   
©2005 Emerson Electric Co.

 

Battery backup   

outlets  

(3 x IEC C13) 

LED 1 

(status) 

LED 3-6 (Load/Battery level)

On/Off button 

LED 2 (fault) 

USB interface 

Battery backup   

outlets  

(3 x Schuko)

AC mains inlet 

& fuse

RJ-11 jacks (2) 

Network surge 

protection 

All manuals and user guides at all-guides.com