Emerson IC200EBI001 Important Product Information Download Page 9

 
GFK-1859S 

 

 

 

 

 

 

Nov 2020

 

 

 

PWR  Green indicates power is applied to the ENIU.   
RES 1 Reserved 
OK  During the power up initialization, this LED will be blinking Green. In Auto-configuration 
mode, power up initialization might take more time (based on the setup) compared to a module 
powering up with a stored configuration. 
Once the ENIU powers up successfully, OK LED remains solid Green indicating that  the ENIU 
firmware is operational.  
OK LED blinking Amber indicates a fatal error. 
FAULT  Amber indicates that ENIU has detected a fault with itself or an I/O module.  
FAULT LED blinking Red indicates an invalid or corrupted MAC address. 
LAN    Green  (solid  or  blinking)  indicates  network  packets  are  being  received  or  transmitted.  
Indicates received data addressed to ENIU as well as broadcast data. 
STAT - Modbus Mode.  Solid Green indicates a Modbus connection. Amber blinking at 1/sec rate 
indicates an IP address problem. 
STAT - EGD Mode.  Solid Green indicates exchanges are being received.  Amber blinking at 1/sec 
rate indicates an IP address problem. 
RES 2 Reserved 
RES 3 Reserved 

 

Installation in Hazardous Locations 

 

EQUIPMENT  LABELED  WITH  REFERENCE  TO  CLASS  I,  GROUPS  A,  B,  C  &  D,  DIV.  2  HAZARDOUS  LOCATIONS  IS 
SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C, D OR NON-HAZARDOUS LOCATIONS ONLY  
 

     

WARNING 

 

 

 

EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2; 

 

EXPLOSION  HAZARD  -  WHEN  IN  HAZARDOUS  LOCATIONS,  TURN  OFF  POWER  BEFORE  REPLACING  OR  WIRING 
MODULES; AND 

 

EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA 
IS KNOWN TO BE NONHAZARDOUS. 

 

General Module Installation Instructions  

Modules must be mounted on a horizontal DIN rail. 

1.

 

Allow sufficient finger clearance for opening ENIU door. 

2.

 

Allow adequate clearance for serial port cables. 

3.

 

Allow adequate space for power wiring. 

The ENIU with power supply attached fits into a 70mm deep enclosure.  
Rated thermal specifications are based on a clearance of 5.1cm (2in) above and below the equipment 
and 2.54cm (1in) to the left of the ENIU module. 
 

Panel-Mounting  

For best stability, the DIN rail should be installed on a panel using screws spaced approximately 5.24cm (6in) apart.  
If excessive vibration is a factor the ENIU should also be screwed down to the mounting panel.  

Note 1.

Tolerances are +/- 0.13mm (0.005in) non-cumulative. 

Note 2.

1.1-1.4Nm (10-12 in/lbs) of torque should be applied to M3.5 (#6-32) steel screw threaded into material containing 

internal threads and having a minimum thickness of 2.4mm (0.093in). 

Summary of Contents for IC200EBI001

Page 1: ...IMPORTANT PRODUCT INFORMATION GFK 1859S Nov 2020 PACSystemsTM VersaMax ETHERNET NETWORK INTERFACE UNIT ENIU IC200EBI001 ...

Page 2: ...mational purposes only and Emerson makes no warranty as to the accuracy of the information included herein Changes modifications and or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein It is understood that Emerson may make changes modifications or improvements to the equipment referenced herein or to the document itself at any...

Page 3: ...dicates an active Serial Console COMM LED indicates activity in USB serial port Number of I O modules IC200EBI001 MH later revisions support 64 I O modules and 7 expansion racks Power Consumption 5V at 600mA Product Revisions Catalogue Revision PM Firmware version 1 21 Firmware upgrades 41G2290 MS10 000 A4 Preinstallation Check Carefully inspect all shipping containers for damage If any equipment ...

Page 4: ...arrier must share the same external power source After a point fault occurs on an IC200MDL730A discrete input module two clear fault table commands must be sent to the VersaMax ENIU to clear the fault table and turn the Fault LED off This issue does not occur when using IC200MDL730B and later I O module hardware Using Extended Distance in a Multiple Remote Rack system may cause delays with some An...

Page 5: ... status of Read command from IC200CMM020 to IC200EBI001 appears as success in IC200EBI001 reference memory a minimum of 30ms is needed for data to be available in the reference memory of IC200CMM020 New Features or Enhacements in IC200EBI001 PL Primary FW 1 21 Subject Description None None Problems Resolved in IC200EBI001 PM Primary FW 1 21 Subject ID code Description ENIU enters 3 1 error blink s...

Page 6: ...Ethernet NIU which reflects Fault present status will not be successful The Modbus TCP second connection cannot be set for Read only mode Though user sets the second connection as Read Only in programmer it always operates in read write mode When a Modbus TCP communication is established between a Modbus master and ENIU STAT LED glows solid GREEN When ENIU communication with master is stopped or t...

Page 7: ...s of the ENIU IC200EBI001 MH or later can be set using a serial console User may connect a PC using USB Refer to Installing the USB Port Driver section in chapter 2 of VersaMax ENIU user s manual GFK 1860 before using the serial console using a standard micro USB cable Connectivity to the serial port is at following configuration BAUD 19200 Data bits 8 PARITY None Stop bits 1 Steps to open the ser...

Page 8: ...he I O station starting at Slot 1 Auto configuration stops at the first empty slot or faulted module If the auto configuration is unsuccessful or a new auto configuration is required it is necessary to first clear the existing configuration from the ENIU This is done by powering down the ENIU disconnecting the ENIU from the first I O carrier and powering up the ENIU Note If the I O station include...

Page 9: ...S A B C D DIV 2 HAZARDOUS LOCATIONS IS SUITABLE FOR USE IN CLASS I DIVISION 2 GROUPS A B C D OR NON HAZARDOUS LOCATIONS ONLY WARNING EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I DIVISION 2 EXPLOSION HAZARD WHEN IN HAZARDOUS LOCATIONS TURN OFF POWER BEFORE REPLACING OR WIRING MODULES AND EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OF...

Page 10: ...100Base TX connections with no termination Points can be hubs or switches If only 2 nodes are present a crossover cable should be used to connect them Point to point distance Maximum of 100 meters Medium Four twisted pair unshielded cable Shielding is permissible but not required Transmission Speed 10 Mbit s 10Base T or 100 Mbit s 100Base TX Connector RJ 45 Cable Type Category 5 Cat 5 Termination ...

Page 11: ...s the right to modify or improve the designs or specifications of the products mentioned in this manual at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson product remains solely with the purchaser 2019 Emerson All rights reserved Emerson Terms and Conditions of ...

Reviews: