Liebert GXTMT Series Installation and User Manual
1-3 kVA UPS
Page
22
V2.11
Emerson Network Power
GXT 1000-MT
GXT 1000L-MT
GXT 2000-MT
GXT 2000L-MT
GXT 3000-MT
GXT 3000L-MT
Input system
Rated voltage
Voltage range
Frequency
Power factor
Output system
Power factor
Voltage
Line regulation
Dynamic variation
Frequency
Frequency range
Crest factor
Bypass operating voltage
Transfer time
DC component
Efficiency
1A
4A
1A
8A
1A
8A
Qty. ×Volts. ×Capacity
3×12V×7.2Ah
-
8X12X7.2Ah
-
8X12X7.2Ah
-
Manufacturer / model
CSB/GP1272F2
or Panasonic
equivalent
-
CSB/GP1272F2
or Panasonic
equivalent
-
CSB/HRL1234W
F2 or Panasonic
equivalent
-
Typical Autonomy Time
12 Minutes
-
15 Minutes
-
9 Minutes
-
Autonomy at Half Load
20 Minutes
-
26 Minutes
-
16 Minutes
-
Charging duration
Model
Electrical
Normal mode:
≥
88% (rated mains voltage, full linear load, battery fully charged)
IP20(static state)
Protection
Rating
Charging current
80~264V
Normal<
-
>Battery: 0ms
≤
200mV
GXT1000L-MT, GXT2000L-MT, GXT3000L-MT: <45db
External battery voltage
36Vdc
96Vdc
Noise (within 1m)
Battery
0.97 (conditions: rated voltage, full pure resistive load, fully charged battery)
1-phase, plus PE
0.7
50 / 60 Hz ±0.2Hz
1000VA/700W
2000VA/1400W
3000VA/2100W
1-phase, plus PE
80% of battery capacity in 4 hrs (standard type)
>150% 300ms
300% for 5s
220Vac / 230 Vac / 240 Vac ±2%
≤
2%(0~100% linear load)
≤
6%(0 ~100% non-linear load)
<5% in 20 ms
46-54 Hz / 56-64 Hz
>150% 300ms
3:1
Input
Output
≤
3%(0 ~100% linear load)
Inverter overload capability (in
Normal mode, 25°C)
108%~150% 30s
Inverter overload capability (in
Battery mode, 25°C)
108%~150% 30s
220Vac / 230Vac / 240 Vac
1. 160~300 Vac full load 2. 110 Vac half load
50/60 Hz
Bypass overload capability
200% for < 60 mins
Battery mode:
≥
83% (rated battery voltage, full linear load)
Voltage harmonic distortion
(rated input voltage, rated input
frequency)
Units with CE markings comply with the following standards:
1) For
GXT1000L-MT/ GXT1000L-MT / GXT1000L-MT
EN62040-1-1 (safety)
Conducted Emission: EN50091-2 ...................................................................Class B
Radiated Emission: EN50091-2 ......................................................................Class B
Harmonic Current: EN61000-3-2
Voltage Fluctuations and Flicker: EN61000-3-3
EMS: EN61000-4-2(ESD) ............................................................................... Level 4
EN61000-4-3(RS) .......................................................................................... Level 3
EN61000-4-4(EFT) .......................................................................................... Level 4
EN61000-4-5(lighting surge) ........................................................................... Level 4
EN61000-2-2 (Immunity to low frequency signals)