Instruction Manual
D103531X012
L2e Controller
June 2022
5
1. Be sure there are no obstructions inside the vessel that will interfere with displacer installation or operation.
2. Provide the appropriate connection in the vessel wall to match the sensor connection. Locate the vessel wall
connection such that the displacer will be at the desired control level.
Attaching a Vertical Displacer
Refer to figure 12 for part locations.
1. Thread jam nut (key 63) all the way onto the threaded portion of the universal joint assembly (key 69).
2. Thread the displacer (key 81) all the way onto the threaded portion of the universal joint assembly.
3. Tighten the jam nut against the displacer.
Attaching a Horizontal Displacer
Refer to figure 12 for part locations.
1. Thread the displacer (key 81) all the way onto the displacer rod (key 64) or extension (key 82) and tighten.
Attaching the Sensor to the Vessel
Insert the displacer end of the L2e sensor into the vessel connection and tighten enough to seal the threads. If
necessary, loosen or tighten slightly to obtain the horizontal orientation shown in figure 2. Make sure that the
controller case is level.
NOTICE
The displacer rod (key 64) is not a handle. Grasp sensor body or controller housing to lift and carry to avoid internal
component damage.
Figure 2. Sensor Orientation
CORRECT CONTROLLER MOUNTING
HOLE ORIENTATION WHEN MOUNTED ON VESSEL
A6639