Emerson Dixell XRi77CX Installing And Operating Instructions Download Page 4

 

1592020670 XRi77CX-CH GB r1.1 15.10.2019

 

XRi77CX-CH

 

4/9

 

MCo 

Maximum time with compressor active:

 (0 to 255 min) if compressor working time 

is over MCo, it will be stopped. MCo=0 means function disabled. 

rtr 

F(P1; P2) percentage for regulation: 

(0 to 100; 100=P1, 0=P2) it allows to set the 

regulation  according  to  the  percentage  of  the  first  and  second  probe,  as  for  the 
following formula (rtr(P1-P2)/100 + P2). 

CCt 

Maximum duration for Pull Down:

 (0.0 to 24h00min, res. 10min) allows setting the 

length of the PULL-DOWN cycle. Compressor stays on without interruption during 

CCt

 

time. This is useful, for instance, when the room is filled with new products. 

CCS 

Differential for Pull Down:

 (-12 to  12°C; -21  to  21°F) relative value to  add  to  the 

regulation SETPOINT and to use during any PULL-DOWN cycle. 

oHt 

Threshold for automatic activation of Pull Down in normal mode:

 (0.0 to 25.5°C; 

0 to 45°F) upper threshold for auto activation of a PULL DOWN 

Con 

Compressor  ON  time  with  faulty  probe:

  (0  to  255min)  time  during  which  the 

compressor is active in case of faulty thermostat probe. With 

Con=0

 compressor is 

always OFF. 

CoF 

Compressor  OFF  time  with  faulty  probe:

  (0  to  255min)  time  during  which  the 

compressor  is  OFF  in  case  of  faulty  thermostat  probe.  With 

CoF=0

  compressor  is 

always active. 

Pon 

Inverter compressor speed during ton (in percentage):

 0 to 100%

 

SCd 

Deactivation of the ONOFF compressor:

 (th1; th2) define when ONOFF compressor is 

stopped. 

th1

=when T<SET+HY; 

th2

 when t<SET 

ton 

Delay before activation of the second compressor (when T> SET + HY + HY1):

 0 to 

255 sec 

toF 

Delay before deactivation of the second compressor: 

0 to 255 sec

 

don 

Minimum operating time of the second compressor: 

0 to 255 sec

 

VARIABLE SPEED COMPRESSOR CONTROL 

HY1 

Differential for normal regulation (compressor cut-in):

 (0.1 to 25.5°C; 1 to 45°F) 

Fr0 

Frequency output value with compressor stopped:

 ([0 Hz ÷ FMi]) 

PMi 

Minimum drive speed (in percentage):

 (0 to PMA) 

PMA 

Maximum drive speed (in percentage):

 (PMi to 100%) 

voS 

Compressor speed variation (increment) when temperature is increasing:

 (1 to 

100  Hz/min,  StP)  StP  =  means  that  inverter  speed  is  adapted  immediately  on 
temperature variation 

vo2 

Compressor speed variation (decrement) when temperature is decreasing:

 (0 to 

100  Hz/min,  StP,  nu)  StP  =  means  that  inverter  speed  is  adapted  immediately  on 
temperature variation; nu = speed decrement disabled 

vo3 

Compressor speed variation (decrement) after any Pull Down:

 (0 to 100 Hz/min, 

StP,  nu)  StP  =  means  that  inverter  speed  is  adapted  immediately  on  temperature 
variation; nu = speed decrement disabled  

PdP 

Variable Speed Drive (in percentage) during any Pull Down:

 0 to 100 % 

t1F 

Time with Variable Speed Drive at minimum before stopping it:

 0 to 999 min 

Spi 

Variable Speed Drive (in percentage) in case of any error probe:

 PMi to PMA 

Aod 

Variable Speed Drive (in percentage) during any defrost:

 PMi to PMA 

AoF 

Variable Speed Drive (in percentage) during a pre-defrost phase

: PMi to PMA 

tH1 

Differential for deadlock control: 

0.1 to 1.0°C

 

oFS 

Compressor speed increment during any deadlock condition: 

1 to 10Hz

 

CMn 

Continuous mode regulation when normal mode: 

(n; Y) 

CME 

Continuous mode regulation when energy saving mode:

 (n; Y) 

MnP 

Minimum  compressor  speed  for  activating  lubrication  control  (valid  only  for 
Variable Speed Drive):

 (nu, 1÷99%, OFF) nu = function disabled; OFF = compressor 

is stopped for tMA time 

tMi 

Compressor running time below the MnP threshold:

 (0.0 to 24h00min) 

tMA 

Lubrication control interval:

 0 to 255 min 

PROBES 

PbC 

Temperature probe selection: 

ntC; PtC; PT1000 

ot 

Probe P1 calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible offset 

of the thermostat probe. 

