Instruction Manual
D200160X012
4195K Controllers
July 2018
5
Table 1‐1. Specifications
Available Configurations
Input Signal (Process Sensor Range)
Lower and Upper Range Limits:
Maximum Allowable Operating Limits:
Output Signal
Proportional‐Only, Proportional‐Plus‐Reset, or
Proportional‐Plus‐Reset‐Plus‐Rate Range:
0.2 to 1.0
bar or 0.4 to 2.0 bar (3 to 15 psig or 6 to 30 psig)
Differential Gap Range:
0 and 1.4 bar (0 and 20 psig)
or 0 and 2.4 bar (0 and 35 psig)
Action:
Field‐reversible between direct (increasing
sensed process pressure increases output pressure)
or reverse (increasing sensed process pressure
decreases output pressure).
Process Scale
Standard scale is matched to the range of the sensing
element, with the exception of receiver controllers.
Optional
scales are available.
Process Connections
Standard:
1/4 NPT, internal, stainless steel
(all input ranges)
Optional:
Supply and Output Connections
1/4 NPT, internal
Supply Pressure Requirements
Supply Pressure Medium
Air or Natural Gas
Supply medium must be clean, dry, and noncorrosive
Per ISA Standard 7.0.01
A maximum 40 micrometer particle size in the air
system is acceptable. Further filtration down to 5
micrometer particle size is recommended. Lubricant
content is not to exceed 1 ppm weight (w/w) or
volume (v/v) basis. Condensation in the air supply
should be minimized.
Per ISO 8573-1
Maximum particle density size:
Class 7
Oil content:
Class 3
Pressure Dew Point:
Class 3 or at least 10
_
C less than
the lowest ambient temperature expected
Remote Set Point Pressure Ranges
0.2 to 1.0 bar or 0.4 to 2.0 bar
(3 to 15 psig or 6 to 30 psig)
Controller Adjustments
Proportional Band:
5 to 500% of process input span
Reset:
Adjustable from 0.01 to more than 74 minutes
per repeat (from 100 to less than 0.0135 repeats per
minute)
Rate:
Adjustable from 0 to 20 minutes
Differential Gap Controllers:
Adjustable from 5 to
100% of process scale range
Set Point:
Adjustable from 0 to 100% of the scale span
Controller Performance
Repeatability:
0.4% of output span
Dead Band:
Less than 0.4% of process scale span
Typical Frequency Response:
1.5 hertz and 90 degree
phase shift with 3.05 m (10 feet) of 6.4 mm (1/4‐inch)
tubing and 1639 cm
3 (
100 cubic inch) volume
Steady‐State Air Consumption
0.2 to 1.0 Bar (3 to 15 Psig) Output:
0.08 m
3
/hr (2.8 scfh)
0.4 to 2.0 Bar
(6 to 30 Psig) Output:
0.07 m
3
/hr (2.5 scfh)
Operative Ambient Temperature Limits
-40 to 71
_
C (-40 to 160
_
F)
Hazardous Area Classification
Complies with the requirements of ATEX Group II
Category 2 Gas and Dust
-continued-