Introduction

This installation guide provides instructions for 

installation, startup and adjustment. To receive a copy 

of the Instruction Manual, contact your local Sales 

Office or view a copy at www.fisher.com. For further 

information refer to: 67C Series Instruction Manual, 

form 5469, D102601X012.

P.E.D. Category

This product may be used as a safety accessory with 

pressure equipment in the following Pressure Equipment 

Directive categories. It may also be used outside of the 

Pressure Equipment Directive using sound engineering 

practice (SEP) per table below. For information on the 

current PED revision see Bulletin: 

D103053X012

.

ProDuCt sIzE

CatEgorY

fluID tYPE

1/4 NPT

SEP

1

Specifications

Body size and End Connection style

1/4 NPT

Maximum Inlet Pressure (Body Rating)

(1)

17.2 bar / 250 psig

Maximum Emergency Outlet Pressure

(1)

3.4 bar / 50 psig over outlet pressure setting

Proof Test Pressure

All Pressure Retaining Components have been 

proof tested per PED

Outlet Pressure Ranges

(1)

 

 

0 to 1.4 bar / 0 to 20 psig 

 

0 to 2.4 bar / 0 to 35 psig 

 

0 to 4.1 bar / 0 to 60 psig 

 

0 to 8.6 bar / 0 to 125 psig

Temperature Capabilities

(1)

With Nitrile (NBR): 

Standard Bolting: 

-29 to 82°C / -20 to 180°F

Stainless Steel Bolting: 

-40 to 82°C / -40 to 180°F

With Fluorocarbon (FKM): 

Polyethylene Filter

(3)

 

(Standard)

:

 

-18 to 82°C /  

0 to 180°F

Polyvinylidene (PVDF), Stainless steel or Glass Filter 

(Optional): 

-18 to 149°C / 0 to 300°F

With Silicone (VMQ)

(2)

 Diaphragm and low 

Temperature bolting: 

-51 to 82°C / -60 to 180°F

With Gauges: 

-40 to 82°C / -40 to 180°F

Installation

!

WarnIng

Only qualified personnel should install 

or service a regulator. Regulators should 

be installed, operated and maintained 

in accordance with international and 

applicable codes and regulations and 

Emerson Process Management Regulator 

Technologies Inc. instructions.
If the regulator vents fluid or a leak 

develops in the system, it indicates that 

service is required. Failure to take the 

regulator out of service immediately may 

create a hazardous condition.
Personal injury, equipment damage 

or leakage due to escaping fluid 

or bursting of pressure-containing 

parts may result if this regulator is 

overpressured or is installed where 

service conditions could exceed the 

limits given in the Specifications 

section or where conditions exceed 

 

any ratings of the adjacent piping or 

piping connections. 
To avoid such injury or damage, 

provide pressure-relieving or pressure-

limiting devices (as required by 

the appropriate code, regulation or 

standard) to prevent service conditions 

from exceeding limits.
Additionally, physical damage to the 

regulator could result in personal injury 

and property damage due to escaping 

fluid. To avoid such injury and damage, 

install the regulator in a safe location.
The internal relief valve in the 67C Series 

regulators does not provide full 

overpressure protection. The internal 

relief valve is designed for minor seat 

leakage only.

Clean out all pipelines before installation of the 

regulator and check to be sure the regulator has not 

been damaged or has collected foreign material during 

shipping. For NPT bodies, apply pipe compound to 

the external pipe threads. For flanged bodies, use 

suitable line gaskets and approved piping and bolting 

1. The pressure/temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded.

2. Silicone (VMQ) is not compatible with hydrocarbon gas. 

3. Do not use in high aromatic hydrocarbon service.

67C and 67CF Series

Installation Guide

D102601X014
English – March 2017

Summary of Contents for Fisher 67C

Page 1: ...rdance with international and applicable codes and regulations and Emerson Process Management Regulator Technologies Inc instructions If the regulator vents fluid or a leak develops in the system it indicates that service is required Failure to take the regulator out of service immediately may create a hazardous condition Personal injury equipment damage or leakage due to escaping fluid or burstin...

Page 2: ...int of the spring range or the pressure requested so an initial adjustment may be required to give the desired results With proper installation completed and relief valves properly adjusted slowly open the upstream and downstream shutoff valves Parts List Key Description 1 Body 2 Drain Valve 3 Flange Screw 4 O ring 5 Dripwell 6 Filter Element 7 Spring Case Assembly 9 Filter Retainer 10 1 Valve Car...

Page 3: ...llation IN 34 B2697 SPACER SPACER OUTER DIAMETER 13 0 50 OD SPACER WIDTH AND INNER DIAMETER 8 1 0 32 4 6 0 18 ID T14123 17 10 26 6 4 3 9 5 13 37 2 12 11 14 L1 15 1 20 31 18 L2 apply lubricant l T40580 L1 MULTI PURPOSE POLYTETRAFLUOROETHYLENE PTFE LUBRICANT L2 ANTI SEIZE COMPOUND 67C and 67CF Series 3 ...

Page 4: ... Process Management Regulator Technologies Inc All rights reserved 05 17 The Emerson logo is a trademark and service mark of Emerson Electric Co All other marks are the property of their prospective owners Fisher is a mark owned by Fisher Controls International LLC a business of Emerson Automation Solutions The contents of this publication are presented for information purposes only and while effo...

Reviews: