background image

Figure 5. 

CSB650 Series Regulator Assembly

GE32407_AN

aPPly luBrICant (l) anD sEalant (s)

(1)

:

s = MultI-PurPosE PtFE thrEaD sEalant

l1 = antI-sEIzE luBrICant

l2 = EXtrEME loW-tEMPEraturE BEarIng grEasE

1. Lubricants and sealant must be selected such that they meet the temperature requirements.

S

72

16

17

TORQUE: 

14 TO 18 N•m /

10 TO 13 FT-LBS

71

70

TORQUE: 

6 TO 8 N•m /

4 TO 6 FT-LBS

80

15

INITIAL TORQUE: 

7 TO 9 N•m / 5 TO 7 FT-LBS 

 

MINIMUM RELAXATION TORQUE: 

5 N•m / 4 FT-LBS

64

66

63

40

51

36

TORQUE: 

3.5 TO 4 N•m /

31 TO 35 IN-LBS

14

 112

13

11

76

74

53

68

10

18

96

L2

19

L2

75

L2

77

L2

82

L1

61

L1

L1

111B

 105 

 114

111D

111C

111E

 1

 9

55

43

50

52

L2

L2

54

L2

TORQUE: 

34 TO 47 N•m /

25 TO 35 FT-LBS

25

TORQUE: 

6 TO 7 N•m /

50 TO 60 IN-LBS

45

TORQUE: 

10 TO 13 N•m /

7 TO 10 FT-LBS

111F

 100

 113

111A

111G

67

62 L2

TORQUE: 

12 N•m /

9 FT-LBS MAXIMUM

CSB600 Series

11

Summary of Contents for CSB600 Series

Page 1: ...Regulator See Table 5 Slam Shut Module See Tables 7a 7b 7c and 7d Maximum Outlet Pressure 1 Emergency Casing Type CSB600 CSB600F CSB620 CSB620F 4 0 bar 58 0 psig Type CSB650 5 0 bar 72 5 psig To Avoid Internal Metallic Parts Damage Type CSB600 CSB600F CSB620 CSB620F 0 34 bar 5 0 psig over set pressure Type CSB650 1 5 bar 21 8 psig not to exceed maximum emergency outlet Operating Casing Types CSB60...

Page 2: ...imits in this Installation Guide and any applicable standard or code limitation should not be exceeded TYPE NUMBER OPTION C S B 6 PRESSURE CONSTRUCTION 0 Low Pressure Applications Outlet Pressure 9 0 to 110 mbar 3 6 in w c to 1 6 psig 2 2 Medium Pressure Applications Outlet Pressure 61 to 780 mbar 0 9 to 11 3 psig 2 5 High Pressure Applications Outlet Pressure 0 70 to 4 0 bar 10 2 to 58 0 psig 2 O...

Page 3: ... ERSA03656A0 Dark Green 4 88 0 192 224 8 82 CSB620 and CSB624 61 to 110 0 9 to 1 6 ERSA03656A0 Dark Green 4 88 0 192 224 8 82 105 to 220 1 5 to 3 2 ERSA03657A0 Blue 5 94 0 234 217 8 54 210 to 380 3 1 to 5 5 GG06247X012 Black 8 00 0 315 206 8 11 320 to 570 4 6 to 8 3 ERSA01582A0 Red with White Stripe 8 71 0 343 177 6 97 510 to 780 7 4 to 11 3 ERSA05055A0 Blue with White Stripe 10 0 0 394 181 7 13 C...

Page 4: ...1 3400 4000 3100 to 4000 4400 Grey areas indicate that token relief is not available above 500 mbar setpoint 1 Max OPSO setpoint truncated to reflect maximum outlet pressure for spring range Table 7a North American Overpressure Shut off OPSO Only Ranges REGULATOR SLAM SHUT DEVICE Type Typical Setpoint Spring Range Type Maximum Operating Inlet Token Relief Set Relief Range Shown as a of Regulator S...

Page 5: ...75 835 to 1120 1 1050 CSB624F 300 270 to 325 VSX8L 8 6 bar 100 to 500 179 to 386 200 379 to 586 400 CSB654 GrDF 1 bar 0 7 to 1 19 bar VSX8L 16 bar 100 to 500 460 to 932 750 1210 to 1682 1210 CSB654 1 bar 0 7 to 1 19 bar 100 to 500 460 to 932 500 960 to 1432 1320 1 2 bar 1 05 to 2 7 bar VSX8H 16 bar 500 to 2000 1050 to 1570 600 1650 to 2170 1650 1 5 bar 750 1800 to 2320 1900 2 bar 1250 to 2300 1000...

Page 6: ...stallation Warning Failure to install a downstream control line could result in a hazardous condition Install downstream control line s to the slam shut device when construction uses external pressure registration The regulator and slam shut device will not control pressure or shutoff if a downstream control line is not installed on those constructions where external pressure registration is requi...

Page 7: ...600 Series regulators have a 1 NPT screened vent opening in the spring case If necessary to vent escaping gas away from the regulator install a remote vent line in the spring case tapping Vent piping should be as short and direct as possible with a minimum number of bends and elbows The remote vent line should have the largest practical diameter Vent piping on regulators with token relief must be ...

Page 8: ...c plated steel with token relief 45 Screw Zinc plated steel without token relief 46 Token Relief Nut 1 required Steel 50 Pusher Post Aluminum 51 Relief Valve Seat Aluminum 52 Pusher Post O ring Nitrile NBR 53 Pin Stainless steel 54 Roller Pin Brass 55 Diaphragm Assembly 60 Closing Cap Aluminum 61 Bonnet Zinc plated steel 62 O ring Nitrile NBR 63 Upper Spring Seat Zinc plated Carbon steel 64 Adjust...

Page 9: ...ent Pointed Downward and with a Type 289H Relief Valve for High Capacity Relief Protect vent pipe with rain cap CSB600 SERIES regulator DN 50 nps 2 Type 289H relief valve Figure 2 CSB600 Series Regulator Vent Line Installation 1 NPT 3 4 G CSB600 Series 9 ...

Page 10: ...N m 50 TO 60 IN LBS 111F 112 111B 111E 111F 111G 111A 111G 111C 111A 55 43 51 44 53 54 10 14 13 11 17 18 L2 52 L2 19 L2 75 L2 77 TORQUE 3 5 TO 4 N m 31 TO 35 IN LBS 50 76 74 68 L2 L2 100 L1 L1 L1 38 L1 60 S 72 L1 65 L2 62 46 42 41 40 106 36 20 L2 21 L2 TORQUE 34 TO 47 N m 25 TO 35 FT LBS 25 L2 82 8 6 TORQUE 1 7 TO 3 4 N m 15 TO 30 IN LBS 111D 95 80 70 TORQUE 6 TO 8 N m 4 TO 6 FT LBS 71 TORQUE 14 T...

Page 11: ... 10 TO 13 FT LBS 71 70 TORQUE 6 TO 8 N m 4 TO 6 FT LBS 80 15 INITIAL TORQUE 7 TO 9 N m 5 TO 7 FT LBS MINIMUM RELAXATION TORQUE 5 N m 4 FT LBS 64 66 63 40 51 36 TORQUE 3 5 TO 4 N m 31 TO 35 IN LBS 14 112 13 11 76 74 53 68 10 18 96 L2 19 L2 75 L2 77 L2 82 L1 61 L1 L1 111B 105 114 111D 111C 111E 1 9 55 43 50 52 L2 L2 54 L2 TORQUE 34 TO 47 N m 25 TO 35 FT LBS 25 TORQUE 6 TO 7 N m 50 TO 60 IN LBS 45 TO...

Page 12: ...051 419 0611 Asia Pacific Singapore 128461 Singapore T 65 6777 8211 Middle East and Africa Dubai United Arab Emirates T 971 4 811 8100 D103130X014 2017 2018 Emerson Process Management Regulator Technologies Inc All rights reserved 10 18 The Emerson logo is a trademark and service mark of Emerson Electric Co All other marks are the property of their prospective owners Fisher is a mark owned by Fish...

Reviews: