Emerson DIXELL XR30CHC Installing And Operating Instructions Download Page 4

 

1592034030 XR30CHC EN r1.0 2019.01.31 

                           XR30CHC 

4/6 

 

LdE 

Energy saving mode controls the lights: 

(n; Y) lights off when energy saving mode is active

 

StE 

Period  to  switch  from  normal  mode  to  energy  saving  mode  (valid  if  ErA=bAS): 

(0.0  to 

24h00min,  res.  10  min)  if  door  stay  closed  for 

StE

  time,  the  energy  saving  mode  will  be 

activated. NOTE: this will require a door switch to work.

 

EtS 

Period  to  switch  from  energy  saving  mode  to  normal  mode  (valid  if  ErA=bAS): 

(0.0  to 

24h00min, res. 10 min) maximum time for energy saving mode. NOTE: this will require a door 
switch to work.

 

dS 

Door open time to switch from EtS to StE (valid if ErA=bAS): 

(0 to 999 sec) the energy 

saving mode will be immediately deactivated as soon as the door stay open more than the 

dS 

time. NOTE: this will require a door switch to work. 

TOTAL COUNTERS - Cnt 

n1H 

Number of relay output 1 activations (thousands of) (read only) 

n1L 

Number of relay output 1 activations (hundreds of) (read only) 

n2H 

Number of relay output 2 activations (thousands of) (read only) 

n2L 

Number of relay output 2 activations (hundreds of) (read only) 

n5d 

Number of daily activations of digital input 1 (read only) 

n5H 

Number of digital input 1 activations (thousands of) (read only) 

n5L 

Number of digital input 1 activations (hundreds of) (read only) 

n6d 

Number of daily activations of digital input 2 (read only) 

n6H 

Number of digital input 2 activations (thousands of) (read only) 

n6L 

Number of digital input 2 activations (hundreds of) (read only) 

F1H 

Number of working hours for relay output oA1 (thousands of) (read only) 

F1L 

Number of working hours for relay output oA1 (hundreds of) (read only) 

F2H 

Number of working hours for relay output oA2 (thousands of) (read only) 

F2L 

Number of working hours for relay output oA2 (hundreds of) (read only) 

REAL TIME CLOCK MENU - rtC 

Hur

 

Hours: 

0 to 23 hours

 

Min

 

Minutes:

 0 to 59 minutes

 

dAY

 

Day of the week:

 Sun to Sat

 

dYM

 

Day of the month:

 1 to 31 

Mon

 

Month:

 1 to 12 

YAr

 

Year:

 00 to 99 

Hd1

 

First day of the weekend: 

(Sun to Sat; nu) set the first day of the week which follows 

the holiday times.

 

Hd2

 

Second day of the weekend: 

(Sun to Sat; nu) set the second day of the week which 

follows the holiday times.

 

iLE

 

Working day energy saving starting time:

 (0 to 23h50min) during the Energy Saving 

cycle the set point is increased by the  value in HES so that the operation set point is 

SET+HES

.

 

dLE

 

Working day energy saving duration:

 (0 to 24h00min) sets the duration of the Energy 

Saving cycle on workdays.

 

iSE

 

Holyday energy saving starting time:

 0 to 23h50min.

 

dSE

 

Holyday energy saving duration:

 0 to 24h00min.

 

dd1…d

d6

 

Daily defrost enabled:

 (n; Y) to enable the 

Ld1…Ld6

 defrost operations for any day of 

the week. 

Ld1

Ld6

 

Daily defrost starting time:

 (0 to 23h50min) these parameters set the beginning of the 

6 programmable defrost cycles during workdays. Ex: when 

Ld2=12.4

 the second defrost 

starts at 12.40 during workdays.

 

 

N.B.: 

To disable a defrost cycle set it to “nu”

 (not used).  

Ex: if Ld6=nu; the sixth defrost cycle will be disabled. 

BLUETOOTH - bLE 

btM 

Bluetooth Mode: 

(0; 1; 2) define the pairing&bonding method: 

-

 

0

=6-digit PIN is required for pairing&bonding 

-

 

1,2

=no PIN required (just works mode) 

rPS 

Reset  owner  password: 

(n;Y)  select  and  confirm  YES  to  come  back  to  default  factory 

configuration. NOTE: remember to cancel the device also from the Cloud database (click on 

“Delete” link present on the right of the appliance card present on the “Permissions” webpage.

 

rLi 

Reset whitelist:

 (n;Y) select and confirm YES for reset the device whitelist and come back to 

default factory configuration. 

EEPROM 

 E2 

rSC 

Reset  Daily  Counters: 

used  to  reset  the  daily  counters  memory.  Please  note  that  after 

selecting  rSC=Y  the  device  will  take  some  time  to  complete  the  operation.  During  the  reset 
phase, the display will show some blinking lines.  

OTHER - oth 

Adr 

Serial address:

 (1 to 247) device address for Modbus communication 

bAU 

Baudrate: 

(9.6; 19.2; 38.4; 57.6) select the correct baudrate for serial communication  

brd 

Keyboard lock type: 

(nu; SEL; ALL) 

UnL

=keyboard unlocked; 

SEL

=only SET and DEF/AUX 

button enabled when locked; 

ALL

=keyboard unlocked after 

tLC

tLC 

Keyboard  lock  timeout:

  (0  to  255  sec)  timeout  after  power-on  and  before  activating  the 

keyboard lock  

LGC 

Light  button  configuration  (left  upper  side):  nu

=not  used; 

LiG

=light  output  control; 

AUS

=auxiliary  output  control; 

dEF

=defrost  control; 

Pb2

=probe  2  value  visualization;

 

ES

=change working mode from normal to energy saving mode and vice-versa;

 

LG2 

Light  button  timed  (3sec)  configuration  (left  upper  side):  nu

=not  used; 

LiG

=light  output 

control; 

AUS

=auxiliary output control; 

dEF

=defrost control; 

CC

=change configuration between 

NT and LT map; 

ES

=change working mode from normal to energy saving mode and vice-versa;

 

UP2 

Up  button  timed  (3sec)  configuration:

 

nu

=not  used; 

Std

=standard  function; 

LdC

=load 

default configuration (factory values); 

Pdn

=pull down activation 

VISUALIZATION - ViS 

d1

 

Probe P1 value visualization 

d2 

Probe P2 value visualization 

d3 

Probe P3 value visualization 

rSE 

Real Set point 

FdY 

Firmware release date: day

 

FMt 

Firmware release date: month

 

FYr 

Firmware release date: year

 

rEL 

Firmware release: progressive number 

Sub 

Firmware sub release: progressive number 

Ptb 

Parameter code table 

12

 

DIGITAL INPUTS 

The free voltage digital input is programmable in different configurations by the 

i1F

 and 

i2F

DOOR SWITCH (ixF=dor) 

It signals the door status and the corresponding relay output status through the 

odC

 parameter:  

no

 = normal (any change); 

FAn

 = Fan OFF; 

CPr

 = Compressor OFF; 

F-C

 = Compressor and fan OFF. 

Since the door is opened, after the delay time set through parameter 

did

, the door alarm is enabled, 

the display shows the message 

dA

 and 

the regulation restarts if rrd = Y.

 The alarm stops as soon 

as the external digital input is disabled again. With the door open, the high and low temperature alarms 
are disabled. 

START DEFROST (ixF=dEF) 

It starts a defrost if there are the right conditions. After finishing any defrost, the normal regulation will 
restart only if the digital input is disabled, otherwise the instrument will wait until the 

MdF

 safety time is 

expired. 

ENERGY SAVING (ixF=ES) 

The energy saving mode will be enabled / disabled with the digital input. 

MOTION SENSOR (ixF=EMt) 

It counts the motion sensor detections. 

AUXILIARY OUTPUT (ixF=AUS) 

The AUX output (if present and configured) will be enabled / disabled with the digital input. 

EXTERNAL WARNING ALARM (ixF=EAL) 

It is used to detect an external alarm. It does not lock the regulation. 

EXTERNAL LOCK ALARM (ixF=bAL) 

It is used to detect any critical external alarm. It locks immediately the regulation. 

EXTERNAL PRESSURE ALARM (ixF=PAL) 

It is used to detect any pressure external alarm. This signal locks the regulation after 

nPS

 events in 

dxd

 interval od time. 

EVAPORATOR FAN MODE (ixF=FAn) 

It is used to control the evaporator fan. 

REMOTE HOLYDAY MODE (ixF=HdF) 

It is used to force the holyday mode. 

REMOTE ONOFF (ixF=onF) 

It is used to switch ON and OFF the device remotely. 

LIGHT OUTPUT (ixF=LiG) 

It is used to control the light output. 

CHANGE CONFIGURATION (ixF=CC) 

It is used to change the controller configuration. 

MOTION SENSOR DETECTOR (ixF=EMt) 

To use the X-MOD motion sensor. Please note that the motion sensor can be connected only to the 
HOTKEY port, so it needs digital input 2 properly configurated. 

13

 

INSTALLATION AND MOUNTING 

 

Instrument 

XR30CHC

  shall  be  mounted  on  vertical  panel,  in  a 

29x71 mm hole, and fixed using the special bracket supplied. 
The temperature range allowed for correct operation is 0 to 60°C. 
Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 
excessive  dirt  or  humidity.  The  same  recommendations  apply  to 
probes. Let air circulate by the cooling holes. 

 

14

 

OPTIONAL FEATURES 

 

The 

MDP/CX

 rear cover can be used to increase the protection 

from water and dust. 

 

The 

HOT-KEY 

is used for a quick and easy upload (from device 

to 

HOT-KEY

)  or  download  (from 

HOT-KEY

  to  device)  the 

parameter map. 

 

The 

XJ485LE

  serial  interface  converts  the  TTL  output  into  an 

RS485  signal  that  can  be  used  to  connect  the  unit  to  the 
controlling  and  supervising  system.  Please  note  that  other 
version of this converter does not work with XR-CHC devices. 

15

 

ELECTRICAL CONNECTIONS 

The  instrument  is  provided  with  screw  terminal  block  to  connect  cables  with  a  cross  section  up  to 
2.5mm

2

.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s 

requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the 
power  connections.  Do  not  exceed  the  maximum  current  allowed  on  each  relay,  in  case  of  heavier 
loads use a suitable external relay. 

15.1

 

PROBES 

The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to  casual  liquid 
infiltration.  It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly 
measure the average room temperature. Place the defrost  termination probe among  the evaporator 

Summary of Contents for DIXELL XR30CHC

Page 1: ...lways saved in the internal memory to resume previous operation if a power failure occurs It needs the presence of a door switch to work for example i1F dor 4 2 1 PARAMETER INVOLVED i1F or i2F set as door input to monitor the appliance usage StE interval to change from normal to energy saving mode EtS interval to change from energy saving to normal mode HES differential for SETPOINT when energy sa...

Page 2: ...fter ending the installing operations 10 3 1 ENTER THE PROTECTED LEVEL 1 Enter the Programming mode by pressing SET DOWN buttons for 3 sec C or F LED starts blinking 2 Released the buttons and then search for submenu Pr2 3 Per SET button and then insert the password value 4 Confirm with SET If the password is correct the label Pr2 will blink for some time and then protected parameter menu will be ...

Page 3: ...he alarm is enabled after the Ad delay time If ALC Ab 55 0 C to ALU or 67 F to ALU If ALC rE 0 0 to 50 0 C or 0 to 90 F AFH Differential for temperature alarm recovery 0 1 to 25 0 C 1 to 45 F differential for alarms ALd Temperature alarm delay 0 to 255 min delay time between the detection of an alarm condition and the relative alarm signalling dot Delay of temperature alarm with door open 0 0 to 2...

Page 4: ...value visualization ES change working mode from normal to energy saving mode and vice versa LG2 Light button timed 3sec configuration left upper side nu not used LiG light output control AUS auxiliary output control dEF defrost control CC change configuration between NT and LT map ES change working mode from normal to energy saving mode and vice versa UP2 Up button timed 3sec configuration nu not ...

Page 5: ...ousing self extinguishing ABS Case frontal 32x74 mm depth 60mm Mounting panel mounting in a 71x29mm panel cut out Body Protection IP20 Frontal protection IP65 Terminal blocks Screw terminal block 2 5 mm2 wiring Power supply according to the model 230Vac 10 50 60Hz 110Vac 10 50 60Hz Power absorption 3 5VA max Display 3 digit LED H 14 2 mm Inputs up to 4 NTC PTC or PT1000 probes Digital input up to ...

Page 6: ...roller via Bluetooth Extend rights of access to a specific appliance also to other users A Cloud portal will be used for Extend rights of access to a specific appliance also to other users Select the permission level for any new user The link for opening the Cloud webpage is on the left side menu of the mobile APP slide right the screen of the APP when on the Device List page and follow the Cloud ...

Reviews: