background image

Instruction Manual

D102005X012

846 Transducer

February 2021

3

Table 1. Specifications

Input Signal

Standard Performance:

4 to 20 mA DC, 4 to 12 mA DC, or 12 to 20 mA DC.
Field adjustable split ranging.

Multirange Performance:

4 to 20 mA DC. Consult factory for split range input

Equivalent Circuit

See figure 3

Output Signal

(1)

Standard Performance:

(Consult factory for split range output)

Direct Action (Minimum span of 6 psi)

Typical outputs: 0.2 to 1.0 bar (3 to 15 psi).
Rangeability between 0.1 and 1.2 bar (1 and 18 psi)

Reverse Action (Minimum span of 11 psi)

Typical outputs: 1.0 to 0.2 bar (15 to 3 psi)
Rangeability between 1.2 and 0.1 bar (18 and 1 psi)

Multirange Performance:
Direct Action (Minimum span of 6 psi)

Typical outputs:

 

0.2 to 1.9 bar (3 to 27 psi), 0.4 to 

2 bar (6 to 30 psi), and 0.3 to 1.7 bar (5 to 25 psi)
Rangeability between 0.03 and 2.3 bar (0.5 and 
33 psi)

Reverse Action (Minimum span of 11 psi)

Typical outputs: 1.9 to 0.2 bar (27 to 3 psi), 2 to 
0.4 bar (30 to 6 psi), and 1.7 to 0.3 bar (25 to 5 psi)
Rangeability between 2.3 and 0.03 bar (33 and 
0.5 psi)

Supply Pressure

(2)

Standard Performance: 

1.2 to 1.6 bar (18 to 24 psi)

Multirange Performance: 

0.2 bar (3 psi)

(3)

 greater than the maximum

calibrated output pressure

Maximum:

 2.4 bar (35 psi)

Supply Pressure Medium

Clean, dry air

Per ISA Standard 7.0.01

A maximum 40 micrometer particle size in the air
system is acceptable. Further filtration down to 5
micrometer particle size is recommended. Lubricant
content is not to exceed 1 ppm weight (w/w) or
volume (v/v) basis. Condensation in the air supply
should be minimized

Per ISO 8573-1

Maximum particle density size:

 Class 7

Oil content:

 Class 3

Pressure Dew Point: 

Class 3 or at least 10°C less than

the lowest ambient temperature expected

Output Air Capacity

(4)

Standard:

 6.4 m

3

/hr (240 scfh) at 1.4 bar 

(20 psi) supply pressure

Multirange:

 9.7 m

3

/hr (360 scfh) at 2.5 bar

(35 psig) supply pressure

Maximum Steady‐State Air Consumption

(4)

0.3 m

3

/hr (12 scfh) at 1.4 bar (20 psi) supply pressure

Temperature Limits

(2)

Operating:

 -40 to 85

_

C (-40 to 185

_

F)

Storage

 

:

-40 to 93

_

C (-40 to 200

_

F)

Humidity Limits

0 to 100% condensing relative humidity

Performance

(5)

Note: The performance of all 846 I/Ps is verified
using computer automated manufacturing systems
to ensure that every unit shipped meets its
performance specifications

Accuracy:

 

$

0.30% of output span

Linearity, Hysteresis, and Repeatability:

 

$

0.3% of

span.

Temperature Effect (total effect including zero and
span): 

$

0.07%/

_

C (0.045%/

_

F) of span

Vibration Effect: 

$

0.3% of span per g during the

following conditions:
5 to 15 Hz at 4 mm constant displacement
15 to 150 Hz at 2 g. 150 to 2000 Hz at 1 g.
per SAMA Standard PMC 31.1, Sec. 5.3, Condition 3,
Steady State

Shock Effect: 

$

0.5% of span, when tested per SAMA

Standard PMC 31.1, Sec. 5.4.

Supply Pressure Effect:

 Negligible

-Continued-

Summary of Contents for Fisher 846

Page 1: ...n 21 4 to 12 mA Input Signal 21 12 to 20 mA Input Signal 21 Transporting the Module Final Assembly 22 Principle of Operation 22 Electronic Circuit 22 Magnetic Actuator 23 Pilot Stage 23 Booster Stage 24 Troubleshooting 25 Diagnostic Features 25 Stroke Port 25 Figure 1 Fisher 846 Current to Pressure Transducer X0234 Remote Pressure Reading RPR 25 Using a Frequency Counter to read the RPR Signal 25 ...

Page 2: ...uce a pneumatic output for operating a control valve actuator or positioner The 846 may also be used to produce a signal for a pneumatic receiving instrument The 846 is an electronic I P transducer It has a single electronic circuit board as shown in figure 2 The circuit contains a solid state pressure sensor that monitors output pressure and is part of an electronic feedback network The self corr...

Page 3: ... 01 A maximum 40 micrometer particle size in the air system is acceptable Further filtration down to 5 micrometer particle size is recommended Lubricant content is not to exceed 1 ppm weight w w or volume v v basis Condensation in the air supply should be minimized Per ISO 8573 1 Maximum particle density size Class 7 Oil content Class 3 Pressure Dew Point Class 3 or at least 10 C less than the low...

Page 4: ...tage with Remote Pressure Reading On Min 6 4 V at 4 mA Max 8 2 V at 20 mA Electrical Classification Hazardous area CSA C US Intrinsically Safe Explosion proof Non Incendive FM Intrinsically Safe Explosion proof Non Incendive ATEX Intrinsically Safe Flameproof Type n IECEx Intrinsically Safe Flameproof Electrical Housing Tropicalization Fungus test per MIL STD 810 CSA C US Type 4X FM Type 4X ATEX I...

Reviews: