background image

2502 Series Controllers

Instruction Manual

Form 1446

November 2006

12

Differential Relief Adjustment

The differential relief valve protrudes from the back

of the controller case on a construction with an F in

the type number. Although normally factory-set to

relieve when the differential between the

proportional and reset bellows reaches 5 psi, the

differential may be reduced down to 2 psi by turning

the adjustment screw clockwise or increased up to 7

psi by turning the screw counterclockwise. The

minimum differential setting will yield the minimum

set point overshoot during startup.

Depending on the characteristics of the process, the

relief valve can be positioned so that the arrow cast

on the case points either to the letters RE (reset) or

to the letter P (proportional) on the back of the

manifold. To reposition the arrow, see figure 9.

Remove the mounting screws. Reposition the

differential relief valve to RE or P and reinstall the

mounting screws.

Calibration

Precalibration Requirements

Note

Calibration of a unit with a displacer

designed for interface or density

control must be conducted with the

displacer completely submerged in a

liquid of the specific gravity for which

the unit was designed.

To calibrate a controller, it is necessary to place the

device into operation. This may be done on the

vessel with the actual service liquid. It may also be

done in the shop, but other means of obtaining a

displacement force change must be provided. It

must be done in the shop if the process variable is

not available for calibration or if the process cannot

be varied for calibration. There are two methods of

adapting the calibration procedure to shop

calibration: wet and dry.

Wet Calibration

Remove the entire controller and sensor assembly

from the vessel. For caged sensors, pour the liquid

into the cage. For cageless sensors, suspend the

displacer to an appropriate depth in a liquid having a

specific gravity equal to that of the process liquid.

If necessary, use water for wet calibration in the

shop. However, this procedure requires

compensation for the difference between the specific

gravity of the water and that of the process liquids.

For example, assume that the process liquid has a

specific gravity of 0.7 and that wet calibration with

water (specific gravity of 1.0) is desired. To simulate

a process level of 50 percent of the input span, a

water level of 35 percent is required (0.7/1.0 x 50

percent = 35 percent).

Dry Calibration

Remove the controller and torque tube arm, as a

single unit, from the cage or vessel. Then, wherever

the standard calibration instructions in this manual

require a specific process variable for input to the

sensor, simulate that variable by suspending the

proper weight (such as a can of sand) from the end

of the displacer rod. Complete the following

Controller and Torque Tube Arm Disassembly and

the Determining Suspended Weight for Calibration

sections before proceeding to the calibration

procedure.

Controller and Torque Tube Arm

Disassembly

WARNING

To avoid personal injury from contact

with the process liquid, lower the

vessel level below the sensor torque

tube arm, or shut off the cage

equalizing valves and drain the cage

before proceeding. For closed vessels,

release any pressure that may be in

the vessel before removing the sensor

assembly.

When removing the displacer from the displacer rod

or removing the controller and torque tube arm from

the cage or vessel, refer to the appropriate sensor

instruction manual for assistance. The method of

removing the displacer or torque tube arm and

attached controller will vary with the type of sensor.

For a caged sensor with top equalizing connection, it

may be appropriate to remove the entire cage from

the vessel before disassembling.

Summary of Contents for Fisher Level-Trol 2502 Series

Page 1: ... Controller 15 Type 2502F Controller with Reset Relief Valve 17 Maintenance 18 Troubleshooting 18 Removing Controller from Sensor 18 Changing Mounting Method 20 Installing Controller on Sensor 20 Changing Proportional Reset or Differential Relief Valve 21 Testing Relay Dead Band 21 Changing Relay 21 TYPE 2502 CONTROLLER 249B SERIES SENSOR W8334 Figure 1 Type 2502 Controller Mounted on Type 249B Se...

Page 2: ... Trol Controller as well as a variety of other products contact Emerson Process Management Educational Services Registration P O Box 190 301 S 1st Ave Marshalltown IA 50158 2823 Phone 800 338 8155 or Phone 641 754 3771 Fax 641 754 3431 e mail education emersonprocess com Note Neither Emerson Emerson Process Management nor any of their affiliated entities assumes responsibility for the selection us...

Page 3: ...4 to 2 0 bar 6 to 30 psig output signal Maximum Supply Pressure 4 3 4 bar 50 psig Supply Pressure Consumption 5 At 1 4 bar 20 Psig Minimum 0 11 normal m3 h 4 2 scfh at proportional band setting of 0 or 200 percent Maximum 0 72 normal m3 h 27 scfh at proportional band setting of 100 percent At 2 4 bar 35 psig Minimum 0 2 normal m3 h 7 scfh at proportional band setting of 0 or 200 percent Maximum 1 ...

