DI Function Block
November 2010
191
Invert Option
Alarm Detection
FIELD_VAL_D
MODE
SIMULATE
PV_D
OUT_D
Discrete Signal
Figure 4-29. Discrete Input Function Block Schematic
Table 4-77. Channel Selection for the Discrete Input Function Block
Selection
Transducer Block Parameter
(1)
Transducer Block
Index Number
Bit Number
(2)
23
TRAVEL_D
33
N/A
24
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
0: Travel Open
25
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
1: Travel Closed
26
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
74.4
2: Travel Limit Lo Lo
27
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
74.4
4: Travel Limit Lo
28
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
74.4
3: Travel Limit Hi
29
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
74.4
1: Travel Limit Hi Hi
30
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
5: Proximity Lo Lo
31
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
4: Proximity Lo
32
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
3: Proximity Hi
33
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
2: Proximity Hi Hi
1. Refer to table 4-14 for parameter descriptions.
2. See pages 432 and 434, Travel ALerts and Prox Alerts, for information on accessing these alerts. Refer to Appendix F for information on accessing these alerts through DeltaV.
Open/Closed Limit Switch
Channels 24 and 25 provide valve open and closed
limit switch functionality for the DI block. These
channels will detect if the valve position is more than
the Travel Open Alert Point for open detection or less
than the Travel Closed Alert Point for closed detection.
These channels provide an adjustable deadband to
clear the detected position.
0= Not Active, 1= Active
Variable Limit Switch
Channels 26 through 29 provide variable limit switch
functionality for the DI block. Trip points for this limit
switch functionality are based on the Travel Alert
settings in the transducer Block. The DI function block
provides the same type of position detection as the
travel alerts in the transducer block. Table 4-78 lists
the transducer block parameters used with DI block
channels 26 through 29. Refer to Travel and Prox, on
page 432 for more information on the transducer block
travel alerts.
0= Not Active, 1= Active
Table 4-78. Transducer Block Parameters Used with Discrete
Input Function Block Channels 26 through 29 (Variable Limit
Switch)
Transducer Block
Parameter
Parameter Function
Travel Lo Lo Alert Point
Lo Lo Limit Switch Trip Point
Travel Lo Lo Alert Deadband
Lo Lo Limit Switch Deadband
Travel Lo Alert Point
Lo Limit Switch Trip Point
Travel Lo Alert Deadband
Lo Limit Switch Deadband
Travel Hi Alert Point
Hi Limit Switch Trip Point
Travel Hi Alert Deadband
Hi Limit Switch Deadband
Travel Hi Hi Alert Point
Hi Hi Limit Switch Trip Point
Travel Hi Hi Alert Deadband
Hi Hi Limit Switch Deadband
4
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...