May 2022
Installation, Operation and Maintenance Manual
VCIOM-01496-EN Rev. 0
8
Description Of OM3 Local Interface
Section 3: Description Of OM3 Local Interface
3.2
Description of the Local Interface
3.2.1
2-Position Selector
•
Local: to enable the local control only.
•
Remote: to enable the remote control and local control via Bluetooth with PC and PDA.
3.2.2
LEDs Indicating the Position of the EPI2 Actuator
The two LEDs indicate the actuator status according to the following logic:
Table 3.
Green LED
Red LED
Indication
ON
OFF
Actuator stopped in completely OPEN position
OFF
ON
Actuator stopped in completely CLOSED position
OFF
Flashing
Actuator running in CLOSING direction
Flashing
OFF
Actuator running in OPENING direction
ON
ON
Actuator stopped in INTERMEDIATE position
NOTES:
It is possible to invert LEDs color, so:
— red color for OPEN position and maneuver;
— green color for CLOSE position and maneuver.
To do this, see configuration section into Installation, Operation and Maintenance manual document.
It is also possible to invert LEDs color by means of Bluetooth optional connection (if present).
3.2.3
OPEN/CLOSE Pushbuttons
The two OPEN and CLOSE pushbuttons are push-to-run type only. Once the pushbuttons
are released, the actuator stops.