Regulator operation below the maximum pressure limitations 

does not preclude the possibility of damage from external 

sources or debris in the line. The regulator should be 

inspected for damage after any overpressure condition.

startup

The regulator is factory set at approximately the midpoint 

of the spring range or the pressure requested, so an initial 

adjustment may be required to give the desired results. 

With proper installation completed and relief valves properly 

adjusted, slowly open the upstream and downstream 

shutoff valves.

adjustment

note

For types that include the slam-shut module, 

refer to the Instruction Manual for type VsX8 

slam shut (D103127X012) for adjustment and 

maintenance of the slam shut.

To change the outlet pressure, loosen the hex nut and turn 

the adjusting screw clockwise to increase outlet pressure, or 

counterclockwise to decrease it. Monitor the outlet pressure 

with a test gauge during the adjustment. Tighten the locknut 

to maintain the desired setting.

taking out of service (shutdown)

!

WarnIng

to avoid personal injury resulting from 

sudden release of pressure, isolate the 

regulator from all pressure before 

attempting disassembly.

Figure 1.

 Type CSB604 Downstream Control Line Installation

M1063

PrIMary rEgulator

slaM shut

uPstrEaM 

BloCk ValVE

DoWnstrEaM 

BloCk ValVE

MInIMuM oF 6 X outlEt 

PIPIng DIaMEtEr

InlEt PrEssurE
outlEt PrEssurE
atMosPhErIC PrEssurE

Vent Line Installation

The CSB600 Series regulators have a 1 NPT screened vent 

opening in the spring case. If necessary to vent escaping 

gas away from the regulator, install a remote vent line in 

the spring case tapping. Vent piping should be as short 

and direct as possible with a minimum number of bends 

and elbows. The remote vent line should have the largest 

practical diameter. Vent piping on regulators with token relief 

must be large enough to vent all relief valve discharge to 

atmosphere without excessive backpressure and resulting 

excessive pressure in the regulator.
For types with optional token relief, this low capacity relief 

is located in the spring case of the primary regulator. If 

necessary to vent escaping gas away, install a remote vent 

line in the spring case tapping of the primary regulator as 

described above.
Periodically check all vent openings to be sure that they are 

not plugged or obstructed.
CSB600 Series outlet pressure ranges are shown 

in Tables 7a, 7b, 7c and 7d. Outlet pressure higher than 

0.34 bar / 5 psig above the setpoint may damage internal 

parts such as the diaphragm head and valve disk. 

the 

maximum emergency (casing) outlet pressure for all 

types is 4.0 bar / 58.0 psig except for type CsB650 

which is 5.0 bar / 72.5 psig.

overpressure Protection

The recommended pressure limitations are stamped on 

the regulator nameplate. Some type of overpressure 

protection is needed if the actual inlet pressure exceeds the 

maximum operating outlet pressure rating. Overpressure 

protection should also be provided if the regulator inlet 

pressure is greater than the safe working pressure of the 

downstream equipment.

CSB600 Series

7

Summary of Contents for CSB600 Series

Page 1: ...Regulator See Table 5 Slam Shut Module See Tables 7a 7b 7c and 7d Maximum Outlet Pressure 1 Emergency Casing Type CSB600 CSB600F CSB620 CSB620F 4 0 bar 58 0 psig Type CSB650 5 0 bar 72 5 psig To Avoid Internal Metallic Parts Damage Type CSB600 CSB600F CSB620 CSB620F 0 34 bar 5 0 psig over set pressure Type CSB650 1 5 bar 21 8 psig not to exceed maximum emergency outlet Operating Casing Types CSB60...

Page 2: ...imits in this Installation Guide and any applicable standard or code limitation should not be exceeded TYPE NUMBER OPTION C S B 6 PRESSURE CONSTRUCTION 0 Low Pressure Applications Outlet Pressure 9 0 to 110 mbar 3 6 in w c to 1 6 psig 2 2 Medium Pressure Applications Outlet Pressure 61 to 780 mbar 0 9 to 11 3 psig 2 5 High Pressure Applications Outlet Pressure 0 70 to 4 0 bar 10 2 to 58 0 psig 2 O...

Page 3: ... ERSA03656A0 Dark Green 4 88 0 192 224 8 82 CSB620 and CSB624 61 to 110 0 9 to 1 6 ERSA03656A0 Dark Green 4 88 0 192 224 8 82 105 to 220 1 5 to 3 2 ERSA03657A0 Blue 5 94 0 234 217 8 54 210 to 380 3 1 to 5 5 GG06247X012 Black 8 00 0 315 206 8 11 320 to 570 4 6 to 8 3 ERSA01582A0 Red with White Stripe 8 71 0 343 177 6 97 510 to 780 7 4 to 11 3 ERSA05055A0 Blue with White Stripe 10 0 0 394 181 7 13 C...

Page 4: ...1 3400 4000 3100 to 4000 4400 Grey areas indicate that token relief is not available above 500 mbar setpoint 1 Max OPSO setpoint truncated to reflect maximum outlet pressure for spring range Table 7a North American Overpressure Shut off OPSO Only Ranges REGULATOR SLAM SHUT DEVICE Type Typical Setpoint Spring Range Type Maximum Operating Inlet Token Relief Set Relief Range Shown as a of Regulator S...

Page 5: ...75 835 to 1120 1 1050 CSB624F 300 270 to 325 VSX8L 8 6 bar 100 to 500 179 to 386 200 379 to 586 400 CSB654 GrDF 1 bar 0 7 to 1 19 bar VSX8L 16 bar 100 to 500 460 to 932 750 1210 to 1682 1210 CSB654 1 bar 0 7 to 1 19 bar 100 to 500 460 to 932 500 960 to 1432 1320 1 2 bar 1 05 to 2 7 bar VSX8H 16 bar 500 to 2000 1050 to 1570 600 1650 to 2170 1650 1 5 bar 750 1800 to 2320 1900 2 bar 1250 to 2300 1000...

Page 6: ...stallation Warning Failure to install a downstream control line could result in a hazardous condition Install downstream control line s to the slam shut device when construction uses external pressure registration The regulator and slam shut device will not control pressure or shutoff if a downstream control line is not installed on those constructions where external pressure registration is requi...

Page 7: ...600 Series regulators have a 1 NPT screened vent opening in the spring case If necessary to vent escaping gas away from the regulator install a remote vent line in the spring case tapping Vent piping should be as short and direct as possible with a minimum number of bends and elbows The remote vent line should have the largest practical diameter Vent piping on regulators with token relief must be ...

Page 8: ...c plated steel with token relief 45 Screw Zinc plated steel without token relief 46 Token Relief Nut 1 required Steel 50 Pusher Post Aluminum 51 Relief Valve Seat Aluminum 52 Pusher Post O ring Nitrile NBR 53 Pin Stainless steel 54 Roller Pin Brass 55 Diaphragm Assembly 60 Closing Cap Aluminum 61 Bonnet Zinc plated steel 62 O ring Nitrile NBR 63 Upper Spring Seat Zinc plated Carbon steel 64 Adjust...

Page 9: ...ent Pointed Downward and with a Type 289H Relief Valve for High Capacity Relief Protect vent pipe with rain cap CSB600 SERIES regulator DN 50 nps 2 Type 289H relief valve Figure 2 CSB600 Series Regulator Vent Line Installation 1 NPT 3 4 G CSB600 Series 9 ...

Page 10: ...N m 50 TO 60 IN LBS 111F 112 111B 111E 111F 111G 111A 111G 111C 111A 55 43 51 44 53 54 10 14 13 11 17 18 L2 52 L2 19 L2 75 L2 77 TORQUE 3 5 TO 4 N m 31 TO 35 IN LBS 50 76 74 68 L2 L2 100 L1 L1 L1 38 L1 60 S 72 L1 65 L2 62 46 42 41 40 106 36 20 L2 21 L2 TORQUE 34 TO 47 N m 25 TO 35 FT LBS 25 L2 82 8 6 TORQUE 1 7 TO 3 4 N m 15 TO 30 IN LBS 111D 95 80 70 TORQUE 6 TO 8 N m 4 TO 6 FT LBS 71 TORQUE 14 T...

Page 11: ... 10 TO 13 FT LBS 71 70 TORQUE 6 TO 8 N m 4 TO 6 FT LBS 80 15 INITIAL TORQUE 7 TO 9 N m 5 TO 7 FT LBS MINIMUM RELAXATION TORQUE 5 N m 4 FT LBS 64 66 63 40 51 36 TORQUE 3 5 TO 4 N m 31 TO 35 IN LBS 14 112 13 11 76 74 53 68 10 18 96 L2 19 L2 75 L2 77 L2 82 L1 61 L1 L1 111B 105 114 111D 111C 111E 1 9 55 43 50 52 L2 L2 54 L2 TORQUE 34 TO 47 N m 25 TO 35 FT LBS 25 TORQUE 6 TO 7 N m 50 TO 60 IN LBS 45 TO...

Page 12: ...051 419 0611 Asia Pacific Singapore 128461 Singapore T 65 6777 8211 Middle East and Africa Dubai United Arab Emirates T 971 4 811 8100 D103130X014 2017 2018 Emerson Process Management Regulator Technologies Inc All rights reserved 10 18 The Emerson logo is a trademark and service mark of Emerson Electric Co All other marks are the property of their prospective owners Fisher is a mark owned by Fish...

Reviews: