Emerson DIXELL XR30CHC Installing And Operating Instructions Download Page 5

 

1592034030 XR30CHC EN r1.0 2019.01.31 

                           XR30CHC 

5/6 

 

fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination. 

16

 

USE THE HOT-KEY 

16.1

 

SAVE PARAMETERS IN A HOT-KEY (UPLOAD FROM INSTRUMENT) 

1.

 

Program one controller with the front keypad. 

2.

 

When  the  controller  is  ON,  insert  the  “

HOT-KEY

”  and  push 

UP

  button;  the 

UP

  message 

appears followed a by flashing “

End

 

3.

 

Push “

SET

” key and the “

End

 will stop flashing. 

4.

 

Turn OFF the instrument 

and then remove the “

HOT-KEY

”.

 At the end turn the instrument ON 

again. 

 

NOTE: 

the “

Err

” message appears in case of a failed programming operation. In this case push again 

the 

UP

 

button if you want to restart the upload again or remove the “

HOT-KEY

” to abort the operation

16.2

 

COPY PARAMETERS FROM A HOT-KEY (DOWNLOAD PARAMETER 

VALUES) 

1.

 

Turn OFF the instrument. 

2.

 

Insert a 

programmed “

HOT-KEY

” into the 5

-PIN port

 and then turn the Controller ON. 

3.

 

T

he parameter list of the “

HOT-KEY

” is 

automatically copied into the controller memory. During 

this operation 

the “

do

” message 

will blink  

4.

 

A flashing 

End

” label will inform that the operation was successful

 

5.

 

Remove the “

HOT-KEY

”.

 

6.

 

After some seconds the instrument will restart, using with the new parameters.  

 

NOTE: 

the message “

Err

” is 

displayed for failed programming. In this case turn the unit off and then on 

if you want to restart the download again or remove the “

HOT-KEY

” to abort the operation

17

 

INTERNAL MEMORY 

The controller has an internal memory where are stored: 

-

 

Two different parameter maps identified as 

C1

 and 

C2

 

-

 

Factory default configurations for both 

C1

 and 

C2 

parameters map 

 
The controller is always shipped with: 

-

 

Parameter map 

C1

 = factory default configuration 

C1

 

-

 

Parameter map 

C2

= factory default configuration 

C2

 

Any modification to parameter map 

C1

 or 

C2

 does not change the default factory values. 

It  is  possible  to  change  parameter  map  between 

C1

  and 

C2

  by  using  a  digital  input  or  a  button  properly 

configurated (

ixF

 or 

LG2=CC

). 

It is possible to restore factory defaults values for  both 

C1

 or 

C2

 parameters map by using 

UP2=LdC

 (Load 

default configuration) function.  

 
NOTES:  

-

 

If  controller  is  using 

C1

  parameter  map,  the  factory  default  configuration 

C1

  will  be  reloaded 

overwriting 

C1

 parameter map. The same for parameter map 

C2

-

 

The factory default configurations are read only (it is not possible to modify them on the field). 

18

 

ALARM SIGNALLING 

Label  Cause 

Outputs 

“oFF”

  Keyboard locked 

Outputs unchanged 

“on”

  Keyboard unlocked 

Outputs unchanged 

P1

  Room probe failure 

Compressor output according to 

Con

 e 

CoF

  

P2

  Evaporator probe failure 

Defrost end is timed 

“P3”

  Third probe failure 

Depends on the alarms 

HA

  Maximum temperature alarm 

Outputs unchanged 

LA

  Minimum temperature alarm 

Outputs unchanged 

“H2”

 

Maximum temperature for second 
temperature alarm 

Outputs unchanged 

“L2”

 

Minimum temperature for second 
temperature alarm 

Outputs unchanged 

“dA”

  Door open more than 

dxd

 time 

Compressor and fans restarts  

“EA”

  External alarm 

Outputs unchanged 

“CA”

  Serious external alarm 

Outputs disabled 

“EE”

  EEPROM alarm 

Outputs unchanged 

18.1

 

ALARM RECOVERY 

Probe  alarms 

P1

P2

 

and  “

P3

  start  some  seconds  after  the  fault  in  the  related  probe;  they 

automatically stop some seconds after the probe restarts normal operation. Check connections before 

replacing the probe. Temperature alarms “

HA

LA

H2

” and “

L2

” 

automatically stop as soon as the 

temperature returns to normal values. 

It is possible to reset the “

EE

” alarm by pressing any button.

 

The alarms “EA”, “CA” and “dA” 

will automatically stop as soon as the digital input is disabled. 

The internal buzzer can be muted by pressing any key if parameter 

tbA=Y

19

 

TECHNICAL DATA 

Housing: 

self-extinguishing ABS

 

Case: 

frontal 32x74 mm; depth 60mm 

Mounting: 

panel mounting in a 71x29mm panel cut-out 

Body Protection: 

IP20 

Frontal protection: 

IP65 

Terminal blocks: 

Screw terminal block 

 2.5 mm

2

 wiring 

Power supply: 

(according to the model) 230Vac 

10%, 50/60Hz; 110Vac 

10%, 50/60Hz

 

Power absorption: 

3.5VA max

 

Display

: 3-digit LED, H=14.2 mm 

Inputs

: up to 4 NTC, PTC or PT1000 probes

 

Digital input: 

 up to 2 voltage free contacts 

Relay outputs:  Compressor 

SPST 16(5)A, 250VAC 

oA2: 

SPDT 8(2)A, 250VAC;  

Data storing

: EEPROM 

Kind of action: 

1B  

Pollution degree: 

2  

Software class: 

Rated impulsive voltage

: 2500V; 

Overvoltage Category

: II

 

Operating temperature: 

0 to 60°C (32 to 140°F) 

Storage temperature: 

-25 to 60°C (-13 to 140°F) 

Relative humidity:

 20 to 85% (no condensing) 

Measuring and regulation range:  

NTC 

-40 to 110°C (-40 to 230°F) 

PTC

 -55 to 150°C (-67 to 302°F) 

PT1000

 -100 to 200°C (-148 to 392°F) 

Resolution: 

0.1°C or 1°C (selectable) 

Accuracy (ambient temp. 25°C):

  ±0.1°C ±1 digit 

Real time clock:

 data maintenance up to 6 months with lithium battery 

HOT-KEY inputs:

 MAX voltage allowed is 3.3VDC. DO NOT CONNECT ANY EXTERNAL POWER 

SUPPLY. 

19.1

 

STANDARDS 

 

The complete Declaration of Conformity can be found at:  

 

https://dxapp.cloud/ 

19.1.1

 

THE XR30CHC IS COMPLIANT WITH THE FOLLOWING STANDARDS  

ETSI EN 300 328 V2.1.1 (2016-11) 
ETSI EN 301 489-17 V3.1.1 (2016-11) 
IEC EN 60730-2-9: 2008 (Third Edition) and Am.1:2011 in conjunction with IEC 60730-1:2010 (Fourth Edition)  
UL  60730-1  Fourth  Edition  and  CAN/CSA-E60730-1:02  Third  Edition  along  with  its  Amendment  1  dated 
February 2007, the Standards for Automatic electrical controls for household and similar use 

 Part 1: General 

requirements. 
 
It therefore meets the essential requirements of the following Directives: 

Radio equipment Directive 2014/53/EU 
Electromagnetic compatibility 2004/108/EC 
Low Voltage equipment 2006/95/EC 

19.1.2

 

THE XR30CHC IS COMPLIANT WITH THE FOLLOWING STANDARDS 

FCC 15.247 

19.1.3

 

THE XR30CHC IS COMPLIANT TO PART 15 OF THE FCC RULE 

Operation is subject to the following two conditions:  
(1) this device may not cause harmful interference, and  
(2)  this  device  must  accept  any  interference  received,  including  interference  that  may  cause  undesired 

operation.”

 

 
Unauthorized repairs, changes or modifications could result in permanent damage to the equipment and void 
your warranty and your authority to operate this device under Part 15 of the FCC Rules. 

 

NOTE:  This  equipment  has  been  tested  and  found  to  comply  with  the  limits  for  a  Class  A  digital  device, 
pursuant  to  part  15  of  the  FCC  Rules.  These  limits  are  designed  to  provide  reasonable  protection against 
harmful interference when the equipment is operated in a commercial environment. This equipment generates, 
uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction 
manual, may cause harmful interference to radio communications. Operation of this equipment in a residential 
area is likely to cause harmful interference in which case the user will be required to correct the interference at 
his own expense. 

19.1.4

 

THE XR30CHC IS COMPLIANT TO RSS 102 

This device complies with Industry Canada RSS-210. Operation is subject to the following two conditions: (1) 
this  device  may  not  cause  interference,  and  (2)  this  device  must  accept  any  interference,  including 
interference that may cause undesired operation of the device. 

 

19.1.5

 

CET XR30CHC INSTRUMENT REPOND AUX NORMES RSS 102 

Le  présent  appareil  est  conforme  aux  CNR  d’Industrie  Canada  applicables  aux  appareils  radio  RSS

-210. 

L’exploitation est autorisée aux deux conditions suivantes : (1) l’appareil ne doit pas produire de brouillage, et 

(2) 

l’utilisateur  de  l’appareil  doit  accepter  tout  brouillage  radioélectrique  subi,  même  si  le  brouillage  est 

susceptible d’en compromettre le fonctionnement.

 

20

 

WIRINGS 

20.1

 

XR30CHC, 16+8+8AMP  

 

 

Power Supply (terminals 5-6):

  

110 or 230 Vac @50 or 60Hz 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for DIXELL XR30CHC

Page 1: ...lways saved in the internal memory to resume previous operation if a power failure occurs It needs the presence of a door switch to work for example i1F dor 4 2 1 PARAMETER INVOLVED i1F or i2F set as door input to monitor the appliance usage StE interval to change from normal to energy saving mode EtS interval to change from energy saving to normal mode HES differential for SETPOINT when energy sa...

Page 2: ...fter ending the installing operations 10 3 1 ENTER THE PROTECTED LEVEL 1 Enter the Programming mode by pressing SET DOWN buttons for 3 sec C or F LED starts blinking 2 Released the buttons and then search for submenu Pr2 3 Per SET button and then insert the password value 4 Confirm with SET If the password is correct the label Pr2 will blink for some time and then protected parameter menu will be ...

Page 3: ...he alarm is enabled after the Ad delay time If ALC Ab 55 0 C to ALU or 67 F to ALU If ALC rE 0 0 to 50 0 C or 0 to 90 F AFH Differential for temperature alarm recovery 0 1 to 25 0 C 1 to 45 F differential for alarms ALd Temperature alarm delay 0 to 255 min delay time between the detection of an alarm condition and the relative alarm signalling dot Delay of temperature alarm with door open 0 0 to 2...

Page 4: ...value visualization ES change working mode from normal to energy saving mode and vice versa LG2 Light button timed 3sec configuration left upper side nu not used LiG light output control AUS auxiliary output control dEF defrost control CC change configuration between NT and LT map ES change working mode from normal to energy saving mode and vice versa UP2 Up button timed 3sec configuration nu not ...

Page 5: ...ousing self extinguishing ABS Case frontal 32x74 mm depth 60mm Mounting panel mounting in a 71x29mm panel cut out Body Protection IP20 Frontal protection IP65 Terminal blocks Screw terminal block 2 5 mm2 wiring Power supply according to the model 230Vac 10 50 60Hz 110Vac 10 50 60Hz Power absorption 3 5VA max Display 3 digit LED H 14 2 mm Inputs up to 4 NTC PTC or PT1000 probes Digital input up to ...

Page 6: ...roller via Bluetooth Extend rights of access to a specific appliance also to other users A Cloud portal will be used for Extend rights of access to a specific appliance also to other users Select the permission level for any new user The link for opening the Cloud webpage is on the left side menu of the mobile APP slide right the screen of the APP when on the Device List page and follow the Cloud ...

Reviews: