1592020010 XR10CX GB m&M r1.1 27.03.2015
XR10CX
3/4
rSE Real set point:
(readable only), it shows the set point used during the energy saving
cycle or during the continuous cycle.
rEL Software release
for internal use
.
Ptb Parameter table code:
readable only
.
8.
DIGITAL INPUT (ENABLED WITH P3P = N)
The free voltage digital input is programmable in different configurations by the “
i1F
”
parameter.
8.1
DOOR SWITCH INPUT (i1F = dor)
It signals the door status and the corresponding relay output status through the “
odc
”
parameter:
no,
Fan
= normal (any change);
CPr,
F_C
= Compressor OFF.
Since the door is opened, after the delay time set through parameter “
did
”, the door alarm is
enabled, the display shows the message “
dA
” and
the regulation restarts is rtr = yES.
The
alarm stops as soon as the external digital input is disabled again. With the door open, the
high and low temperature alarms are disabled.
8.2
GENERIC ALARM (i1F = EAL)
As soon as the digital input is activated the unit will wait for “
did
” time delay before signalling
the “
EAL
” alarm message. The outputs status don’t change. The alarm stops just after the
digital input is de-activated.
8.3
SERIOUS ALARM MODE (i1F = bAL)
When the digital input is activated, the unit will wait for “
did
” delay before signalling the “
CA
”
alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the
digital input is de-activated.
8.4
PRESSURE SWITCH (i1F = PAL)
If during the interval time set by “
did
” parameter, the pressure switch has reached the number
of activation of the “
nPS
” parameter, the “
CA
” pressure alarm message will be displayed. The
compressor and the regulation are stopped. When the digital input is ON the compressor is
always OFF.
If the nPS activation in the did time is reached, switch off and on the instrument to
restart normal regulation.
8.5
INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F = Htr)
This function allows to invert the regulation of the controller: from cooling to heating and
viceversa.
8.6
ENERGY SAVING (i1F = ES)
The Energy Saving function allows to change the set point value as the result of the SET+
HES (parameter) sum. This function is enabled until the digital input is activated.
8.7
DIGITAL INPUTS POLARITY
The digital input polarity depends on the “
i1P
” parameter.
i1P=CL
: the input is activated by closing the contact.
i1P=OP
: the input is activated by opening the contact
9.
TTL SERIAL LINE – FOR MONITORING SYSTEMS
The TTL serial line, available through the HOT KEY connector, allows by means of the
external TTL/RS485 converter,
XJ485-CX
, to connect the instrument to a monitoring system
ModBUS-RTU
compatible such as the X-WEB500/3000/300.
10.
X-REP OUTPUT – OPTIONAL
As optional, an X-REP can be connected to the instrument, trough the HOY
KEY connector. The X-REP output
EXCLUDES
the serial connection.
To connect the X-REP to the
instrument the following
connectors must be used CAB-
51F(1m), CAB-52F(2m), CAB-
55F(5m),
11.
INSTALLATION AND MOUNTING
Instrument
XR10CX
shall be mounted on vertical panel, in a
29x71 mm hole, and fixed using the special bracket supplied.
The temperature range allowed for correct operation is 0
60
°C. Avoid places subject to strong vibrations, corrosive
gases, excessive dirt or humidity. The same
recommendations apply to probes. Let air circulate by the
cooling holes.
12.
ELECTRICAL CONNECTIONS
The instrument is provided with screw terminal block to connect cables with a cross section up
to 2,5 mm
2
. Before connecting cables make sure the power supply complies with the
instrument’s requirements. Separate the probe cables from the power supply cables, from the
outputs and the power connections. Do not exceed the maximum current allowed on each
relay, in case of heavier loads use a suitable external relay.
12.1
PROBE CONNECTION
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
infiltration. It is recommended to place the thermostat probe away from air streams to correctly
measure the average room temperature. Place the defrost termination probe among the
evaporator fins in the coldest place, where most ice is formed, far from heaters or from the
warmest place during defrost, to prevent premature defrost termination.
13.
HOW TO USE THE HOT KEY
13.1
HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1.
Program one controller with the front keypad.
2.
When the controller is ON, insert the “
Hot key
” and push
o
key; the
"uPL"
message
appears followed a by flashing
“End”
3.
Push “
SET”
key and the
End
will stop flashing.
4.
Turn OFF the instrument remove the
“Hot Key”,
then turn it ON again.
NOTE
: the “
Err
” message is displayed for failed programming. In this case push again
o
key
if you want to restart the upload again or remove the “
Hot key
” to abort the operation.
13.2
HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY
(DOWNLOAD)
1.
Turn OFF the instrument.
2.
Insert a
programmed “Hot Key” into the 5 PIN receptacle
and then turn the
Controller ON.
3.
Automatically the parameter list of the
“Hot Key”
is downloaded into the Controller
memory, the “
doL
” message is blinking followed a by flashing
“End”.
4.
After 10 seconds the instrument will restart working with the new parameters.
5.
Remove the
“Hot Key”.
.
NOTE
the message “
Err
” is displayed for failed programming. In this case turn the unit off and
then on if you want to restart the download again or remove the “
Hot key
” to abort the
operation.
14.
ALARM SIGNALS
Message
Cause
Outputs
“P1”
Room probe failure
Compressor output acc. to par. “Con” and
“COF”
“P3”
Third probe failure
Outputs unchanged
“P4”
Fourth probe failure
Outputs unchanged
“HA”
Maximum temperature alarm
Outputs unchanged.
“LA”
Minimum temperature alarm
Outputs unchanged.
"HA2"
Condenser high temperature
It depends on the “Ac2” parameter
"LA2"
Condenser low temperature
It depends on the “bLL” parameter
“dA”
Door open
Compressor according to rrd
“EA”
External alarm
Output unchanged.
“CA”
Serious
external
alarm
(i1F=bAL)
All outputs OFF.
“CA”
Pressure
switch
alarm
(i1F=PAL)
All outputs OFF
14.1
ALARM RECOVERY
Probe alarms
P1
”, “
P3
” and “
P4
” start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Check
connections before replacing the probe.
Temperature alarms “
HA
”, “
LA
” “
HA2
” and “
LA2
” automatically stop as soon as the
temperature returns to normal values.
Alarms
“EA”
and
“CA”
(with i1F=bAL)
recover as soon as the digital input is disabled.
Alarm “
CA”
(with i1F=PAL) recovers only by
switching off and on
the instrument.
14.2
OTHER MESSAGES
Pon
Keyboard unlocked.
PoF
Keyboard locked
noP
In programming mode
: none parameter is present in Pr1
On the display
or in dP2, dP3, dP4: the selected probe is nor enabled
noA
None alarm is recorded.
15.
TECHNICAL DATA
Housing:
self extinguishing ABS.
Case: XR10CX
frontal 32x74 mm; depth 60mm;
Mounting: XR10CX
panel mounting in a 71x29mm panel cut-out
Protection:
IP20;
Frontal protection: XR10CX
IP65
Connections:
Screw terminal block
2,5 mm
2
wiring.
Power supply:
according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac
10%,
50/60Hz, 110Vac
10%, 50/60Hz
Power absorption:
3VA max
Display
: 3 digits, red LED, 14,2 mm high;
Inputs
: Up to 3 NTC or PTC probes.
Digital input:
free voltage contact
Relay outputs: compressor
SPST 8(3) A, 250Vac; or 20(8)A 250Vac
Data storing
: on the non-volatile memory (EEPROM).
Kind of action:
1B;
Pollution grade:
2;
Software class:
A.;
Rated impulsive voltage
: 2500V;
Overvoltage Category
: II
Operating temperature:
0÷60 °C;
Storage temperature:
-30÷85 °C.
Relative humidity:
20
85% (no condensing)
Measuring and regulation range: NTC probe:
-40÷110°C (-40÷230°F);
PTC probe:
-50÷150°C (-58÷302°F)
Resolution:
0,1 °C or 1°C or 1 °F (selectable);
Accuracy (ambient temp. 25°C)
: ±1 °C ±1
digit