Note

It is important that the regulator be 

installed so that the vent hole in the 

spring case is unobstructed at all times.  

For outdoor installations, the regulator 

should be located away from vehicular 

traffic and positioned so that water, ice, 

and other foreign materials cannot enter 

the spring case through the vent.  Avoid 

placing the regulator beneath eaves or 

downspouts, and be sure it is above the 

probable snow level.

Overpressure Protection

The recommended pressure limitations are 

stamped on the regulator nameplate.  Some type of 

overpressure protection is needed if the actual inlet 

pressure exceeds the maximum operating outlet 

pressure rating.  Overpressure protection should 

also be provided if the regulator inlet pressure 

is greater than the safe working pressure of the 

downstream equipment.
Regulator operation below the maximum pressure 

limitations does not preclude the possibility of damage 

from external sources or debris in the line.  The 

regulator should be inspected for damage after any 

overpressure condition.

Startup

The regulator is factory set at approximately 

the midpoint of the spring range or the pressure 

requested, so an initial adjustment may be required 

to give the desired results.  With proper installation 

completed and relief valves properly adjusted, slowly 

open the upstream and downstream shutoff valves.

Adjustment

To change the outlet pressure, loosen the locknut 

and turn the adjusting screw clockwise to increase 

outlet pressure or counterclockwise to decrease 

pressure.  Monitor the outlet pressure with a test 

gauge during the adjustment.  Tighten the locknut to 

maintain the desired setting.

Taking Out of Service (Shutdown)

!

WARNING

To  avoid  personal  injury  resulting 

from  sudden  release  of  pressure, 

isolate the regulator from all pressure 

before  attempting  disassembly.

Parts List

Key  

Description

  1       Body

  2          Spring Case
  3          Bottom Cap
  4          Yoke
  5          Orifice
  6          Valve Disk Assembly
  7          Diaphragm
  8          Diaphragm Plate
  9          Upper Spring Seat
  10          Valve Spring

  11       Spring

  12          Body Gasket
  13          Diaphragm Plate Gasket
  14          Bottom Cap O-ring
  15          Adjusting Screw
  16          Spring Case Cap Screw
  17          Machine Screw

  18       Locknut

  19          Diaphragm Locknut
  21          Top Connector
  22          Valve Disk Collar
  24         Handwheel (Not shown)
  26         Vent Screen (Not shown)
  27         Mounting Post (Not shown)
  28         Mounting Screw (Not shown)
  29         Screw (Not shown)
  30         Washer (Not shown)
  32         Mounting Bracket (Not shown)
  33         Bracket Cap Screw (Not shown)
  34         Bracket Mounting Washer (Not shown)
  35         NACE Tag (Not shown)
  36         Tag Wire (Not shown)
  38         Body O-Ring (Not shown)
  39         Top Connector O-Ring (Not shown)
  40         Pipe Plug

Summary of Contents for Fisher 1301

Page 1: ...re relieving or pressure limiting devices as required by the appropriate code regulation or standard to prevent service conditions from exceeding limits Additionally physical damage to the regulator could result in personal injury and property damage due to escaping fluid To avoid such injury and damage install the regulator in a safe location Clean out all pipelines before installation of the reg...

Page 2: ...justment may be required to give the desired results With proper installation completed and relief valves properly adjusted slowly open the upstream and downstream shutoff valves Adjustment To change the outlet pressure loosen the locknut and turn the adjusting screw clockwise to increase outlet pressure or counterclockwise to decrease pressure Monitor the outlet pressure with a test gauge during ...

Page 3: ...CN7095_C 15 2 11 19 16 1 13 14 3 22 10 6 5 4 12 17 7 8 9 18 21 Figure 1 Type 1301F Regulator Figure 2 Type 1301G Regulator 20 40 S 6 0 0 0 P S I M A X I N L E T F I S H E R M AX OUTLET PSI U S A 20 6 0 0 0 M A X F I S H E M A X PSI U S A 40 S APPLY SEALANT S APPLY SEALANT S ...

Page 4: ... proper selection use and maintenance of any Emerson Process Management product remains solely with the purchaser Industrial Regulators Emerson Process Management Regulator Technologies Inc USA Headquarters McKinney Texas 75069 1872 USA Tel 1 800 558 5853 Outside U S 1 972 548 3574 Asia Pacific Shanghai 201206 China Tel 86 21 2892 9000 Europe Bologna 40013 Italy Tel 39 051 419 0611 Middle East and...

Reviews: