background image

0X00119-F

Figure 1.

 Spring-Loaded Type 630 Regulator - Low-Pressure Construction 

REGULATOR 

CONSTRUCTION

RELIEf (INLET) PRESSURE SETTINGS

MAXIMUM ALLOWABLE RELIEf  

(INLET) PRESSURE

MAXIMUM EMERGENCY INLET  

(CASING) PRESSURE

(1)

bar

psig

bar

psig

Low-Pressure

0.21 to 0.55

0.41 to 1.2

1.0 to 1.5

1.4 to 2.4

2.4 to 3.5

3 to 8

6 to 17

15 to 22

20 to 35

35 to 50

Relief Pressure Setting Plus Maximum 

Allowable Build-up of 

1.7 bar / 25 psig

5.2

75

High-Pressure

2.1 to 4.8

3.5 to 6.6

5.2 to 12.1

10.3 to 17.2

30 to 70

50 to 95

75 to 175

150 to 250

Relief Pressure Setting Plus

Maximum Allowable Build-up of

17.2 bar / 250 psig

37.9

550

1.  Leakage or bursting of pressure-containing parts may occur if inlet pressure exceeds these values. 

Table 3.

 Type 630R Relief Pressure Ranges

Startup

The regulator is factory set at approximately 

the midpoint of the spring range or the pressure 

requested, so an initial adjustment may be required 

to give the desired results. With proper installation 

completed and relief valves properly adjusted, slowly 

open the upstream and downstream shutoff valves.

 

Adjustment

To change the set pressure, remove the closing 

cap or loosen the locknut and turn the adjusting 

screw clockwise to increase set pressure or 

counterclockwise to decrease pressure. Monitor the 

set pressure with a test gauge during the adjustment. 

Replace the closing cap or tighten the locknut to 

maintain the desired setting.

Taking Out of Service (Shutdown)

!

To avoid personal injury resulting from 

sudden release of pressure, isolate 

the regulator from all pressure before 

attempting disassembly.

30

8

7

9

6

5

4

3

2

1

10

9

11

12

13

14

15

16

17

18

19

20

21

22

23

27

34

35

A

630 Series

3

Summary of Contents for Fisher 630 Series

Page 1: ...stalled operated and maintained in accordance with international and applicable codes and regulations and Emerson Process Management Regulator Technologies Inc instructions If the regulator vents fluid or a leak develops in the system it indicates that service is required Failure to take the regulator out of service immediately may create a hazardous condition Personal injury equipment damage or l...

Page 2: ... loaded constructions have a screened vent assembly key 27 Figures 1 2 and 3 installed in the 1 4 NPT spring case vent opening If a remote vent is required remove the vent assembly and install a remote vent line Overpressure Protection The recommended pressure limitations are stamped on the regulator nameplate Some type of overpressure protection is needed if the actual inlet pressure exceeds the ...

Page 3: ...e 630R Relief Pressure Ranges Startup The regulator is factory set at approximately the midpoint of the spring range or the pressure requested so an initial adjustment may be required to give the desired results With proper installation completed and relief valves properly adjusted slowly open the upstream and downstream shutoff valves Adjustment To change the set pressure remove the closing cap o...

Page 4: ...om emr_automation Webadmin Regulators emerson com Emerson Automation Solutions For further information on the current PED revision see Bulletin D103053X012 or scan the QR code Fisher com Americas McKinney Texas 75070 USA T 1 800 558 5853 1 972 548 3574 Europe Bologna 40013 Italy T 39 051 419 0611 Asia Pacific Singapore 128461 Singapore T 65 6777 8211 Middle East and Africa Dubai United Arab Emirat...

Reviews: