8 • RLDS I&O Manual
026-1309 Rev 11
3
RLDS Installation
Standard accessories needed for a four (4)-point
System:
3.1. RLDS - Installation
Considerations
3.1.1. Warnings and Cautions
3.1.2. Inspection
The RLDS has been thoroughly inspected and tested
prior to shipment from the factory. Nevertheless, it is
recommended that the monitor be re-checked prior to
installation. Inspect the outside of the enclosure to
make sure there are no obvious signs of shipping
damage. Open the enclosure and inspect the interior
of the unit for loose components that may have
become dislodged during shipment. If damage is
discovered, please contact Technical Support for
assistance (
770-425-2724
).
3.1.3. Monitor Location
The RLDS should be centrally located in the facility
and should be easily accessible for visual monitoring
and servicing. Combined length of the intake sample
line and the exhaust line cannot exceed 1200 feet
(366 m) in length, but it is important to remember that
sampling cycle time is proportional to the total
number and length of individual sample lines.
Dirt, grease, and oils can adversely affect the
operation of the RLDS. The monitor should be
installed out of direct sunlight in a clean, dry area that
is not subject to temperature or humidity extremes.
Installation of the monitor in a mechanical room is
acceptable provided reasonable environmental
conditions exist. If there is a question, consider
installing the unit outside of the mechanical room in a
cleaner area of the facility.
Figure 3-1
- RLDS Diagram
Accessory
Part Number
Five (5) Line-End Filters
(Assembly)
275-0300
Charcoal Filter
275-0275
RLDS Instruction Manual
026-1309
Table 3-1
- RLDS Accessories and Part Numbers
WARNING: Explosion hazard! Do not mount
or operate this equipment in an area that may
contain or in the presence of flammable
liquids, vapors, or aerosols. Operation of any electrical
equipment in such an environment constitutes a safety
hazard.
WARNING: Shock hazard! Always disconnect
the AC power before working inside the
equipment.
CAUTION: Drilling holes in the RLDS
enclosure may damage the unit and will void
the warranty. Please use the knockouts
provided for electrical connections.
CAUTION: The RLDS contains sensitive
electronic components that can be easily
damaged. Do not to touch nor disturb any of
these components.
NOTE: The mounting location of the monitor
should allow it to be easily accessible for visual
monitoring and servicing.
Summary of Contents for GW-810-3760
Page 1: ...Refrigerant Leak Detection System RLDS Installation and Operation Manual 026 1309 Rev 11 ...
Page 37: ...30 RLDS I O Manual 026 1309 Rev 11 Figure 4 22 Connecting the Gateway to the RS485 Network ...
Page 84: ...Appendix B System Menu Map B 79 Appendix B System Menu Map ...