Page 4: ...NO INSULATOR NECESSARY AMBIENT TEMPERATURE _C STANDARD CONTROLLER OR TRANSMITTER AMBIENT TEMPERATURE _F HEAT INSULATOR REQUIRED TOO HOT NOTE FOR SERVICE BELOW 29_C 20_F CONTACT FACTORY PROCESS TEMPERATURE C _ PROCESS TEMPERATURE F _ B1413 1 IL 0 20 40 60 80 100 120 140 200 0 10 20 18 10 30 40 50 60 70 93 593 500 400 300 200 100 0 0 400 800 1100 20 29 NO INSULATOR NECESSARY AMBIENT TEMPERATURE _C H...

Page 5: ...or assembly A displacer longer than 813 mm 32 inches is crated separately A shorter displacer is crated with the sensor but is 1 4 18 NPT SUPPLY CONNECTION ADJUSTING SCREW DRAIN VALVE LOCKNUT 1 4 18 NPT OUTPUT CONNECTION VENT PRESSURE REGULATOR Figure 3 Pressure Connections not attached to the displacer rod Inspect the displacer and replace if it is dented A dent may reduce the pressure rating of ...

Page 6: ...ge connections will normally be either 1 1 2 or 2 inch screwed or flanged Figure 5 shows the combinations With flanged connections use standard gaskets or other flat sheet gaskets compatible with the process liquid Spiral wound gaskets without compression controlling centering rings cannot be used for flanged connections Mount the cage by running equalizing lines between the cage connections and t...

Page 7: ...t an erroneous output signal Since the displacer hangs inside the vessel provide a stillwell around the displacer if the liquid is in a state of continuous agitation to avoid excessive turbulence around the displacer Note Displacers used in an interface level application must be completely submerged during operation If displacers aren t completely submerged they will not calibrate or perform prope...

Page 8: ...el connection The displacer may then be swung out horizontally for insertion into the vessel However once the sensor is installed and the displacer drops to a vertical position the displacer may not be capable of being withdrawn for servicing later Be sure there is another access to the displacer to permit swinging it to a horizontal position or to permit disconnecting it from the displacer rod W0...

Page 9: ... pressure and check all connections for leaks Prestartup Checks WARNING The following procedure requires taking the controller out of service To avoid personal injury and property damage caused by an uncontrolled process provide some temporary means of control for the process before taking the controller out of service Adjustment locations are shown in figure 9 unless otherwise indicted When perfo...

Page 10: ...r Adjustments 1 Turn on the supply pressure and check that the controller supply gauge reads 1 4 bar 20 psig for a 0 2 to 1 0 bar 3 to 15 psig output pressure range or 2 4 bar 35 psig for a 0 4 to 2 0 bar 6 to 30 psig output pressure range If the pressure is incorrect loosen the locknut of the filter regulator figure 3 turn the adjusting screw clockwise to increase or counterclockwise to decrease ...

Page 11: ...he unit would appear to be out of calibration and recalibration may be desirable See the Calibration Procedure on page 14 On a controller with level indicator the pointer should reflect the magnitude of the process variable for instance with liquid or interface level covering 50 percent of the displacer the pointer should be in the middle of the high low scale Slight plate adjustment might be nece...

Page 12: ...sel For caged sensors pour the liquid into the cage For cageless sensors suspend the displacer to an appropriate depth in a liquid having a specific gravity equal to that of the process liquid If necessary use water for wet calibration in the shop However this procedure requires compensation for the difference between the specific gravity of the water and that of the process liquids For example as...

Page 13: ...ondition of liquid level or specific gravity solve the following equation Ws Wd 0 0361 V SP GR where Ws Total suspended weight in pounds should never be less than 0 5 pounds For a unit with a horizontal displacer make sure the center of gravity of the substitute weight is where it would be on the actual displacer Note For liquid level control only simulate the lower range limit of the input span b...

Page 14: ...Rotate the reset knob to 0 01 minutes per repeat 3 Rotate the proportional band knob to zero 4 Set the liquid at the minimum limit dry displacer 5 Turn the RAISE LEVEL knob to zero 6 Adjust the nozzle until output pressure is between 0 and 0 2 bar for a 0 2 to 1 0 bar signal range 0 and 3 psig for a 3 to 15 psig signal range or 0 and 0 4 bar for a 0 4 to 2 0 bar signal range 0 and 6 psig for a 6 t...

Page 15: ...roller which uses a nozzle bellows and pneumatic relay to convert the rotary motion to a standard pneumatic output signal The output signal is sent to a final control element In conjunction with this control element 2502 249 Series controller sensors are capable of bringing the controlled variable back to a specific control point all the time The following descriptions show how the relay works in ...

