Single Point Calibration
Fisher

 FIELDVUE

 DVC6200 HW2 Digital Valve

Controller

The Single Point Calibration procedure allows you to replace an existing positioner with a DVC6200 HW2, on
sliding-stem applications, without performing a travel calibration. This procedure should only be used in emergency
situations where a positioner must be completely replaced and is part of a valve assembly that does not have a process
bypass or the process cannot be shut down. For other procedures, refer to the DVC6200 Quick Start Guide and the
DVC6200 HW2 Instruction Manual.

Related Documents

D

 Fisher FIELDVUE DVC6200 Series Digital Valve Controllers Quick Start Guide (

D103566X012

)

D

 Fisher FIELDVUE DVC6200 HW2 Digital Valve Controller Instruction Manual (

D103605X012

)

These documents are available from your 

Emerson sales office

 or at Fisher.com.

  WARNING

Personal injury or property damage, caused by unexpected valve movement and an uncontrolled process, could result if
this procedure is attempted when the valve is not locked at its present position. If you cannot safely lock the valve in
position until this procedure is complete, do not proceed with this procedure.

Notes

This procedure should only be used in emergency situations where a positioner must be completely replaced and is part of a valve
assembly that does not have a process bypass or the process cannot be shut down. Do not proceed if the valve has a bypass or the
process can be shut down.

The valve will need to be locked at its present position. This can be accomplished by using a handwheel or other mechanism. If the
valve assembly or valve application will not allow you to safely lock the valve in position until this procedure is complete, do not
proceed with this procedure.

This procedure can be used to replace a positioner with a DVC6200. The DVC6200 used to replace the existing positioner must
have firmware 2, 3, 4, 5, 6, or 7, hardware 2 and HC, AD, or PD diagnostic tiering. Do not proceed with this procedure if the digital
valve controller does not meet the tiering and firmware requirements mentioned above.

This procedure can only be performed on sliding-stem valve assemblies and only supports feedback connections using the linear
sliding-stem arrays. This procedure cannot be performed with a long stroke roller array. Do not proceed if you have something
other than a sliding-stem valve assembly with a linear sliding-stem array.

The Single Point Calibration procedure cannot be completed with Pressure Control. Do not proceed with this procedure if the
Travel/Pressure Control Mode is Pressure.

This procedure is not recommended for a valve assembly with a double-acting actuator that uses a DVC6200 with a Relay A that
was previously configured for a valve assembly with a single-acting actuator.

This procedure requires the use of ValveLink

 software 13.5 or newer.

DVC6200 Digital Valve Controller

January 2020

Instruction Manual Supplement

D104490X012

Summary of Contents for Fisher FIELDVUE DVC6200 HW2

Page 1: ...cannot be shut down Do not proceed if the valve has a bypass or the process can be shut down The valve will need to be locked at its present position This can be accomplished by using a handwheel or other mechanism If the valve assembly or valve application will not allow you to safely lock the valve in position until this procedure is complete do not proceed with this procedure This procedure can...

Page 2: ...Do not proceed with this procedure until you have obtained a mounting kit compatible with the replacement DVC6200 and the control valve assembly 1 2 Block the valve into position either with a handwheel or other mechanism If you cannot safely lock the valve in position until this procedure is complete do not proceed with this procedure 1 3 Disconnect the operating lines that provide air pressure t...

Page 3: ... if the Tvl Dev Press Fallback setting is exceeded for more than the Tvl Dev Press Fallback Time D Relay Type The relay type is printed on the label affixed to the relay body d A double acting or single acting d B single acting reverse d C single acting direct Note The Single Point Calibration procedure cannot be completed with Pressure Control Do not proceed with this procedure if the Travel Pres...

Page 4: ...alibration process cannot be started if air is supplied to the instrument 3 5 Attach pneumatic and electrical operating lines to the replacement digital valve controller but Do Not Turn On Air Supply D Measure and record the valve assembly s Observed Travel Observed Travel is the current position of the valve as a percentage of the actual travel 4 Run Single Point Calibration 4 1 In ValveLink soft...

Page 5: ...is resupplied Once the travel setpoint matches travel click Next 4 9 Reintroduce instrument air pressure to the digital valve controller The air pressure supplied will be shown on the dial graphic on the Air Screen Once you ve confirmed instrument air has been supplied click Next WARNING Refer to the Installation Warning on page 2 4 10 On the resulting Finish Screen adjust the Travel Setpoint to r...

Page 6: ...ons which are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice E 2020 Fisher Controls International LLC All rights reserved Fisher FIELDVUE and ValveLink are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co Emerson Automation Solutions Emerson and th...

Reviews: