Section 4– Page 5
4.4.2 Motor Poles Selection
Switch SW3 sets the number of motor poles. The default setting is for a 6 pole motor.
Table 4-D – Motor Poles Selection
OFF = 0 ON = 1
(Table 4-D – Rev. 01/13/95j)
SW3/1
SW3/2
MOTOR POLES
0
0
8
0
1
6
1
0
4
1
1
2
4.4.3 Continuous Current Adjustment
When continuous current of the motor is less than the continuous current of the drive, it
is possible to reduce the drive continuous current using the four SW2 switches with the
following logic.
Identify the required current level in Table 16 related to the LX drive model you are
using. Set the relevant SW2/ 1, 2, 3, 4 ON or OFF configuration.
Table 4-E – Nominal Current Adjustment
OFF = 0 ON = 1
(Table 4-E – Rev. 01/13/95j)
SW2/1
SW2/2
SW2/3
SW2/4
LX-400
AMPS RMS
LX-700
AMPS RMS
LX-1100
AMPS RMS
0
0
0
0
2.16
3.78
5.67
0
0
0
1
2.30
4.02
6.02
0
0
1
0
2.43
4.25
6.38
0
0
1
1
2.57
4.49
6.73
0
1
0
0
2.70
4.73
7.09
0
1
0
1
2.84
4.96
7.44
0
1
1
0
2.97
5.20
7.80
0
1
1
1
3.11
5.43
8.15
1
0
0
0
3.24
5.67
8.51
1
0
0
1
3.38
5.91
8.86
1
0
1
0
3.51
6.14
9.21
1
0
1
1
3.65
6.38
9.57
1
1
0
0
3.78
6.62
9.92
1
1
0
1
3.92
6.85
10.28
1
1
1
0
4.05
7.09
10.63
1
1
1
1
4.19
7.32
10.99