Emerson Dixell XR60CHC Installing And Operating Instructions Download Page 5

 

1592033080 XR60CHC EN r1.0 2019.01.30 

                           XR60CHC 

5/6 

 

START DEFROST (ixF=dEF) 

It starts a defrost if there are the right conditions. After finishing any defrost, the normal regulation will 
restart only if the digital input is disabled, otherwise the instrument will wait until the 

MdF

 safety time is 

expired. 

ENERGY SAVING (ixF=ES) 

The energy saving mode will be enabled / disabled with the digital input. 

MOTION SENSOR (ixF=EMt) 

It counts the motion sensor detections. 

AUXILIARY OUTPUT (ixF=AUS) 

The AUX output (if present and configured) will be enabled / disabled with the digital input. 

EXTERNAL WARNING ALARM (ixF=EAL) 

It is used to detect an external alarm. It does not lock the regulation. 

EXTERNAL LOCK ALARM (ixF=bAL) 

It is used to detect any critical external alarm. It locks immediately the regulation. 

EXTERNAL PRESSURE ALARM (ixF=PAL) 

It is used to detect any pressure external alarm. This signal locks the regulation after 

nPS

 events in 

dxd

 interval od time. 

EVAPORATOR FAN MODE (ixF=FAn) 

It is used to control the evaporator fan. 

REMOTE HOLYDAY MODE (ixF=HdF) 

It is used to force the holyday mode. 

REMOTE ONOFF (ixF=onF) 

It is used to switch ON and OFF the device remotely. 

LIGHT OUTPUT (ixF=LiG) 

It is used to control the light output. 

CHANGE CONFIGURATION (ixF=CC) 

It is used to change the controller configuration. 

MOTION SENSOR DETECTOR (ixF=EMt) 

To  use  the  X-MOD  motion  sensor.  Please  note  that  motion  sensor  can  be  connected  only  to  the 
HOTKEY port, so it needs digital input 2 properly configurated. 
 

14

 

INSTALLATION AND MOUNTING 

 

Instrument 

XR60CHC

  shall  be  mounted  on  vertical  panel,  in  a 

29x71 mm hole, and fixed using the special bracket supplied. 
The temperature range allowed for correct operation is 0 to 60°C. 

Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 
excessive  dirt  or  humidity.  The  same  recommendations  apply  to 
probes. Let air circulate by the cooling holes. 

 

15

 

OPTIONAL FEATURES 

 

The 

MDP/CX

 rear cover can be used to increase the protection 

from water and dust. 

 

The 

HOT-KEY 

is used for a quick and easy upload (from device 

to 

HOT-KEY

)  or  download  (from 

HOT-KEY

  to  device)  the 

parameter map. 

 

The 

XJ485LE

  serial  interface  converts  the  TTL  output  into  an 

RS485  signal  that  can  be  used  to  connect  the  unit  to  the 
controlling  and  supervising  system.  Please  note  that  other 
version of this converter does not work with XR-CHC devices. 

16

 

ELECTRICAL CONNECTIONS 

The  instrument  is  provided  with  screw  terminal  block  to  connect  cables  with  a  cross  section  up  to 
2.5mm

2

.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s 

requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the 
power  connections.  Do  not  exceed  the  maximum  current  allowed  on  each  relay,  in  case  of  heavier 
loads use a suitable external relay. 

16.1

 

PROBES 

The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to  casual  liquid 
infiltration.  It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly 
measure the average room temperature. Place the defrost  termination probe among  the evaporator 
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination. 

17

 

USE THE HOT-KEY 

17.1

 

SAVE PARAMETERS IN A HOT-KEY (UPLOAD FROM INSTRUMENT) 

1.

 

Program one controller with the front keypad. 

2.

 

When  the  controller  is  ON,  insert  the  “

HOT-KEY

”  an

d  push 

UP

  button;  the 

UP

  message 

appears followed a by flashing “

End

 

3.

 

Push “

SET

” key and the “

End

 will stop flashing. 

4.

 

Turn OFF the instrument 

and then remove the “

HOT-KEY

”.

 At the end turn the instrument ON 

again. 

 

NOTE: 

the “

Err

” message appears in case of a failed programming operation. In this case push again 

the 

UP

 

button if you want to restart the upload again or remove the “

HOT-KEY

” to abort the operation

17.2

 

COPY PARAMETERS FROM A HOT-KEY (DOWNLOAD PARAMETER 

VALUES) 

1.

 

Turn OFF the instrument. 

2.

 

Insert a 

programmed “

HOT-KEY

” into the 5

-PIN port

 and then turn the Controller ON. 

3.

 

T

he parameter list of the “

HOT-KEY

” is 

automatically copied into the controller memory. During 

this operation 

the “

do

” message 

will blink  

4.

 

A flashing 

End

” l

abel will inform that the operation was successful 

5.

 

Remove the “

HOT-KEY

”.

 

6.

 

After some seconds the instrument will restart, using with the new parameters.  

 

NOTE: 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and then 

on 

if you want to restart the download again or remove the “

HOT-KEY

” to abort the operation

18

 

INTERNAL MEMORY 

The controller has an internal memory where are stored: 

-

 

Two different parameter maps identified as 

C1

 and 

C2

 

-

 

Factory default configurations for both 

C1

 and 

C2 

parameters map 

 
The controller is always shipped with: 

-

 

Parameter map 

C1

 = factory default configuration 

C1

 

-

 

Parameter map 

C2

= factory default configuration 

C2

 

Any modification to parameter map 

C1

 or 

C2

 does not change the default factory values. 

It  is  possible  to  change  parameter  map  between 

C1

  and 

C2

  by  using  a  digital  input  or  a  button  properly 

configurated (

ixF

 or 

LG2=CC

). 

It is possible to restore factory defaults values for  both 

C1

 or 

C2

 parameters map by using 

UP2=LdC

 (Load 

default configuration) function.  

 
NOTES:  

-

 

If  controller  is  using 

C1

  parameter  map,  the  factory  default  configuration 

C1

  will  be  reloaded 

overwriting 

C1

 parameter map. The same for parameter map 

C2

-

 

The factory default configurations are read only (it is not possible to modify them on the field). 

19

 

ALARM SIGNALLING 

Label  Cause 

Outputs 

“oFF”

  Keyboard locked 

Outputs unchanged 

“on”

  Keyboard unlocked 

Outputs unchanged 

P1

  Room probe failure 

Compressor output according to 

Con

 e 

CoF

  

P2

  Evaporator probe failure 

Defrost end is timed 

“P3”

  Third probe failure 

Depends on the alarms 

“P4”

  Fourth probe failure 

Linked temperature alarm is not managed 

HA

  Maximum temperature alarm 

Outputs unchanged 

LA

  Minimum temperature alarm 

Outputs unchanged 

“H2”

 

Maximum temperature for second 
temperature alarm 

Outputs unchanged 

“L2”

 

Minimum temperature for second 
temperature alarm 

Outputs unchanged 

“dA”

  Door open more than 

dxd

 time 

Compressor and fans restarts  

“EA”

  External alarm 

Outputs unchanged 

“CA”

  Serious external alarm 

Outputs disabled 

“EE”

  EEPROM alarm 

Outputs unchanged 

19.1

 

ALARM RECOVERY 

Probe alarms 

P1

P2

P3

 

and “

P4

 start some seconds after the fault in the related probe; they 

automatically stop some seconds after the probe restarts normal operation. Check connections before 

replacing the probe. Temperature alarms “

HA

LA

H2

” and “

L2

” 

automatically stop as soon as the 

temperature returns to normal values. 

It is possible to reset the “

EE

” alarm by pressing any button.

 

The alarms “EA”, “CA” and “dA” 

will automatically stop as soon as the digital input is disabled. 

The internal buzzer can be muted by pressing any key if parameter 

tbA=Y

20

 

TECHNICAL DATA 

Housing: 

self-extinguishing ABS

 

Case: 

frontal 32x74 mm; depth 60mm 

Mounting: 

panel mounting in a 71x29mm panel cut-out 

Body Protection: 

IP20 

Frontal protection: 

IP65 

Terminal blocks: 

Screw terminal block 

 2.5 mm

2

 wiring 

Power supply: 

(according to the model) 230Vac 

10%, 50/60Hz; 110Vac 

10%, 50/60Hz

 

Power absorption: 

3.5VA max

 

Display

: 3-digit LED, H=14.2 mm 

Inputs

: up to 4 NTC, PTC or PT1000 probes

 

Digital input: 

 up to 2 voltage free contacts 

Relay outputs:  Compressor 

SPST 16(5)A, 250VAC or SPST 20(8)A, 250VAC  

oA2: 

SPDT 8(2)A, 250VAC;  

oA3: 

SPST 8(3)A, 250VAC or SPST 5(2)A, 250VAC 

Data storing

: EEPROM 

Kind of action: 

1B  

Pollution degree: 

2  

Software class: 

Rated impulsive voltage

: 2500V; 

Overvoltage Category

: II

 

Operating temperature: 

0 to 60°C (32 to 140°F) 

Storage temperature: 

-25 to 60°C (-13 to 140°F) 

Relative humidity:

 20 to 85% (no condensing) 

Measuring and regulation range:  

NTC 

-40 to 110°C (-40 to 230°F) 

PTC

 -55 to 150°C (-67 to 302°F) 

PT1000

 -100 to 200°C (-148 to 392°F) 

Resolution: 

0.1°C or 1°C (selectable) 

Accuracy (ambient temp. 25°C)

:   

Summary of Contents for Dixell XR60CHC

Page 1: ...NERGY SAVING ALGORITHM The energy saving status will be always saved in the internal memory to resume previous operation if a power failure occurs It needs the presence of a door switch to work for example i1F dor 4 2 1 PARAMETER INVOLVED i1F or i2F set as door input to monitor the appliance usage StE interval to change from normal to energy saving mode EtS interval to change from energy saving to...

Page 2: ...ton 4 To memorise the new set point value push the SET button again or wait for 60 sec 10 3 START A MANUAL DEFROST Push the DEFROST button for more than 3 sec to start a manual defrost 11 PARAMETER MENU The device has a parameter menu available from keyboard and where it is possible to modify some specific parameters A couple of parameter levels are present PR1 user menu standard parameters are pl...

Page 3: ...50 C 67 to 122 F it sets the temperature measured by the evaporator probe dFP which causes the end of defrost idF Interval between two consecutive defrost cycles 0 to 255 hours determines the time interval between the beginnings of two defrosting cycles MdF Maximum length for defrost 0 to 255 min 0 means no defrost when P2P n no evaporator probe presence it sets the defrost duration when P2P Y def...

Page 4: ...ns hundreds of read only n3H Number of relay output 3 activations hundreds of read only n3L Number of relay output 3 activations hundreds of read only n5d Number of daily activations of digital input 1 read only n5H Number of digital input 1 activations thousands of read only n5L Number of digital input 1 activations hundreds of read only n6d Number of daily activations of digital input 2 read onl...

Page 5: ...to abort the operation 17 2 COPY PARAMETERS FROM A HOT KEY DOWNLOAD PARAMETER VALUES 1 Turn OFF the instrument 2 Insert a programmed HOT KEY into the 5 PIN port and then turn the Controller ON 3 The parameter list of the HOT KEY is automatically copied into the controller memory During this operation the do message will blink 4 A flashing End label will inform that the operation was successful 5 R...

Page 6: ...MES RSS 102 Le présent appareil est conforme aux CNR d Industrie Canada applicables aux appareils radio RSS 210 L exploitation est autorisée aux deux conditions suivantes 1 l appareil ne doit pas produire de brouillage et 2 l utilisateur de l appareil doit accepter tout brouillage radioélectrique subi même si le brouillage est susceptible d en compromettre le fonctionnement 21 WIRINGS 21 1 XR60CHC...

Reviews: