Introduction

This installation guide provides instructions for installation, 

startup and adjustment. To receive a copy of the 

instruction manual, contact your local Sales Office or view 

a copy at www.fisher.com. For further information refer to: 

630 Series Instruction Manual, D100300X012.

PED Categories

This product may be used as a safety accessory with 

pressure equipment in the following Pressure Equipment 

Directive categories. It may also be used outside of the 

Pressure Equipment Directive using sound engineering 

practice (SEP) per table below. For information on the 

current PED revision see Bulletin: 

D103053X012

.

PRODUCT SIZE

CATEGORIES

DN 25 / NPS 1

SEP

Specifications

Available Configurations

Type 630:

 Spring-loaded reducing regulators

Type 630R:

 Spring-loaded relief valves

Body Size and End Connection Style

DN 25 and 50 / 1 and 2 in.

End Connection Style

NPT, ASME CL150 RF, CL300 RF or CL600 RF

Maximum Allowable Inlet Pressures

(1)

Type 630 Regulators:

 See Table 1

Type 630R relief Valves:

 See Table 3

Type 630 Outlet Pressure Ranges

(1)

0.21 to 34.5 bar / 3 to 500 psig with intermediate 

values shown in Table 2

Type 630R Relief Pressure Ranges

(1)

0.21 to 17.2 bar / 3 to 250 psig

See Table 3

Maximum Allowable Outlet Pressures

(1)

See Table 2

Maximum Allowable Pressure Drops

(1)

See Table 1

Temperature Capabilities

(1)

Standard:

 -29 to 82°C / -20 to 180°F

Optional:

 -29 to 149°C / -20 to 300°F

Orifice Sizes

3.2 mm / 1/8 in., 4.8 mm / 3/16 in., 6.4 mm / 1/4 in., 

9.5 mm / 3/8 in. or 13 mm / 1/2 in.

Installation 

!

Only qualified personnel should install 

or service a regulator. Regulators 

should be installed, operated and 

maintained in accordance with 

international and applicable codes 

and regulations and Emerson Process 

Management Regulator Technologies, 

Inc. instructions.

If the regulator vents fluid or a leak 

develops in the system, it indicates that 

service is required. Failure to take the 

regulator out of service immediately may 

create a hazardous condition.
Personal injury, equipment damage, or 

leakage due to escaping fluid or bursting 

of pressure-containing parts may result 

if this regulator is overpressured or 

is installed where service conditions 

could exceed the limits given in the 

Specifications section, or where 

conditions exceed any ratings of the 

adjacent piping or piping connections.

To avoid such injury or damage, provide 

pressure-relieving or pressure-limiting 

devices (as required by the appropriate 

code, regulation or standard) to prevent 

service conditions from exceeding limits.

Additionally, physical damage to the 

regulator could result in personal injury 

and property damage due to escaping 

fluid. To avoid such injury and damage, 

install the regulator in a safe location.

Clean out all pipelines before installation of the 

regulator and check to be sure the regulator has not 

been damaged or has collected foreign material during 

shipping. For NPT bodies, apply pipe compound to the 

external pipe threads. For flanged bodies, use suitable 

line gaskets and approved piping and bolting practices. 

Install the regulator in any position desired, unless 

otherwise specified, but be sure flow through the body 

is in the direction indicated by the arrow on the body.

1. The pressure/temperature limits in this installation guide or any applicable standard limitation should not be exceeded.

630 Series

Installation Guide

D100300X014
English – December 2015

Summary of Contents for Fisher 630 Series

Page 1: ...stalled operated and maintained in accordance with international and applicable codes and regulations and Emerson Process Management Regulator Technologies Inc instructions If the regulator vents fluid or a leak develops in the system it indicates that service is required Failure to take the regulator out of service immediately may create a hazardous condition Personal injury equipment damage or l...

Page 2: ... loaded constructions have a screened vent assembly key 27 Figures 1 2 and 3 installed in the 1 4 NPT spring case vent opening If a remote vent is required remove the vent assembly and install a remote vent line Overpressure Protection The recommended pressure limitations are stamped on the regulator nameplate Some type of overpressure protection is needed if the actual inlet pressure exceeds the ...

Page 3: ...e 630R Relief Pressure Ranges Startup The regulator is factory set at approximately the midpoint of the spring range or the pressure requested so an initial adjustment may be required to give the desired results With proper installation completed and relief valves properly adjusted slowly open the upstream and downstream shutoff valves Adjustment To change the set pressure remove the closing cap o...

Page 4: ...om emr_automation Webadmin Regulators emerson com Emerson Automation Solutions For further information on the current PED revision see Bulletin D103053X012 or scan the QR code Fisher com Americas McKinney Texas 75070 USA T 1 800 558 5853 1 972 548 3574 Europe Bologna 40013 Italy T 39 051 419 0611 Asia Pacific Singapore 128461 Singapore T 65 6777 8211 Middle East and Africa Dubai United Arab Emirat...

Reviews: