1592009040 XW263L GB R1.0 04.08.2015 

                           XW263L 

3/4 

 

Es 

= Energy Saving;

 

 

onF 

= remote On/OFF. 

 

did   Time  interval/delay  for  digital  input  alarm:

(0

255  min.) Time interval to  calculate the number of  the 

pressure switch activation when I2F=PAL. If I2F=EAL or bAL (external alarms), “did” parameter defines 
the time delay between the detection and the successive signalling of the alarm. 

SAA  Set  Point  for  anti-condensing  heater:

  (-50,0÷110,0°C;  -58÷230°F)  defines  the  room  temperature 

setpoint  to switch on the anti-condensing heater.

 

 
OTHER 
Adr   RS485  serial  address 

(1÷247)

Identifies  the  instrument  address  when  connected  to  a  ModBUS 

compatible monitoring system. 

Rel   Release software:

 (read only) Software version of the microprocessor. 

Ptb   Parameter table:

 (read only) it shows the original code of the Dixell parameter map. 

Prd    Probes display: 

(read only) display the temperature values of the evaporator probe Pb2 . 

Pr2   Access to the protected parameter list 

(read only). 

6.

 

DIGITAL INPUTS 

The Wing series can support up to 2 free contact digital inputs. One is always configured as door switch, the 
second is programmable in seven different configurations by the “

I2F

” parameter. 

6.1

 

DOOR SWITCH INPUT  

It signals the door status and the corresponding relay output status through the “

odc

” parameter: 

no

 = normal (any change); 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan OFF. 

Since the door is opened, after the delay time set through parameter “

dOA

”, the alarm output is enabled and the 

display shows the message “

dA

”. The alarm stops as soon as the external digital input is disabled again. During 

this time and then for the delay “

dot

” after closing the door, the high and low temperature alarms are disabled. 

6.2

 

CONFIGURABLE INPUT - GENERIC ALARM (EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before signalling the “

EAL

” alarm 

message. The outputs status don’t change. The alarm stops just after the digital input is de-activated. 

6.3

 

CONFIGURABLE INPUT - SERIOUS ALARM MODE (BAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the “

BAL

” alarm message. 

The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated. 

6.4

 

CONFIGURABLE INPUT - PRESSURE SWITCH (PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached the number of activation of  

the “

nPS

” parameter, the “

PAL

” pressure alarm message will be displayed. The compressor and the regulation 

are stopped. When the digital input is ON the compressor is always OFF. 

6.5

 

CONFIGURABLE INPUT - START DEFROST (DFR) 

It  executes  a  defrost  if  there  are  the  right  conditions.  After  the  defrost  is  finished,  the  normal  regulation  will 
restart only if the digital input is disabled otherwise the instrument will wait until the “Mdf” safety time is expired. 

6.6

 

CONFIGURABLE INPUT - ENERGY SAVING (ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ HES (parmeter) sum. 
This function is enabled until the digital input is activated. 

6.7

 

CONFIGURABLE INPUT -  REMOTE ON/OFF (ONF) 

This function allows to switch ON and OFF the instrument. 

6.8

 

DIGITAL INPUTS POLARITY  

The digital inputs polarity depends on “

I1P

” and “

I2P

” parameters. 

 

CL

 : the digital input is activated by closing the contact.

 

 

OP

 : the digital input is activated by opening the contact 

 

7.

 

INSTALLATION AND MOUNTING 

Instruments 

XW263L 

shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two screws 

 3 

x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L). The temperature 
range  allowed  for  correct  operation  is  0  -  60  °C.  Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 
excessive  dirt  or  humidity.  The  same  recommendations  apply  to  probes.  Let  the  air  circulate  by  the  cooling 
holes. 

 

7.1

 

CUT OUT 

 
 
 

165

150

31

+0.5

-0

+0

.5

-0

+1

-1

Ø3 x2

 

 
 
 
 
 
 
 
 
 
 
 
 
 

7.2

 

MOUNTING WITH KEYBOARD COVER OPENING DOWNWARD 

 

CLICK!

1

2

2

3

3

1

1

 

7.3

 

MOUNTING WITH KEYBOARD COVER OPENING UPWARD 

 

 

CLICK!

1

2

2

2

3

3

1

1

 
 

8.

 

ELECTRICAL CONNECTIONS 

The instruments are provided with screw terminal block to connect cables with a cross section up to 2,5 mm

for 

the digital and analogue inputs. Relays and power supply have a Faston connection (6,3mm). Heat-resistant 
cables have to be used. Before connecting cables make sure the power supply complies with the instrument’s 
requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the  power 
connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable 
external relay. 

8.1

 

PROBE CONNECTIONS 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is 
recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly  measure  the  average  room 
temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most ice 
is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination. 
 

9.

 

RS485 SERIAL LINE 

The  RS485  connector  allows  to  connect  the  unit  to  a  network  line 

ModBUS-RTU

  compatible  as  the  Dixell

 

monitoring system XJ500 (Version 3.0). 

10.

 

TTL SERIAL LINE 

The TTL connector allows to upload and download the parameter list of the “

HOT KEY

“. 

11.

 

USE OF THE PROGRAMMING “HOT KEY “ 

The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the 

“Hot 

Key” 

and vice-versa. 

 

11.1

 

DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT) 

1.

 

Turn OFF the instrument by means of the ON/OFF key insert the 

“Hot Key” 

and then turn the Wing ON. 

2.

 

Automatically  the  parameter  list  of  the 

“Hot  Key”

  is  downloaded  into  the  Wing  memory,  the  “

DoL

” 

message is blinking. After 10 seconds the instrument will restart working with the new parameters. 

3.

 

Turn OFF the instrument remove the 

“Hot Key” 

then turn it ON again. 

At the end of the data transfer phase the instrument displays the following messages: 

end

 “ for right programming. The instrument starts regularly with the new programming. 

err

” for failed programming. In this case turn the unit off and then on if you want to restart the download again 

or remove the “

Hot key

” to abort the operation. 

 

 

Summary of Contents for Dixell Wing XW263L

Page 1: ...ature is bigger than SdF parameter At the end of defrost the drip time is controlled through the Fdt parameter 3 4 CONTROL OF EVAPORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C n fans will switch ON and OFF with the compressor and not run during defrost FnC C y fans will run continuously but not during defrost After defrost there is a timed fan delay allowing for ...

Page 2: ...s less than the value in SdF set point for SMARTFROST SdF Set point for SMARTFROST 30 30 C 22 86 F evaporator temperature which allows the IdF counting interval between defrosts in SMARTFROST mode dtE Defrost termination temperature 50 0 110 0 C 58 230 F Enabled only when the evaporator probe is present sets the temperature measured by the evaporator probe which causes the end of defrost IdF Inter...

Page 3: ...ntil the digital input is activated 6 7 CONFIGURABLE INPUT REMOTE ON OFF ONF This function allows to switch ON and OFF the instrument 6 8 DIGITAL INPUTS POLARITY The digital inputs polarity depends on I1P and I2P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 7 INSTALLATION AND MOUNTING Instruments XW263L shall be mounte...

Page 4: ...rescent lights fans relay SPST 8 3 A 250Vac defrost relay SPDT 16 3 A 250Vac Other output alarm buzzer Hot Key output Serial output RS485 standard Communication protocol Modbus RTU Data storing on the non volatile memory EEPROM Kind of action 1B Pollution grade normal Software class A Operating temperature 0 60 C Storage temperature 25 60 C Relative humidity 20 85 no condensing Measuring and regul...