Emerson Dixell XR10CX Installing And Operating Instructions Download Page 3

 

 

1592020010 XR10CX GB m&M r1.1 27.03.2015 

XR10CX 

3/4 

rSE  Real  set  point: 

(readable  only),  it  shows  the  set  point  used  during  the  energy  saving 

cycle or during the continuous cycle. 

rEL  Software release 

for internal use

Ptb  Parameter table code: 

readable only

8.

 

DIGITAL INPUT (ENABLED WITH P3P = N) 

The free voltage digital input is programmable in different configurations by the “

i1F

” 

parameter. 

8.1

 

DOOR SWITCH INPUT  (i1F = dor) 

It  signals  the  door  status  and  the  corresponding  relay  output  status  through  the  “

odc

” 

parameter: 

no,

 

Fan

 = normal (any change); 

CPr, 

  

F_C

 = Compressor OFF. 

Since the door is opened, after the delay time set through parameter “

did

”, the door alarm is 

enabled, the display shows the message “

dA

” and 

the regulation restarts is rtr = yES.

 The 

alarm stops as soon as the external digital input is disabled again. With the door open, the 
high and low temperature alarms are disabled. 

8.2

 

GENERIC ALARM (i1F = EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before signalling 

the  “

EAL

”  alarm  message.  The  outputs status don’t  change.  The  alarm stops  just  after the 

digital input is de-activated. 

8.3

 

SERIOUS ALARM MODE (i1F = bAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the “

CA

” 

alarm  message.  The  relay  outputs  are  switched  OFF.  The  alarm  will  stop  as  soon  as  the 
digital input is de-activated. 

8.4

 

PRESSURE SWITCH (i1F = PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached the number 

of activation of  the “

nPS

” parameter, the “

CA

” pressure alarm message will be displayed. The 

compressor and the regulation are stopped. When the digital input is ON the compressor is 
always OFF. 

If  the  nPS  activation  in  the  did  time  is  reached,  switch  off  and  on  the  instrument  to 
restart normal regulation. 

8.5

 

INVERSION OF  THE KIND OF ACTION: HEATING-COOLING (i1F = Htr) 

This  function  allows  to  invert  the  regulation  of  the  controller:  from  cooling  to  heating  and 
viceversa. 

8.6

 

ENERGY SAVING (i1F = ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ 
HES (parameter) sum. This function is enabled until the digital input is activated. 

8.7

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “

i1P

” parameter. 

i1P=CL

: the input is activated by closing the contact.

 

i1P=OP

: the input is activated by opening the contact 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The  TTL  serial  line,  available  through  the  HOT  KEY  connector,  allows  by  means  of  the 
external TTL/RS485 converter, 

XJ485-CX

, to connect the instrument to a monitoring system 

ModBUS-RTU

 compatible  such as the  X-WEB500/3000/300. 

10.

 

X-REP OUTPUT – OPTIONAL 

As optional, an X-REP can be connected to the instrument, trough the HOY 
KEY connector. The X-REP output 

EXCLUDES 

 the serial connection.

 

 

To connect the X-REP to the 
instrument the following 
connectors must be used CAB-
51F(1m), CAB-52F(2m), CAB-
55F(5m), 

11.

 

INSTALLATION AND MOUNTING 

 

Instrument 

XR10CX

 shall be mounted on vertical panel, in a 

29x71 mm hole, and fixed using the special bracket supplied.  
The temperature range allowed for correct operation is 0

60 

°C.  Avoid  places  subject  to  strong  vibrations,  corrosive 
gases,  excessive  dirt  or  humidity.  The  same 
recommendations  apply  to  probes.  Let  air  circulate  by  the 
cooling holes. 
 

12.

 

ELECTRICAL CONNECTIONS 

The instrument is provided with screw terminal block to connect cables with a cross section up 
to  2,5  mm

2

.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the 

instrument’s requirements. Separate the probe cables from the power supply cables, from the 
outputs  and  the  power  connections.  Do  not  exceed  the  maximum  current  allowed  on  each 
relay, in case of heavier loads use a suitable external relay. 

12.1

 

PROBE CONNECTION 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid 
infiltration. It is recommended to place the thermostat probe away from air streams to correctly 
measure  the  average  room  temperature.  Place  the  defrost  termination  probe  among  the 
evaporator fins in the coldest place, where most ice is formed, far from heaters or from the 
warmest place during defrost, to prevent premature defrost termination. 

13.

 

HOW TO USE THE HOT KEY  

13.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “

Hot key

” and push 

o

 key; the  

"uPL" 

message 

appears followed a by flashing 

“End”

 

3.

 

Push “

SET”

 key and the 

End

 will stop flashing. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

then turn it ON again. 

 

NOTE

: the “

Err

” message is displayed for failed programming. In this case push again 

o

 key 

if you want to restart the upload again or remove the “

Hot key

” to abort the operation. 

13.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY 

(DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert    a 

programmed  “Hot  Key”  into  the  5  PIN  receptacle 

and  then  turn  the 

Controller ON. 

3.

 

Automatically  the  parameter  list  of  the 

“Hot  Key”

  is  downloaded  into  the  Controller 

memory, the “

doL

” message is blinking followed a by flashing 

“End”.

 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the 

“Hot Key”.

 

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and 

then  on  if  you  want  to  restart  the  download  again  or  remove  the  “

Hot  key

”  to  abort  the 

operation. 

14.

 

ALARM SIGNALS 

Message  

Cause 

Outputs 

“P1” 

Room probe  failure 

Compressor output acc. to par. “Con” and 
“COF” 

“P3” 

Third probe  failure 

Outputs unchanged 

“P4” 

Fourth probe  failure 

Outputs unchanged 

“HA” 

Maximum temperature alarm 

Outputs unchanged. 

“LA”  

Minimum temperature alarm 

Outputs unchanged. 

"HA2" 

Condenser high temperature 

It depends on the “Ac2” parameter 

"LA2" 

Condenser low temperature 

It depends on the “bLL” parameter 

“dA” 

Door open 

Compressor according to rrd 

“EA”  

External alarm 

Output unchanged. 

“CA”  

Serious 

external 

alarm 

(i1F=bAL) 

All outputs OFF. 

“CA” 

Pressure 

switch 

alarm 

(i1F=PAL) 

All outputs OFF 

14.1

 

ALARM RECOVERY  

Probe alarms 

P1

”, “

P3

” and “

P4

” start some seconds after the fault in the related probe; they 

automatically  stop  some  seconds  after  the  probe  restarts  normal  operation.  Check 
connections before replacing the probe. 
Temperature  alarms  “

HA

”,  “

LA

”  “

HA2

”  and  “

LA2

”  automatically  stop  as  soon  as  the 

temperature returns to normal values. 
Alarms 

“EA”

 and 

“CA” 

(with i1F=bAL)

 

recover as soon as the digital input is disabled. 

Alarm “

CA”

 (with i1F=PAL) recovers only by 

switching off and on

 the instrument. 

14.2

 

OTHER MESSAGES 

Pon 

Keyboard unlocked. 

PoF 

Keyboard locked 

noP 

In programming mode

: none parameter is present in Pr1 

On the display

 or in dP2, dP3, dP4: the selected probe is nor enabled 

noA 

None alarm is recorded.

 

15.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: XR10CX 

frontal 32x74 mm; depth 60mm; 

Mounting: XR10CX 

panel mounting in a 71x29mm panel cut-out 

Protection: 

IP20; 

Frontal protection: XR10CX 

IP65 

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring. 

Power supply: 

according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%;  230Vac 

10%, 

50/60Hz, 110Vac 

10%, 50/60Hz

 

Power absorption: 

3VA max

 

Display

: 3 digits, red LED, 14,2 mm high; 

Inputs

: Up to 3 NTC or PTC probes.

 

Digital input: 

 free voltage contact 

Relay outputs: compressor 

SPST 8(3) A, 250Vac; or 20(8)A 250Vac

 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B; 

Pollution grade: 

2;

Software class: 

A.;  

Rated impulsive voltage

: 2500V; 

Overvoltage Category

: II

 

Operating temperature: 

0÷60 °C;

Storage temperature: 

-30÷85 °C.  

Relative humidity:

 20

85% (no condensing) 

Measuring and regulation range: NTC probe: 

-40÷110°C (-40÷230°F);  

PTC probe: 

-50÷150°C (-58÷302°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable); 

Accuracy (ambient temp. 25°C)

:  ±1 °C ±1 

digit 
 

Summary of Contents for Dixell XR10CX

Page 1: ...ut to drive the compressor It is also provided with 2 NTC or PTC probe inputs the first one for temperature control the second one optional to connect to the HOT KEY terminals to signal the condenser temperature alarm or to display a temperature The digital input can operate as third temperature probe The HOT KEY output allows to connect the unit by means of the external module XJ485 CX to a netwo...

Page 2: ...With COn 0 compressor is always OFF COF Compressor OFF time with faulty probe 0 255 min time during which the compressor is OFF in case of faulty thermostat probe With COF 0 compressor is always active CH Type of action CL cooling Ht heating DISPLAY CF Temperature measurement unit C Celsius F Fahrenheit WARNING When the measurement unit is changed the SET point and the values of the parameters Hy ...

Page 3: ...able external relay 12 1 PROBE CONNECTION The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature Place the defrost termination probe among the evaporator fins in the coldest place where most ice is formed far from heaters or from th...

Page 4: ... cL Pr1 CF Temperature measurement unit C F C Pr2 rES Resolution in integer dE dec point dE Pr1 dLy Display temperature delay 0 20 0 min 10 sec 0 Pr2 ALc Temperat alarms configuration rE related to set Ab absolute Ab Pr2 ALU MAXIMUM temperature alarm Set 110 0 C Set 230 F 110 Pr1 ALL Minimum temperature alarm 50 0 C Set 58 F Set 50 0 Pr1 AFH Differential for temperat alarm recovery 0 1 C 25 5 C 1 ...

Reviews: