background image

 

 

© 2017 Emerson Climate Technologies, Inc.

 

AE4-1414 

should be properly insulated. See 

Table 6

 of 

AE-1328

 

for thermistor  temperature vs  resistance values.  Refer 
to 

Table  1

  for  part  numbers  of  discharge  line 

thermistors. 

Figure  6

  illustrates  the  discharge 

thermistor. 

Motor Overload Protection 

The  drive  will  provide  motor  over  current  protection  in 
the  event  the  compressor  becomes  mechanically 
locked  or  if  the  load  on  the  compressor  motor  is 
abnormally  high.  The  input  power  supply  to  the  drive 
must be properly fused. 

 

Oil Type

 

The variable speed scrolls are charged with polyolester 
(POE)  oil.  See  the  compressor  nameplate  for  the 
original  oil  charge.  A  complete  recharge  should  be 
approximately  four  fluid  ounces  (118cc)  less  than  the 
nameplate value. Copeland

 Ultra 32-3MAF, available 

from  Emerson  Wholesalers,  should  be  used  if 
additional  oil  is  needed  in  the  field.  Mobil  Arctic 
EAL22CC,  Emkarate  RL22,  Emkarate  32CF  and 
Emkarate 3MAF are acceptable alternatives. 

CAUTION!  POE  oil  must  be  handled  carefully  and 
the  proper  protective  equipment  (gloves,  eye 
protection,  etc.)  must be  used when  handling  POE 
lubricant.  POE  must  not  come  into  contact  with 
any  surface  or  material  that  might  be  harmed  by 
POE,  and  spills  should  be  cleaned up quickly with 
paper towels, soap and water.

 

Maximum Tilt Angle

 

Applications,  such  as  transportation  air  conditioning  or 
mobile radar applications, may require the compressor 
to  operate  at  some  angle  from  vertical.  Service 
personnel may be required to maneuver a unit through 
a  stairwell  or  other  cramped  area  that  might  require 
tilting the unit. The maximum allowable tilt angles from 
horizontal  for  individual  compressors  (not  tandem  or 
trio applications) are summarized below: 

Max. tilt angle with compressor running = 15°  

Max. tilt angle with compressor not running = 60° 

Contaminant Control

 

Copeland Scroll

 compressors leave the factory with a 

miniscule  amount  of  contaminants.  Manufacturing 
processes  have  been  designed  to  minimize  the 
introduction 

of 

solid 

or 

liquid 

contaminants. 

Dehydration  and  purge  processes  ensure  minimal 
moisture  levels  in  the  compressor  and  continuous 
auditing  of  lubricant  moisture  levels  assure  that 
moisture  isn’t  inadvertently  introduced  into  the 
compressor. 

Moisture levels should be maintained below 50 ppm for 
optimal  performance. 

A  filter-drier  is  required  on  all 

R-410A and POE lubricant systems to prevent solid 
particulate  contamination,  oil  dielectric  strength 
degradation,  ice  formation,  oil  hydrolysis,  and 
metal  corrosion.

 

It  is  the  system  designer’s 

responsibility to make sure the filter-drier is adequately 
sized  to  accommodate  the  contaminants  from  system 
manufacturing  processes  that  leave  solid  or  liquid 
contaminants  in  the  evaporator  coil,  condenser  coil, 
and  interconnecting  tubing  plus  any  contaminants 
introduced  during  the  field  installation  process. 
Molecular  sieve  and  activated  alumina  are  two  filter-
drier  materials  designed  to  remove  moisture  and 
mitigate  acid  formation.  A  100%  molecular  sieve  filter 
can  be  used  for  maximum  moisture  capacity.  A  more 
conservative  mix,  such  as  75%  molecular  sieve  and 
25%  activated  alumina,  should  be  used  for  service 
applications.

 

Refrigerant Piping

 

Particular  attention  must  be  given  to  the  system 
refrigerant  pipe  size  with  the  variable  speed  scrolls. 
ASHRAE guidelines for pipe sizing should be followed 
to ensure that refrigerant velocities are high enough at 
low  speeds  to  ensure  oil  return  to  the  compressor.  At 
the same time, high refrigerant velocities at high speed 
operation  can  result  in  excessive  pressure  drop  and 
loss  of  system  efficiency.  A  careful  evaluation  and 
compromise in pipe sizing will likely have to be settled 
upon.  A  compressor  sample  with  a  sight-tube  for 
monitoring  the  oil  level  should  be  used  during  system 
development  to  ensure  an  adequate  oil  level  is 
maintained at operating conditions and speeds.  

If testing shows a gradual, continuous loss of oil in the 
compressor  sight-tube  over  long  run  cycles  at  low 
speed,  an  oil  boost  cycle  should  be  incorporated  into 
the system logic. An oil boost cycle is accomplished by 
ramping the compressor speed up to a higher speed to 
increase  the  refrigerant  flow  rate  to  flush  or  sweep  oil 
back  to  the  compressor.  Frequency  and  duration  of  a 
recovery  cycle  depends  on  many variables  and  would 
have to be determined through testing for each system 
type  and  configuration.  A  default  method  could  be  to 
initiate a recovery cycle at regular intervals.  

Long Pipe Lengths / High Refrigerant Charge 

Some  system  configurations  may  contain  higher-than-
normal  refrigerant  charges  either  because  of  large 
internal coil volumes or long line sets. If such a system 
also contains an accumulator then the permanent loss 
of  oil  from  the  compressor  may  become  critical.  If  the 
system  contains  more  than  20  pounds  (9  kg)  of 
refrigerant,  it  is  our  recommendation  to  add  one  fluid 
ounce of oil for every 5 pounds (15 ml/kg) of refrigerant 

Summary of Contents for Copeland Scroll ZPV066

Page 1: ... Lengths High Refrigerant Charge 7 Discharge Check Valve 8 Suction and Discharge Tube Design 8 Compressor Mounting 8 Discharge Mufflers 8 Airborne Sound Control 8 Expansion Devices 9 Reversing Valves 9 Accumulators 9 Off Cycle Migration Control 9 Manifolded Compressors 10 Manifolded Applications 10 Application Tests 11 General Application Tests 11 Assembly Line Procedures Installing the Compressor...

Page 2: ...ssor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which if not avoided could result in...

Page 3: ...rants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury WARNING BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be used Failure to follow...

Page 4: ...quirements please see the Emerson EVC Drive user guide Ensure correct wiring at both the compressor and drive connections prior to starting the compressor to avoid a mis wire or powered reverse situation These situations may cause compressor damage The variable speed compressor must be paired with the appropriate variable speed drive Do not connect the power supply directly to the compressor Nomen...

Page 5: ...e includes motor protection features for the compressor The drive sets the maximum current limit low voltage fold back which allows the compressor to ride through low voltage situations which helps keep the compressor running to avoid nuisance trips The drive also includes lost rotor avoidance and locked rotor detection The lost rotor avoidance uses a custom algorithm to evade a speed error by red...

Page 6: ... by the discharge line thermistor If operating the compressor below 1800 RPM an oil boost cycle is required Refer to the note in the operating envelope For applications where the voltage is below the rated minimum voltage the drive speed may be limited The limitation may also be affected by the ambient temperature High Pressure Control A high pressure control must be used in all applications A hig...

Page 7: ...systems to prevent solid particulate contamination oil dielectric strength degradation ice formation oil hydrolysis and metal corrosion It is the system designer s responsibility to make sure the filter drier is adequately sized to accommodate the contaminants from system manufacturing processes that leave solid or liquid contaminants in the evaporator coil condenser coil and interconnecting tubin...

Page 8: ...nt frequency or b evaluate the risk and life of the piping system when the compressor is allowed to run at frequencies that are coincident with natural frequencies of the piping system To do part b strain gauging the system piping is required For assistance in evaluating strain gauging results contact Application Engineering In order to properly determine if a design is appropriate for a given app...

Page 9: ...me outdoor ambient and system charge The reversing valve solenoid should be wired so that the valve does not reverse when the system is shut off by the operating thermostat in the heating or cooling mode If the valve is allowed to reverse at the system shutoff suction and discharge pressures are reversed to the compressor This will result in pressures equalizing through the compressor which can ca...

Page 10: ...lication guidelines as single compressors outlined in this bulletin The refrigerant charge limit for manifolded compressors is shown in Table 4 A manifolded circuit with charge over the limit must have a crankcase heater or stator heating applied to both compressors Oil levels in the individual sight glasses will vary depending on whether one or more compressors in the manifolded set are operating...

Page 11: ...s run test The inside of both fittings should be wiped with a lint free cloth to remove residual oil prior to brazing A compressor containing POE oil should never be left open longer than 20 minutes Assembly Line Brazing Procedure Personal safety equipment must be used during brazing operation Heat shields should be used to prevent overheating or burning nearby temperature sensitive parts Fire ext...

Page 12: ...est times Copeland Scroll compressors are designed for use with refrigerant and testing with nitrogen may result in a situation where the compressor does not develop a pressure differential no pump condition When testing with nitrogen the compressor must be allowed to cool for several minutes between tests Unbrazing System Components Before attempting to braze it is important to recover all refrig...

Page 13: ...d service practice when charging a system with a scroll compressor to charge liquid refrigerant into the high side only It is not good practice to dump liquid refrigerant from a refrigerant cylinder into the crankcase of a stationary compressor If additional charge is required charge liquid into the low side of the system with the compressor operating CAUTION Do not start the compressor while the ...

Page 14: ... 2017 Emerson Climate Technologies Inc 14 AE4 1414 ...

Page 15: ... 2017 Emerson Climate Technologies Inc 15 AE4 1414 ...

Page 16: ...round tube as necessary to heat tube evenly Add braze material to the joint while moving torch around joint to flow braze material around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final result Fiel...

Page 17: ... 2017 Emerson Climate Technologies Inc 17 AE4 1414 ...

Page 18: ... 2017 Emerson Climate Technologies Inc 18 AE4 1414 ...

Page 19: ... 2017 Emerson Climate Technologies Inc 19 AE4 1414 ...

Page 20: ... 2017 Emerson Climate Technologies Inc 20 AE4 1414 Figure 9 Start Up Procedure Figure 10 Shut Down Procedure ...

Page 21: ... 01 10 32 x 8mm Long Taptite Screw Molded Plug 529 0099 00 8 Gauge Wire 42 Leads Discharge Line Thermistor Molex Connector 085 0211 00 Fits 7 8 Tube Thermistor Clip 032 0688 04 7 8 Clip Suction Discharge Discharge Rotalock O Ring Seal 020 0028 02 Suction Rotalock O Ring Seal 020 0028 03 Discharge Rotalock Service Valve 7 8 998 0510 90 Suction Rotalock Service Valve 1 1 8 998 0510 99 Discharge Rota...

Page 22: ...Recommended Switching Frequency Hertz 6 000 6 000 Table 3 Emerson Compressor Drive Selection Drive Model Compressor Model Rated Voltage Drive Voltage Input Range Drive Nominal Power EVC1150B J1 124 ZPV0662E 5E9 230 200 240 15kW EVC1150B K2 124 ZPV0662E 4E9 380 380 480 EVC1150B K1 124 ZPV0662E 7E9 460 380 480 EVC1150B L1 124 ZPV0662E 7E9 575 500 575 EVC1185B J1 124 ZPV0962E 5E9 230 200 240 18kW EVC...

Page 23: ...active and the speed is above 3600 RPM decelerate 3600 RPM for a default of three minutes After two minutes and the command has not changed shut down the compressor 4 If envelope control is not active and the speed is below 3600 RPM maintain current speed for a default of three minutes After two minutes and the command has not changed shut down the compressor The contents of this publication are p...

Reviews: