EC3-P32 Superheat Controller with TCP/IP 

Installation in non explosive environment 

 

 

 

Emerson Climate Technologies GmbH  

www.emersonclimate.eu

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 04.05.2017 

EC3-P32_OI_ML_R01_865918.docx 

E r r o r / A l a r m   h a n d l i n g :  

Alarm code 

Description 

Related 

parameter 

Alarm 

relay 

Valve 

What to do? 

Requires manual 

reset after resolving 

alarm 

E0

 

Pressure transmitter 
error 

Signalling  Fully close  Check wiring connection and measure the signal 4 to 20 mA. 

No 

E1

 

Temperature sensor 
error 

Signalling  Fully close  Check wiring connection and measure the resistance of sensor. 

No 

 

EXV electrical 
connection error 

Signalling 

Check wiring connection and measure the resistance of winding. 

No 

Ab 

Battery error 

b1: 1 

Regulating  Battery potentially does not have enough charge to close valve in 

case of main power supply interruption. May occur temporarily 
with new controllers or after long storage but should disappear 
when battery is charged sufficiently. If Ab remains active even 
when battery is charged, battery may be defective and should be 
replaced. (Replacement kit: 807790). 

Ab 

b1: 2 

Signalling  Fully close 

Ab blinking 

b1: 3 

Signalling  Fully close 

Yes 

AE blinking 

Pump down action 
cannot accomplished 

P6: 1 

Signalling 

Allocate the source, which does not let suction pressure drops 
below desired set-point. 

Yes 

AF

 

Freeze protection 

P4: 1 

Signalling  Fully close  Check the system for cause of low pressure such as insufficient 

load on evaporator. 

No 

AF blinking

 

P4: 2 

Signalling  Fully close 

Yes 

AL

 

Low superheat  
(<0,5K) 

uL: 1 

Signalling  Fully close 

Check wiring connection and operation of valve. 

No 

AL blinking

 

uL: 2 

Signalling  Fully close 

Yes 

AH 

High superheat 

uH: 1 

Signalling  Fully close  Check the system. 

No 

AP

 

Low pressure 

P9: 1 

Signalling  Fully close  Check the system for cause of low pressure such as refrigerant 

loss. 

No 

AP blinking

 

P9: 2 

Signalling  Fully close 

Yes 

Er 

Data error display - 
out of range 

Data send to the display is out of range. Check temperature and 
pressure sensor. 

No 

--- 

No data to display 

Check Cable and plug connection between EC3-P32 and  
ECD-002. 

No 

Note:

 When multiple alarms occur, the highest priority alarm is displayed until being cleared, then the next highest alarm is displayed until all alarms are cleared. Only then 

will parameters be shown again. 
 

C h e c k i n g   s y s t e m   o p e r a t i n g   c o n d i t i o n s   u s i n g   l o c a l   d i s p l a y / ke y p a d   E C D - 0 0 2 :  

The data to be permanently shown on the display can be selected by the user (parameter ┌┘1). It is possible to temporarily display these values. However this function is 

not available in an alarm condition. The display will show for one second the numerical identifier of the data (see ┌┘1 parameter) and then the selected data. After 5 minutes, 

the display will return to the value selected by parameter ┌┘1. 
 

S e r v i c e   /   T r o u b l e s h o o t i n g :  

Symptom 

Cause 

Action 

Operating superheat is several degrees higher or lower than 
set-point 

Incorrect signal from pressure or 
temperature sensors 

1- Check the sensors. 
2- Make sure ECN-N60 temperature sensor is used. 
3- For optimum accuracy, please use: 
     PT5-30L-FLR  
4- Make sure the sensor cables are not installed along with other  
    high voltage cables 

Operating superheat is too low i.e. compressor wet running 

1- Incorrect wiring of EVC05A 
2- Defective sensors 

1- Check the wiring 
2- Check the sensor 

Valve is not fully closed 

1- The digital input is ON (24 V) 
2- Wrong setting of parameter ut. 

1- Valve is shut off only when the digital input is turned off 
(0 V). 
2- Check the setting of parameter ut. 

Instable superheat (hunting) 

Evaporator is designed to operate at 
higher superheat  

Increase the superheat set-point. 

Valve opens when EC3 commands to close and vice versa 

Wrong wiring between EC3-P32 and 
valve 

Correct the wiring. 

Superheat set-point is shifting after several months of 
uninterrupted operation or permanent jumper of 24 V digital 
input 

Stepper motor driven valves require 
synchronization 

Do not apply permanent 24 V digital input. Interrupt digital input 
once every week for 5 seconds if compressor never stops. 

 

Summary of Contents for EC3-P32

Page 1: ...ing lugs will turn and gradually move towards panel 2 Turn Allen key until mounting lug barely touches panel Then move other mounting lug to the same position 3 Tighten both sides very carefully until keypad is secured Do not over tighten as mounting lugs will break easily Electrical Installation Refer to the electrical wiring diagram for electrical connections Do not apply voltage to the controll...

Page 2: ...Main parameters must be checked and modified if necessary Code Parameter description and choices Min Max Factory setting Field setting H5 Password 1 199 12 u0 System refrigerant 0 6 0 0 R290 1 R32 2 R1234ze 3 R1234yf 4 R1270 5 R227 6 R600a uP Installed pressure sensor type PT5 30L FLR ut Installed valve type 0 3 1 0 EX4 FLR 1 EX5 FLR 2 EX6 FLR 3 EX7 FLR uu Start valve opening 5 100 10 u9 Start ope...

Page 3: ...stem components All other parameters can be modified at any time The EC3 P32 has a TCP IP Ethernet communication interface enabling the controller to be directly connected to a network or a PC via the standard Ethernet port The EC3 P32 controller has embedded WebPages to enable the user to visualize the parameter lists using real text labels To view WebPages on the PC a standard Web Browser like I...

Page 4: ...ta error display out of range Data send to the display is out of range Check temperature and pressure sensor No No data to display Check Cable and plug connection between EC3 P32 and ECD 002 No Note When multiple alarms occur the highest priority alarm is displayed until being cleared then the next highest alarm is displayed until all alarms are cleared Only then will parameters be shown again Che...

Page 5: ...start function NTC input EMERSON temperature sensor ECN Nxx 4 20 mA Analog input EMERSON PT5 30L FLR pressure Transmitter 4 20 mA Analog output Deviation from input signal For connection to any 3rd party controller with 12 24 VDC power supply and appropriate burden 8 max Output alarm relay SPDT contacts 24 VAC DC 2 Amp inductive load If L2 1 Activated During normal operation no alarm condition Dea...

Page 6: ...alterungen treten aus dem Gehäuse hervor und bewegen sich in Richtung Frontplatte 2 Imbusschraube drehen bis die erste Halterung die Frontplatte leicht berührt Dann zweite Halterung in diese Position bringen 3 Beide Seiten gleichmäßig und nicht zu fest anziehen Hinweis durch zu festes Anziehen können die Halterungen abbrechen Elektrischer Anschluss Den elektrischen Anschluss gem Verdrahtungsschema...

Page 7: ...OV möglich 1 Aktuelle TCP IP Adresse anzeigen 2 Dem Regler vorübergehend die Standard TCP IP Adresse 192 168 1 101 zuweisen falls dieser eine andere Adresse besitzt Nach dem Abschalten wird die zuvor eingestellte Adresse wieder aktiviert SEL drücken alle Parameter werden auf Werkseinstellung zurückgesetzt PRG drücken die gewählte Funktion wird aktiviert und die Betriebsart Spezial funktionen verla...

Page 8: ...rhindert die Beschädigung des Verdichters oder anderer Systemkomponenten Alle anderen Parameter können jederzeit verändert werden Der EC3 P32 kann mit seiner TCP IP Ethernet Schnittstelle direkt an den Ethernetanschluss eines PCs oder an ein lokales Netzwerk angeschlossen werden Übersichtliche Webseiten auf denen die Parameterlisten angezeigt oder geändert werden können sind bereits eingebaut Zur ...

Page 9: ...Daten nicht darstellen Einstellwert der Parameter verändern Nein Keine Daten Kabel und Steckerverbindungen zwischen EC3 P32 und ECD 002 prüfen Nein Hinweis Bei mehreren Alarmen gleichzeitig wird der Alarm mit der höchsten Priorität angezeigt nach dessen Beseitigung wird der nächsthöhere angezeigt usw bis alle Alarme beseitigt sind Danach werden wieder die Parameter angezeigt Überprüfung der Betrie...

Page 10: ...C DC zum Ein bzw Ausschalten NTC Analogeingang EMERSON Temperatursensor ECN N60 4 20 mA Analogeingang EMERSON PT5 30FLR Drucktransmitter 4 20 mA Analogausgang Abweichung vom Eingangssignal für externen Regler mit 12 24 VDC Speisespannung und geeignetem internen Widerstand 8 max Ausgang Alarmrelais Wechsler für 24 V AC DC Induktive Last 2 A wenn L2 1 Aktiviert bei Normalbetrieb kein Alarmzustand In...

Reviews: