Specifications
26
Table 10
Battery cabinet specifications
Model Number
GXT3-240TBATTCE
Dimensions, W x D x H, in. (mm)
Unit
31.5 x 11.81 x 26.57 (800 x 300 x 675)
Shipping
41.8 x 16.7 x 34 (1062 x 426 x 866)
Weight, lb (kg)
Unit
243 (110)
Shipping
309 (140)
Internal Battery Parameters
Type
Valve-regulated, non-spillable, lead acid
Quantity x V
2 x 20 x 12V
Battery Manufacturer, Part #
CSB HR1234R or Panasonic UP-RW1245
Temperature Limits, Batteries Only,
°F (°C)
32 to 104 (0 to 40)
Backup Time
Environmental
Operating Temp, °F (°C)
32 to 80 (0 to 27)
Storage Temp
5 to 104 (-15 to 40)
Transportation Temp, °F (°C)
5 to 122 (-15 to 50)
Relative Humidity
0-95% non-condensing
Operating Elevation
Up to 3281 ft (1000m) at 80°F (27°C) without derating
Agency
Safety
UL 1778, c-UL Listed
Transportation
ISTA Procedure 1B
Table 11
Typical battery run times for the Liebert
®
GXT3-10000T230
™
Number of Batteries,
Battery Cabinets
Load %
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Internal Battery
81
39
22
15
11
8
6
5
4
3
Internal B 1
External Battery Cabinet
190
127
81
60
46
39
32
26
22
18
Internal B 2
External Battery Cabinets
316
162
136
106
82
69
52
48
44
39
Approximate discharge times are at 77°F (25°C) with a 100% resistive load.
FOR
HISTORICAL
USE
ONLY