DVC6200f Digital Valve Controller
November 2010
62
Travel Lo Alert Point
The Travel Alert Lo alert is set when the value of the
travel, in percent (%) of ranged travel, goes below the
Travel Lo Alert Point (TVL_LO_ALRT_PT [77.14]).
Travel Lo Deadband
Travel Lo Deadband (TVL_LO_DB [77.15]) is the
travel, in percent (%) of ranged travel, required to
clear a travel lo alert, once it has been set. See
figure 4-3.
Proximity Alerts
Field Communicator
TB
>
Configure/Setup
>
Detailed Setup
>
Alerts
>
Prox Alerts
Note
See page 4164 for additional details on
using Proximity detection.
Travel
Travel displays the actual position of the valve in
percent (%) of calibrated travel.
Travel Open
Travel Open Alert
This alert is active if the Travel is greater than the
Travel Open Alert Point.
Travel Open Alert Enable
When enabled Travel Open Alert Enable activates the
Travel Open Alert.
Travel Open Alert Point
Travel Open Alert Point (TVL_OPEN_ALRT_PT
[77.8]) is the value of the travel in percent (%) or
ranged travel, which, when exceeded, sets the Travel
Open Alert.
Travel Open Deadband
Travel Open Deadband (TVL_OPEN_DB [77.9]) is the
travel in percent (%) of ranged travel required to clear
a Travel Open alert, once it has been set.
Travel Closed
This alert is active if the Travel is lower than the Travel
Closed Alert Point.
Travel Closed Alert
This alert is active is the Travel goes below the Travel
Closed Alert Point.
Travel Closed Alert Enable
When enabled Travel Closed Alert Enable activates
the Travel Closed Alert.
Travel Closed Alert Point
The Travel Closed Alert is set when the value of the
travel, in percent (%) of ranged travel, goes below the
Travel Closed Alert Point (TVL_CLOSED_ALRT_PT
[77.10]).
Travel Closed Deadband
Travel Closed Deadband (TVL_CLOSED_DB [77.11])
is the travel in percent (%) of ranged travel required to
clear a Travel Closed alert, once it has been set.
Proximity
Proximity Hi Hi Alert
This alert is active if the Travel is within the detection
band set by the Travel Hi Hi Alert Point and the Travel
Hi Hi Deadband.
Proximity Hi Hi Alert Enable
When enabled Proximity Hi Hi Alert Enable activates
the Proximity Hi Hi Alert.
Proximity Hi Alert
This alert is active if the Travel is within the detection
band set by the Travel Hi Alert Point and the Travel Hi
Deadband.
Proximity Hi Alert Enable
When enabled Proximity Hi Alert Enable activates the
Proximity Hi Alert.
Proximity Lo Alert
This alert is active if the Travel is within the detection
band set by the Travel Lo Alert Point and the Travel
Lo Deadband.
Proximity Lo Alert Enable
When enabled Proximity Lo Alert Enable activates the
Proximity Lo Alert.
Proximity Lo Lo Alert
This alert is active if the Travel is within the detection
band set by the Travel Lo Lo Alert Point and the
Travel Lo Lo Deadband.
4
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...