126 Appendix 3 Accessories
EV2100 Series Variable Speed Drive User Manual
Address
Function code
Register address
Register content
Checksum
Request 0x05 0x06 0x3200 0x0180 0x86C6
Response
0x05
0x06
0x3200
0x0180
0x86C6
Read the running frequency of No.5 drive and the response running frequency is 50.00HZ:
Address Function
code
Register
address
Number of
registers or
Number of
read bytes
Register
content
Checksum
Request 0x05 0x03 0x3301 0x0001 None 0xDB0A
Response
0x05 0x03 None 0x02 0x1388
0x44D2
Change the acceleration time 1 (i.e. function code F0.10) of No.5 drive to be 10.0s, which can not be saved
upon power off.
Address
Function code
Register address
Register content
Checksum
Request 0x05 0x06 0x000A 0x0064 0xA9A7
Response
0x05
0x06
0x000A
0x0064
0xA9A7
Read the output current of No.5 drive and the response output current is 30.0A:
Address Function
code
Register
address
Number of
registers or
Number of
read bytes
Register
content
Checksum
Request 0x05 0x03 0x3306 0x0001 None 0x6ACB
Response
0x05 0x03 None 0x02 0x12C
0x49C9
Read the deceleration time (i.e. F0.11) of No.5 drive and the response deceleration time is 6.0s:
Address Function
code
Register
address
Number of
registers or
Number of
read bytes
Register
content
Checksum
Request 0x05 0x03 0x000B 0x0001 None 0xF4C4
Response
0x05 0x03 None 0x02 0x003C
0x4995
9. Scaling relations of the drive
A) Scaling of the frequency is 1:100
To make the drive run at 50Hz, the main setting
shall be 0x1388 (5000).
B) Scaling of time is 1:10
To make the acceleration time of the drive to be
30S, the function code shall be set to 0x012c (300).
C) Scaling of current is 1:10
If the feedback current of the drive is 0x012C, the
present current shall be 30A.
D) The output power is its absolute value.
E) For others (such as terminal input/output), please
refer to the Drive User Manual.