RLDS Electrical Wiring
RLDS Installation • 15
3.5.1. Warnings and Cautions
• A switch or circuit breaker rated 1.0 A, 250 VAC
must be attached to the unit’s AC power leads.
• This switch must also be located in close proximity
to the monitor, and be within easy reach of the
operator.
• This switch should also be clearly marked as the
unit’s main AC disconnect device. The circuit
breaker or switch must disconnect all current-
carrying conductors (i.e., Live and Neutral).
WARNING: Electrical installation should be performed by a certified electrician and must comply with all
applicable local, state, and federal electrical safety codes.
WARNING: The AC power ground wire must first be connected to the monitor’s ground stud. Under no
circumstances should this monitor be operated without a protective ground. Doing so poses a potential shock
hazard, and is also a violation of electrical safety standards applicable to this type of equipment.
WARNING: Drilling holes in the RLDS enclosure may damage the unit and will void the warranty. Only use
the knockouts provided for electrical connections.
Figure 3-7
- RLDS AC Input Power and Ground Connections