Section 12: Reverse Acting
(Counterclockwise to Close)
Standard factory actuators are normally set to clockwise rotation to close. However the
rotation can be reverse to counter-clockwise to close by simply reconfiguring the wiring
as follows:
•
Exchange 9 and 10 in main actuator terminal block
•
Exchange 11 and 12 in main actuator terminal block
If a PCU card is installed:
•
Exchange Potentiometer input wires P1(Orange wire) and P3 (Grey wire) on PCU
•
Change the direction of the indicator (HQ-200 and 300 only)
•
Recalibrate by using Auto Calibrate feature