1592026601 XWi70K STD FULL EN r1.6 2022.07.29.docx
XWi70K
7/15
DIGITAL INPUT MENU - inP
i1P
Digital input 1 polarity:
(oP; CL)
oP
= activated by closing the contact;
CL
= activated
by opening the contact.
i1F
Digital input 1 configuration:
(nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF;
LiG; CC; EMt)
•
EAL
= external warning alarm
•
bAL
= external lock alarm
•
PAL
= external pressure alarm
•
dor
= door switch function
•
dEF
= defrost activation
•
AUS
= auxiliary output
•
ES
= energy saving mode activation
•
HdF
= holiday defrost
•
LiG
= light output control
•
onF
= ON/OFF status change
•
Lnt
= change configuration (between Lt and nt)
did
Digital input 1 alarm delay:
(0 to 255 min) delay between the detection of an external
event and the activation of the relative function.
i2P
Digital input 2 polarity:
(oP; CL)
oP
= activated by closing the contact;
CL
= activated
by opening the contact.
i2F
Digital input 2 configuration:
(nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF;
LiG; CC; EMt)
•
EAL
= external warning alarm
•
bAL
= external lock alarm
•
PAL
= external pressure alarm
•
dor
= door switch function
•
dEF
= defrost activation
•
AUS
= auxiliary output
•
ES
= energy saving mode activation
•
HdF
= holiday defrost
•
LiG
= light output control
•
onF
= ON/OFF status change
•
Lnt
= change configuration (between Lt and nt)
d2d
Digital input 2 alarm delay:
(0 to 255 min) delay between the detection of an external
event and the activation of the relative function.
nPS
Number of external pressure switch alarms before stopping the regulation:
(0 to
15) after reaching nPS events in the digital input alarm delay (par.
dxd
), the regulation
will be stopped and a manual restart (ON/OFF, power OFF and power ON) will be
required
odC
Compressor and fan status after door opening:
(no; FAn; CPr; F-C): no = normal;
FAn = Fans OFF; CPr = Compressor OFF; F-C = Compressor and fans OFF.
rrd
Regulation restart after door alarm:
(n; Y)
n
= regulation disabled until door open
alarm is ON;
Y
= when the delay
rrd
elapses, the regulation restarts even if a door open
alarm is ON.
ENERGY SAVING MENU
–
ES
HES
Temperature differential in energy saving:
(-30.0 to 30.0°C; -54 to 54°F) sets the
increasing value of the set point during the Energy Saving cycle.
ESt
Energy saving timeout:
(0 to 255 hours) maximum duration for energy saving mode. If
ESt=0
then this function is disabled.
LdE
Energy saving controls the lights:
(n; Y) lights off when energy saving mode is active
LHt
Time-out for light output:
(0 to 255 min) the light output will be forced OFF after this
period.
LHt=0
means function disabled.
REAL TIME CLOCK MENU - rtC
Hur
Hours:
0 to 23 hours
Min
Minutes:
0 to 59 minutes
dAY
Day of the week:
Sun to Sat
dYM
Day of the month:
1 to 31
Mon
Month:
1 to 12
YAr
Year:
00 to 99
Hd1
First day of weekend:
(Sun to SAt; nu) setting for the first day of the weekend.
Hd2
Second day of weekend:
(Sun to SAt; nu) setting for the second day of the
weekend.
iLE
Energy saving cycle starting time on working days:
(00h00min to 23h50min)
during the Energy Saving cycle, the set point is increased by the value in HES so
that the operation set point is
SET+HES
.
dLE
Energy saving cycle duration on working days:
(00h00min to 24h00min) sets
the duration of the Energy Saving cycle on working days.
iSE
Energy saving cycle starting time on weekends:
00h00min to 23h50min
dSE
Energy saving cycle duration on weekends:
00h00min to 24h00min
dd1…d
d6
Daily defrost enabled:
(n; Y) to enable the
Ld1 to Ld6
defrost operations for any
day of the week.
•
dd1
= Sunday defrost
•
dd2
= Monday defrost
•
dd3
= Tuesday defrost
•
dd4
= Wednesday defrost
•
dd5
= Thursday defrost
•
dd6
= Friday defrost
•
dd7
= Sunday defrost
Ld1
…
Ld6
Defrost starting time:
(00h00min to 23h50min) these parameters set the
beginning of the programmable defrost cycles during any
ddx
day. Example: when
Ld2=12.4,
the second defrost starts at 12:40 am during working days.
N.B.:
To disable a defrost cycle set it to “nu”(not used).
Ex:
if
Ld6=nu
;
the sixth defrost cycle will
be disabled.
SERIAL COMMUNICATION - CoM
Adr
Serial address:
(1 to 247) device address for Modbus communication
bAU
Baudrate:
(9.6; 19.2) select the correct baudrate for serial communication
USER INTERFACE - Ui
brd
Type of keyboard lock:
(UnL; SEL; ALL)
•
UnL
= function disabled
•
SEL
= only some buttons are locked after
tLC
•
ALL
= all buttons are locked after
tLC
tLC
Delay before keyboard lock:
(0 to 255 sec) this delay is used after power-on to lock
some functions of the keyboard.
onC
ONOFF button configuration:
(nU; oFF; ES; SEr)
•
nU
= not used
•
oFF
= to switch on and off the device
•
ES
= energy saving mode
on2
ONOFF button timed configuration (3 sec):
(nU; oFF; ES)
•
nU
= disabled
•
oFF
= to switch on and off the device
•
ES
= energy saving mode
LGC
Light button configuration:
(nU; oFF; ES; SEr)
•
nU
= not used
•
LiG
= to switch on and off the light output
•
AUS
= acts on the auxiliary output
LG2
Light button timed configuration (3 sec):
(nU; oFF; ES)
•
nU
= not used
•
LiG
= to switch on and off the light output
•
AUS
= acts on the auxiliary output
•
Lnt
=
to swap the parameter map between “Lt” and “nt”
•
CC
= to load the default factory settings
dFC
Defrost button configuration:
(nU; oFF; ES; SEr)
•
nU
= not used
•
Pb2
= to quickly visualize the current values of probe P2
•
AUS
= acts on the auxiliary output
dF2
Defrost button timed configuration (3 sec):
(nU; oFF; ES)
•
nU
= disabled
•
dEF
= to start a defrost
•
AUS
= acts on the auxiliary output
dn2
Down button timed configuration (3 sec):
(nU; Std; Lnt; ALr; Pnd)
•
nU
= not used
•
Std
= lower temperature value
•
Lnt
= configuration map change
•
Pdn
= force Pull Down mode
UP2
UP button timed configuration (3 sec):
(nU; Std; CC; ALr; Pnd)
•
nU
= not used
•
Std
= higher temperature value
•
CC
= to load the default factory settings
•
Pnd
= force Pull Down mode
Info Menu - Info
dP1
Probe P1 value visualization
dP2
Probe P2 value visualization
dP3
Probe P3 value visualization
dP4
Probe P4 value visualization
SPd
Instantaneous compressor speed (RPM * 10)
rSE
Real regulation
Set Point
rEL
Firmware release: progressive number
Ptb
Parameter map version
16
DIGITAL INPUT
The free voltage digital inputs are programmable in different configurations by the
i1F or i2F
parameters.
16.1
DOOR SWITCH INPUT (dor)
It signals the door status and the corresponding relay output status through the
odC
parameter:
no
=
normal (any change);
FAn
= Fan OFF;
CPr
= Compressor OFF;
F_C
= Compressor and fan OFF.
Since the door is opened, after the delay time set through parameter
did
, the door alarm is enabled, the
display shows the message “
dA
” and
the regulation restarts is rtr = yES.
The alarm stops as soon as
the external digital input is disabled again. With the door open, the high and low temperature alarms are
disabled.
16.2
GENERIC ALARM (EAL)
As soon as the digital input is activated the unit will wait for
did
time delay before signalling the “
EAL
”
alarm message. The outputs status doesn’t change. The alarm stops just after the digital input is de
-
activated.
16.3
SERIOUS ALARM MODE (bAL)
When the digital input is activated, the unit will wait for
did
delay before signalling the “
CA
” alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.
16.4
PRESSURE SWITCH (PAL)
If during the interval time set by
did
parameter, the pressure switch has reached the number of activation
of the
nPS
parameter, the “
CA
” pressure alarm message will be displayed. The compressor and the
regulation are stopped. When the digital input is ON the compressor is always OFF.
If the nPS
activation in the did time is reached, switch off and on the instrument to restart normal
regulation.
16.5
AUXILIARY OUTPUT CONTROL (AUS)
To activate and deactivate the auxiliary output