background image

nOMinAL PiPE 

DiAMETEr

nUMBEr OF BOLTS

BOLT DiAMETEr

TOrQUE

in.

mm

Ft-lbs

N•m

1

4

0.50

12.70

9

12.20

1-1/4 

4

0.50

12.70

13

17.63

1-1/2

4

0.50

12.70

18

24.40

2

4

0.63

16.00

35

47.45

2-1/2 

4

0.63

16.00

41

55.59

3

4

0.63

16.00

60

81.35

3-1/2 

8

0.63

16.00

34

46.10

4

8

0.63

16.00

43

58.30

6

8

0.75

19.05

80

108.5

8

8

0.75

19.05

109

147.8

10

12

0.88

22.4

101

136.9

12

12

0.88

22.4

135

183.0

14

12

1.00

25.0

168

227.8

16

16

1.00

25.0

159

215.6

18

16

1.13

28.7

244

330.8

20

20

1.13

28.7

214

290.2

24

24

1.25

31.8

253

343.0

Assumptions:  Use of SAE grade 5 bolts or studs or stronger.

 

No lubricant.

 

Compressed mineral fiber material or similar.

Notes:  If lubricant is used on bolts, apply torque reduction factor listed in Lubricant Table.

 

For best results hardened steel washers should be used on all cast flange bolted connections.

Table 6. 

Torque Values for Raised Face Connection Flange (Steel Only)

nOMinAL PiPE DiAMETEr

nUMBEr OF BOLTS

BOLT DiAMETEr

TOrQUE

in.

mm

Ft-lbs

N•m

1

4

0.50

12.70

14

18.98

1-1/4 

4

0.50

12.70

16

21.69

1-1/2 

4

0.50

12.70

18

24.41

2

4

0.63

16.00

32

43.39

2-1/2 

4

0.63

16.00

43

58.30

3

4

0.63

16.00

47

63.72

3-1/2 

8

0.63

16.00

26

35.25

4

8

0.63

16.00

32

43.39

6

8

0.75

19.05

49

66.44

8

8

0.75

19.05

68

92.20

10

12

0.88

22.4

69

93.55

12

12

0.88

22.4

98

132.9

14

12

1.00

25.0

138

187.1

16

16

1.00

25.0

125

169.5

18

16

1.13

28.7

142

192.5

20

20

1.13

28.7

135

183.0

24

24

1.25

31.8

156

211.5

8 API

16

0.50

12.70

20

27.12

20 API

16

0.63

16.00

75

101.7

24 API

20

0.63

16.00

75

101.7

Assumptions:  Use of SAE grade 5 bolts or studs or stronger.

 

No lubricant.

 

Elastomer <70 Durometer Shore A.

Notes:  Flat faced flanges should never be mated to a raised face flange for installation.

 

If lubricant is used on bolts, apply torque reduction factor listed in Lubricant Table.

 

For best results hardened steel washers should be used on all cast flange bolted connections.

Table 7. 

Torque Values for Flat Face Connection Flange (Steel or Aluminum)

DESCriPTiOn

COEFFiCiEnT OF FriCTiOn

MULTiPLY TOrQUE VALUE in TABLE 6 BY

Machine Oil

f = 0.15

0.75

API SA2 Grease

f = 0.12

0.60

Nickel-based Lubricant

f = 0.11

0.55

Copper-based Lubricant

f = 0.10

0.50

Heavy-Duty Lubricating Paste

f = 0.06

0.30

Table 8. 

Torque Correction Factors for Common Lubricants Applied on Flanges

10

Enardo DFA Series

Outside North 

America Only

Summary of Contents for Enardo DFA Series

Page 1: ...ctions for installation startup maintenance and parts ordering information for the Enardo DFA Series detonation flame arrestor Product Description The Enardo DFA Series detonation flame arrestor represents the best value in flame arrestor protection The detonation flame arrestor provides protection against flame propagation in piping systems that are manifolded or have long run up distances These ...

Page 2: ...d USCG Approved 4 5 1 The pressure temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded 2 Hastelloy housings and element material are not USCG approved 3 Not all models are available with USCG and ATEX certifications Contact your local Sales Office for more information 4 USCG and ATEX approval report s are available upon request 5 Flow...