P2P 

Probe P2 presence:

 (n; Y) 

n

 = not present, the defrost stops by time;  

Y

 = present, the defrost stops by temperature. 

oE 

Probe P2 calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible offset 

of the evaporator probe. 

P3P 

Probe P3 presence:

 (n; Y) 

n

 = not present, the  terminals 18-20  operate  as digital 

input; 

Y

 = present, the terminals 18-20 operate as third probe. 

o3 

Probe P3 calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible offset 

of the third probe. 

P4P 

Probe P4 presence:

 (n; Y) 

n

 = not present; 

Y

 = present 

o4 

Probe P4 calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible offset 

of the fourth probe 

DISPLAY 

CF 

Temperature measurement unit: 

(°C; °F) °C = Celsius; °F = Fahrenheit.  

WARNING: When the measurement unit is changed the SET point and the values of 
the  parameters HY,  LS, US,  ot, ALU and ALL have to be checked and modified  (if 
necessary). 

rES 

Resolution for °C: 

(in=1°C; dE=0.1°C) allows decimal point display. 

Lod 

Probe visualized 

(P1; P2, P3, P4, SET, dtr) it selects which probe is displayed by the 

instrument. P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe (only for 
model with this option enabled); P4 = Fourth probe, SET = set point; dtr = percentage 
of visualization. 

dLY 

Temperature visualization delay: 

(0 to 20min00s; res. 10 sec) when the temperature 

increases, the display is updated of 1°C or 1°F after this time. 

dtr 

Visualization percentage=F(P1;P2)

: (1 to 99; 99=P1, 1=P2) if Lod=dtr it allows to set 

the visualization according to the percentage of the first and second probe, as for the 
following formula (dtr(P1-P2)/100 + P2). 

DEFROST 

EdF 

Defrost mode (only for controller with RTC): rtC

=Real Time Clock mode. Defrost 

time follows dd1...dd6 and Ld1

Ld6 parameters on working days. 

in

=interval mode. 

The defrost starts when the time idF is expired. 

tdF 

Defrost type: 

(EL; in) EL = electrical heater; in = hot gas. 

dFP 

Probe selection for defrost control: 

(nP; P1; P2; P3; P4) nP = no probe;  

P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on 
Hot Key plug. 

dtE 

Defrost end temperature: 

(-55 to 50°C; -67 to 122°F) (enabled only when EdF=Pb) 

sets  the  temperature  measured  by  the  evaporator  probe,  which  causes  the  end  of 
defrost. 

idF 

Interval between two consecutive defrost cycles: 

(0 to 120 hours) determines the 

interval of time between two defrost cycles. 

MdF    Maximum length for any defrost: 

(0 to 255min) when P2P=n, (not evaporator probe: 

timed  defrost)  it  sets  the  defrost  duration.  When  P2P=Y  (defrost  end  based  on 
temperature) it sets the maximum length for defrost. 

dSd 

Start  defrost  delay:

  (0  to  255  sec)  when  a  defrost  starts,  the  compressor  will  be 

stopped and the defrost output delayed. If 

dSd=0

 this function is disabled. 

StC 

Compressor stop before activating any defrost

: (0 to 255 sec) is used to delay the 

compressor restart when the defrost is managed for inversion of cycle (hot-gas). 

dFd    Displaying during any defrost: 

(rt; it; Set; dEF) rt = real temperature;  

it = temperature at defrost start; Set = set point; dEF 

= “

dEF

” label

dAd 

Delay  for  display  temperature  update  after  any  defrost: 

(0  to  255min)  sets  the 

maximum time between the end of a defrost and the beginning of the visualization of 
the real room temperature. 

Fdt 

Draining  time: 

(0  to  120min)  time  interval  between  reaching  defrost  termination 

temperature and t

he restoring of the control’s normal operation. This time allows the 

evaporator to eliminate water drops that might have formed due to defrost. 

Hon 

Time with drain heater activated after drainig time Fdt (valid is oAx=HEt):

 (0.0 to 

24h00min, res. 10 min) the heating elements stay on for this time after finishing the 
dripping phase. 

dPo 

Defrost after power on:

 (n; Y) n = after the idF time or following RTC, Y = immediately. 

dAF 

Pre-defrost time

: (0 to 255 min) it is used to sub freeze the goods before activating 

any  defrost. The regulation setpoint is modified to SET-1°C  or SET-2°F during this 
interval. If dAF=0 this function is disabled. 

FANS 

FAP 

Probe selection for evaporator fan:

 (nP; P1; P2; P3; P4) nP = no probe;  

P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on 
Hot Key plug. 

FSt 

Evaporator fan stop temperature: 

(-50 to 50°C; -55 to 122°F) setting of temperature, 

detected by evaporator probe, above which fans are always OFF. 

HY 

Differential for evaporator fan regulator:

 (0.1 to 25.5°C; 1 to 45°F)

 

FnC 

Evaporator fan mode operation: 

(C-n; o-n; C-Y; o-Y) C-n = runs with the compressor, 

OFF during defrost; o-n = continuous mode, OFF during defrost; C-Y = runs with the 
compressor, ON during defrost; o-Y = continuous mode, ON during defrost. 

Fnd 

Evaporator  fan  delay  after  defrost: 

(0  to  255min)  interval  between  the  end  of  a 

defrost and the next evaporator fans start. 

FCt 

Temperature differential for evaporator fan activation:

 (0 to 59°C; 0 to 90°F) (N.B.: 

FCt=0  means  function  disabled)  if  the  difference  of  temperature  between  the 
evaporator and the room probes is higher than FCt value, the fans will be switched on. 

Ft 

Evaporator fan controlled during any defrost:

 (n;Y) 

Fon 

Evaporator fan ON in normal mode (with compressor OFF): 

(0 to 15min)  

with Fnc=C_n or C_Y, (fan activated in parallel with compressor) it sets the evaporator 
fan ON cycling time when the compressor i

s off. With Fon=0 and FoF≠0 the fan are 

always off, with Fon=0 and FoF=0 the fan are always off. 

FoF 

Evaporator fan OFF in normal mode (with compressor OFF):

 (0 to 15min)  

With FnC=C_n or C_Y, (fan activated in parallel with compressor) it sets the evaporator 
fan off cycling time when the compressor is off.  

With  Fon=0  and  FoF≠0  the  fan  are  always  off,  with  Fon=0  and  FoF=0  the  fan  are 

always off. 

FAC 

Probe selection for condenser fan: 

(nP; P1; P2; P3; P4) nP = no probe;  

P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on 
Hot Key plug. 

St2 

Set Point for condenser fan regulator:

 (-100.0 to 150.0°C; -148 to 302°F) 

HY2 

Differential for condenser fan regulator:

 (0.1 to 25,5°C; 1 to 45°F) 

FCC 

Condenser fan mode operation: 

(C-n; o-n; C-Y; o-Y) C-n = runs with the compressor, 

OFF during defrost; o-n = continuous mode, OFF during defrost; C-Y = runs with the 
compressor, ON during defrost; o-Y = continuous mode, ON during defrost 

FCo 

Condenser fan activated when compressor off (valid if FCC=C-n, C-Y):

 (0 to 999 

sec 

AUXILIARY 

ACH 

Type of action for auxiliary regulator: 

(CL; Ht) CL=cooling; Ht = heating

 

SAA 

Set point for auxiliary regulator: 

(-100.0 to 150.0°C; -148 to 302°F)

 

SHY 

Differential for auxiliary regulator: 

(0.1 to 25.5°C; 1 to 45°F)

 

ArP 

Probe selection for auxiliary regulator: 

(nP; P1; P2; P3; P4) nP = no probe;  

P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on 
Hot Key plug.

 

Sdd 

Auxiliary  regulator  disabled  during  any  defrost:

  (n;  Y) 

n

=the  auxiliary  relay 

operates during defrost. 

Y

=the auxiliary relay is switched off during defrost. 

ALARMS 

ALP 

Temperature  alarm  probe  selection:

  (nP;  P1;  P2;  P3;  P4)  nP  =  no  probe,  the 

temperature  alarms  are  disabled;  P1  =  Probe  1  (Thermostat  probe);  P2  =  Probe  2 
(evaporator probe);  
P3 = Probe 3 (display probe); P4 = Fourth probe. 

ALC    Temperature  alarms  configuration:

  (Ab;  rE)  Ab  =  absolute  temperature,  alarm 

temperature is given by the ALL or ALU values.  rE = temperature alarms are referred 
to  the  set  point.  Temperature  alarm  is  enabled  when  the  temperature  exceeds  the 

[SET+ALU] or [SET-ALL] values. 

ALU 

Maximum temperature alarm:  

If ALC=Ab: [ALL to 150.0°C or ALL to 302°F] 

If ALC=rE: [0.0 to 50.0°C or 0 to 90°F]  
when this temperature is reached the alarm is enabled, after the Ald delay time. 

Summary of Contents for Dixell XRi77CX

Page 1: ...t RTC EdF rtC the defrost is real time controlled depending on the hours set in the parameters Ld1 Ld6 for workdays Other parameters are used to control defrosting cycles the maximum length MdF and defrosting modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 2 1 PR...

Page 2: ... to set the regulation HY1 Differential for proportional regulation 0 1 to 25 5 C 1 to 45 F Fr0 Frequency output value with compressor stopped 0 to 50Hz frequency output signal when compressor stopped PMi Minimum compressor speed in percentage 0 to PMA PMA Maximum compressor speed in percentage PMi to 100 voS Signal output variation increment when temperature is increasing if vdC FrE then 1 to 100...

Page 3: ...g mode by pressing the SET DOWN buttons for 3 sec the C or F LED will start blinking 2 Browse to the required parameter and then press the SET button to display its current value 3 Use UP or DOWN buttons to change its value 4 Press SET button to store the new value and move to the following parameter To exit press SET UP buttons or wait for 15 sec without pressing any key NOTE the set value is sto...

Page 4: ... idF is expired tdF Defrost type EL in EL electrical heater in hot gas dFP Probe selection for defrost control nP P1 P2 P3 P4 nP no probe P1 thermostat probe P2 evaporator probe P3 configurable probe P4 Probe on Hot Key plug dtE Defrost end temperature 55 to 50 C 67 to 122 F enabled only when EdF Pb sets the temperature measured by the evaporator probe which causes the end of defrost idF Interval ...

Page 5: ... condition and its signalling When i1F PAL it is the interval of time to calculate the number of pressure switch activation d2d Digital input 2 alarm delay 0 to 255 min delay between the detection of the external alarm condition and its signalling When i1F PAL it is the interval of time to calculate the number of pressure switch activation nPS Number of pressure alarm events before stopping the re...

Page 6: ... and then turn the Controller ON 3 The parameter list of the HOT KEY will be automatically downloaded into the Controller memory The doL message will blink followed a by a flashing End label 4 After 10 seconds the instrument will restart working with the new parameters 5 Remove the HOT KEY NOTE the message Err is displayed for failed programming In this case turn the unit off and then on if you wa...

Page 7: ...ion for defrost control P2 Pr2 dtE Defrost termination temperature 4 0 Pr2 idF Interval between two consecutives defrost cycles 24 Pr2 MdF Maximum length for defrost 45 Pr2 dSd Start defrost delay 0 Pr2 StC Compressor stop time before starting any defrost 5 Pr2 dFd Displaying during defrost it Pr1 dAd Delay for display temperature update after any defrost 20 Pr1 Fdt Draining time 5 Pr2 Hon Drain h...

Page 8: ...in percentage 100 Pr2 voS_nt Compressor speed variation increment when temperature is increasing 1 Pr2 vo2_nt Compressor speed variation decrement when temperature is decreasing 2 Pr2 vo3_nt Compressor speed variation decrement after any Pull Down 5 Pr2 PdP_nt Compressor speed during any Pull Down 100 Pr2 t1F_nt Time with compressor speed at PMI before stopping the compressor 1 Pr2 SPi_nt Compress...

Page 9: ...arity CL Pr2 i2F_nt Digital input 2 configuration EAL Pr2 did_nt Digital inputs 1 alarm delay 1 Pr1 d2d_nt Digital inputs 2 alarm delay 1 Pr2 nPS_nt Number of pressure alarm switch before stopping the regulation Lock alarm 15 Pr1 OdC_nt Compressor and fan status after door opening F C Pr1 rrd_nt Regulation restart after open door alarm yes Pr1 HES_nt Differential for energy saving mode 0 Pr1 LdE_n...

Reviews: