Introduction
Instruction Manual
Form 5739
February 2002
1–7
Table 1-3. Model Number Table
Model
Product Description
3311/0846
Current-to-Pressure Transducer
Code
Action
D
R
Direct—Output changes directly with input
Reverse—Output changes inversely with input
Code
Performance
S
M
Standard (Typical Output: 3–15 psi; Wide rangebility betweeen 1 and 18 psi)
Multirange (Typical Outputs: 3–27 psi, 6–30 psi, and 5–25 psi; Wide rangebility betweeen 0.5 and 33.0 psi)
Code
Input
1
2
3
4
4–20 mA dc
4–12 mA dc
12–20 mA dc
Specify (Consult factory for other input ranges between 4–20 mA and 10–50 mA)
Code
Output
J
K
L
M
W
H
3–15 psi for direct action (15–3 psi for reverse action)
0.2–1.0 bar for direct action (1.0–0.2 bar for reverse action)
0.2–1.0 kg/cm
2
for direct action (1.0–0.2 kg/cm
2
for reverse action)
3–27 psi for direct action (27–3 psi for reverse action) Multirange performance units only
6–30 psi for direct action (30–6 psi for reverse action) Multirange performance units only
Specify (Consult factory for other calibration requirements; minimum span is 6 psi for direct and 11 psi for
reverse-acting units)
Code
Electrical Connections/Housing Material
1
2
1/2–14 NPT/Aluminum
1/2–14 NPT/316 stainless steel
Code
Options
B1
B2
B3
B4
F2
F3
G1
G2
G7
G8
G9
GA
GB
GE
GF
GG
P1
R1
(3)
A1
(1)
Q4
K5
C6
I1
N1
E9
(2)
K7
EG
(2)
IG
Universal mounting bracket, epoxy painted carbon steel, carbon steel nuts and bolts
Universal mounting bracket, epoxy painted carbon steel, stainless steel nuts and bolts
316 SST universal mounting bracket, SST nuts and bolts for use with SST housing
316 SST universal mounting bracket, SST nuts and bolts for use with aluminum housing
Filter-regulator, SST bolts
SST Filter-regulator, SST bolts
Supply gauge (0–60 psi/0–400 kPa/0–4 bar)
Output gauge (0–30 psi/0–200 kPa/0–2 bar)
Supply gauge (0–60 psi/0–4 kg/cm
2
)
Output gauge (0–30 psi/0–2 kg/cm
2
)
Output gauge (0–60 psi/0–400 kPa/0–4 bar)
SST Supply gauge (0–60 psi/0–400 kPa/0–4 bar)
SST Output gauge (0–60 psi/0–400 kPa/0–4 bar)
SST Output gauge (0–60 psi/0–4 kg/cm
2
)
SST Supply gauge (0–60 psi/0–4 kg/cm
2
)
Output gauge (0–60 psi/0–4 kg/cm
2
)
Module Cover with Multiple Ports
Remote pressure reading feature
Attach all applicable options at the factory (i.e., filter-regulator and gauges)
Calibration data sheet
Factory Mutual (FM) explosion-proof and intrinsic safety approval
Canadian Standards Association (CSA) explosion-proof and intrinsic safety approval
BASEEFA/CENELEC intrinsic safety certification
BASEEFA Type N certification
ISSeP/CENELEC flameproof certification
Standards Association of Australia (SAA) flameproof intrinsic safety, and Type n certification
Russian GOST flameproof certification
Russian GOST intrinsic safety certification
Typical Model Number: 3311 D S 1 J 1 B1
1. Not available with stainless steel housing
2. Hazardous location approval options E9 and EG are currently not available on multirange performance units.
3. With option R1, the Type 846 and Model 3311 circuit board contains the Remote Pressure Reading feature. The Remote Pressure Reading jumper is placed in the ON position prior
to shipment.
Companion Product: Model 272 Field Calibrator
The Rosemount Model 272 Field Calibrator can be
used to calibrate the I/P transducer. A
battery-operated, portable calibrator designed for
field use, the Model 272 features an adjustable 4–20
mA range, and selectable indication/simulation
modes. See product data sheet 00813-0100-4372.