Page 3: ...ble with USCG and ATEX certifications Contact your local Sales Office for more information Hastelloy is a mark owned by Haynes International Inc 1 Hastelloy housings are not USCG approved 2 Hastelloy element material is not USCG approved Hazardous Locations Figure 4 Product Identification and Marking for ATEX Units Markings Nameplate Information A nameplate will be attached to the arrestor and wil...

Page 4: ... oxygen nitrogen ratio chlorine as oxidant etc Minimum distance between flame arrestor connection and a restriction on the protected side is 10 L D but not less than 3 m Arrestors shall only be installed into piping with a nominal size that is smaller than or equal to the nominal size of the flame arrestor connection Factors Affecting Flame Arrestor Performance Gas Group Warning Methanol is classi...

Page 5: ... conditions The likelihood for developing detonations via Deflagration to Detonation Transition DDT is enhanced by turbulent flow conditions Pipe Length Extended lengths of pipe allow the flame to advance into more severe states of flame propagation such as high pressure deflagration and detonations Enardo Detonation Flame Arrestors are not limited by pipe length Flow Restrictions at Protected Sid...

Page 6: ...stem where indications of stabilized burning are observed Effective corrective measures must be taken to correct this condition Any Detonation Flame Arrestor with indications of stabilized burning must be removed from service and thoroughly inspected by personnel with appropriate training and qualifications Warning Temperature sensors must be used with flame arrestors having 1 minute ATEX burn rat...

Page 7: ...emperatures to which the device may be exposed and at a minimum be capable of withstanding a hydrostatic pressure test of 350 psig 24 bar The Enardo DFA Series detonation flame arrestor may be installed in any vapor control line that is smaller than or equal to the nominal pipe diameter of the arrestor s connection flanges When it is necessary to increase the diameter of the piping on the downstre...

Page 8: ...alues for their respective gas group Use the following pin gauges as no go gauges Model Enardo DFA E D Explosion Group D IIA 0 063 in 1 6 mm Model Enardo DFA E C Explosion Group C IIB3 0 039 in 1 mm 4 If any damage is noted or crimp openings exceed maximum size allowable as indicated by the entry of the no go gauge replace the element assembly Note Under no circumstance shall any element assembly ...

Page 9: ...97 Enardo DFA 1206 3 1 1 8 8 Snug 50 68 100 136 165 224 Enardo DFA 1608 4 1 1 4 8 Snug 50 68 120 163 190 258 Enardo DFA 2010 5 1 1 4 8 Snug 50 68 100 136 180 244 260 353 Enardo DFA 2412 5 1 1 2 8 Snug 75 102 150 203 280 380 400 542 500 678 Enardo DFA 2814 6 1 5 8 8 Snug 75 102 150 203 320 434 450 610 550 746 Enardo DFA 3016 6 1 3 4 8 Snug 80 108 200 271 350 475 500 678 700 949 Enardo DFA 3418 6 1 ...

Page 10: ... 4 0 63 16 00 32 43 39 2 1 2 4 0 63 16 00 43 58 30 3 4 0 63 16 00 47 63 72 3 1 2 8 0 63 16 00 26 35 25 4 8 0 63 16 00 32 43 39 6 8 0 75 19 05 49 66 44 8 8 0 75 19 05 68 92 20 10 12 0 88 22 4 69 93 55 12 12 0 88 22 4 98 132 9 14 12 1 00 25 0 138 187 1 16 16 1 00 25 0 125 169 5 18 16 1 13 28 7 142 192 5 20 20 1 13 28 7 135 183 0 24 24 1 25 31 8 156 211 5 8 API 16 0 50 12 70 20 27 12 20 API 16 0 63 1...

Page 11: ...studs Wiping rags necessary for the clean up of excessive lubricant Molykote G n is a mark owned by Dow Corning Corporation Procedure 1 Use studs and nuts that are free of visible contamination and corrosion 2 Apply lubricant to the threads of the stud protruding outboard of the interior flanges and to the face of the hex nuts which will contact the flange 3 Assemble the nuts to the studs such tha...

Page 12: ...tees express or implied regarding the products or services described herein or their use or applicability All sales are governed by our terms and conditions which are available on request We reserve the right to modify or improve the designs or specifications of our products at any time without notice Emerson Process Management Regulator Technologies Tulsa LLC does not assume responsibility for th...

Reviews: