Advanced Microprocessor Controls Setup
7
3.3.5 Analog Sensors
The four (4) analog sensor inputs can be monitored from this submenu of Status/Alarm Data. The
inputs are filtered and displayed along with the text label assigned during setup. See
Analog
Setup on page 12
.
3.4
Main Menu (AM)—Setpoints/Setup
Selecting Setpoints/Setup from the Main Menu will display the following selections:
VIEW SETPOINTS
SETUP SYSTEM
RUN DIAGNOSTICS
CHANGE PASSWORDS
3.4.1 View Setpoints Selection
Control and alarm setpoints can be reviewed or changed with this submenu of Setpoints/Setup. The
following table lists the default setpoints and their allowable ranges.
3.4.2 Setup System Selection
The Setup System, a submenu of Setpoints/Setup, includes the following selections:
SETUP OPERATION
SELECT OPTIONS
CALIBRATE SENSORS
SHOW DIP SWITCHES
SELECT CONTROL TYPE
SETUP ALARMS
HUM CONTROL METHOD
ANALOG SETUP
SET STATUS DISPLAY
CALIBRATE ACTUATOR
NOTE
Setpoints and system setup parameters are kept in nonvolatile memory.
Table 1
Default control and alarm setpoints
Setpoint
Default
Range
Temperature Setpoint
72°F
40 to 90°F (5 to 32°C)
Temperature Sensitivity
2.0°F
1 to 9.9°F (0.6 to 5.6°C)
Humidity Setpoint
50%
20 to 80% RH
Humidity Sensitivity
5%
1 to 30% RH
High Temperature Alarm
80°F
35 to 95°F (2 to 35°C)
Low Temperature Alarm
65°F
35 to 95°F (2 to 35°C)
High Humidity Alarm
60%
15 to 85% RH
Low Humidity Alarm
40%
15 to 85% RH