OM13 Wiring Diagram
Section 5: OM13 Wiring Diagram
Alternatively, to avoid induced voltage phenomena over floating command line, the
following wiring diagram may be used.
Figure 56
USE TO AVOID INDUCED VOLTAGE PHENOMENA
Monitor
Relay
Blinker/
Local Selector
Relay
CLC1
CLC2
OPC1
OPC2
Output Contacts
(Note 2-4)
MODULE 13 (3-WIRES)
(Note 1)
(Note 3)
G
rou
nd
NOTES:
1. Supply from 110 to 240 V AC / 1-ph
L2 neutral
When L1 - L2 - L3 cables are long (more than 10 metres) induced voltage phenomena may occur on
floating command line
To avoid this unwanted effect, realize a cabling system where unused line (either L1 OPEN or
L3 CLOSE) is pulled to NEUTRAL line. To do this, a switch may be used.
For example with the BACO PN NC02GQ1, the following configuration may be used:
short circuit
pins 1 and 3
short circuit
pins 5 and 7
short circuit
pins 2 and 8
short circuit
pins 4 and 6
pin 3 = PHASE
pin 5 = NEUTRAL (L2)
pin 2 = OPEN (L1)
pin 4 = CLOSE (L3)
2. Contacts shown in intermediate position CLC1 - CLC2 end of travel signaling in CLOSING
Contacts shown in intermediate position OPC1 - OPC2 end of travel signaling in OPENING
3. Internal heater (max. 10 watt) is activated when a power supply from 110 to 240 V AC is connected to the
terminals 33-344
4. Output contact rating: 240 V AC / 5 A - 30 V DC / 5 A - 120 V DC / 0.5 A