Page 16: ...OT BEAM AND FLAPPER CAM RESET VALVE PROPORTIONAL VALVE FIXED RESTRICTION EXHAUST END OF RELAY VALVE LARGE DIAPHRAGM OF ASSEMBLY SMALL DIAPHRAGM OF ASSEMBLY INLET END OF RELAY VALVE SUPPLY PRESSURE REGULATOR DIRECT ACTING DIAPHRAGM CONTROL VALVE VESSEL INFLOW PROPORTIONAL PRESSURE SUPPLY PRESSURE OUTPUT PRESSURE NOZZLE PRESSURE RESET PRESSURE EXHAUST NOZZLE Figure 10 Direct Acting Right Hand Mounte...

Page 17: ...ssure into a reset bellows that opposes proportional bellows action This automatically dampens the effect of any proportional overcorrection by a set amount per time interval as long as there is a deviation from the control point Figure 10 illustrates these principles at work in a direct acting right hand mounted construction controlling liquid inflow to a vessel by means of a direct acting diaphr...

Page 18: ...sult from fire or explosion if preventative measures are not taken such as adequate ventilation and the removal of any ignition sources Check with your process or safety engineer for any additional measures that must be taken to protect against process media Troubleshooting When troubleshooting open loop conditions must exist unless otherwise stated When monitoring the process variable use the mos...

Page 19: ... 4 Flapper adjustment 2 4 Insure the flapper is not loose on the torque tube shaft and is centered on the nozzle 2 4 Replace or tighten flapper assembly as necessary and or center flapper on nozzle 2 5 Process variable changed 2 5 Insure the process variable has not changed from original calibration settings or displacer not design specific gravity of process 2 5 Change process variable back to or...

Page 20: ...que tube arm in the opposite position according to the appropriate instruction manual 3 Check the desired control action to determine if it is also necessary to reverse the controller action The nozzle block and bellows tubing should be arranged in the proper position as shown in figure 13 4 Remove the RAISE LEVEL dial turn it over and install it in the desired position The arrow on it under the w...

Page 21: ...band 2 To change the reset restriction valve assembly key 91 remove the two mounting screws key 182 located on the back side of case Install the replacement valve assembly and reconnect the tubing connections 3 Remove the differential relief valve assembly key 186 figure 14 by removing the two mounting screws figure 9 that anchor the valve to the manifold key 184 figure 14 Install the valve with t...

Page 22: ...to the bellows frame Unscrew each bellows from the spacer key 98 being careful not to lose the O ring key 57 not shown from the spacer end of the bellows 3 Inspect each bellows and O ring and replace if necessary using an unpainted bellows for a 0 2 to 1 0 bar 3 to 15 psig range and a red bellows for a 0 4 to 2 0 bar 6 to 30 psig range Be sure to install the O ring at the spacer end of the bellows...

Page 23: ...ponsibility for the selection use and maintenance of any product remains with the purchaser and end user Parts Kits Description Part Number Controller Parts Kit Contains keys 12 15 21 24 38 55 57 58 60 62 63 64 77 79 84 86 87 93 101 and 187 Standard Temperature R2502X00L52 High Temperature R2502X00H52 Relay Replacement Kit Contains keys 22 43 and the relay assembly Standard Temperature RRELAYX0L22...

Page 24: ...2502 Series Controllers Instruction Manual Form 1446 November 2006 24 30A8942 H DOC 43A2366 H DOC 30A8943 H DOC Figure 14 2502 Series Controller Constructions ...

Page 25: ...l 1U639135132 59 Beam steel pl 1K873825072 60 Flapper K93600 alloy 1J416241132 61 Flapper Base stainless steel 1J416335032 62 Connecting Link N04400 1L379641012 63 Sealing Screw stainless steel 14A5721X012 64 Screw stainless steel 24A5720X012 65 Bellows Ass y brass 2 req d 0 2 to 1 0 bar 3 to 15 psig 14A5726X012 0 4 to 2 0 bar 6 to 30 psig 14A5726X032 66 Level Set Arm steel pl 1J416425072 67 Opera...

Page 26: ...2F and 2502FC 1D6875X0132 184 Manifold aluminum Type 2502F and 2502FC 23A2072X012 185 Manifold Nipple aluminum Type 2502F and 2502FC 13A2074X012 Key Description Part Number 186 Differential Relief Valve Ass y Types 2502F and 2502FC Standard 21A6447X0A2 High temperature 21A6447X012 187 Sleeve plastic 16A0976X012 188 0 Ring Types 2502F and 2502FC 1C8538X0132 215 Nameplate metal Pipe Plug Types 2502 ...

Page 27: ...2502 Series Controllers Instruction Manual Form 1446 November 2006 27 ...

Page 28: ... designs or specifications of such products at any time without notice Neither Emerson Emerson Process Management nor any of their affiliated entities assumes responsibility for the selection use and maintenance of any product Responsibility for the selection use and maintenance of any product remains with the purchaser and end user EFisher Controls International LLC 1977 2006 All Rights Reserved ...

Reviews: