background image

 

 

© 2017 Emerson Climate Technologies, Inc.

 

11 

AE4-1414 

APPLICATION TESTS

 

New  system  designs  should  be  evaluated  throughout 
the  entire  expected  operating  range  of  the  unit  to 
ensure the system will perform reliably throughout the 
life  of  the  product.  Test  data,  taken  throughout  the 
operating  range  of  the  unit,  should  be  closely 
scrutinized  to  help  identify  gross  errors  in  system 
design that may produce conditions that could lead to 
compressor failure.

 

General Application Tests 

In  addition  to  the  tests  outlined  above,  off-cycle 
migration  tests  are  recommended  if  the  system 
charge  amount  exceeds  11  pounds  (7  kg)  and  less 
than  100  watts  of  the  stator  heat  option  is  selected. 
The  purpose  of  the  off-cycle  migration  test  is  to 
ensure  that  stator  heat  is  great  enough  to  minimize 
off-cycle migration after long compressor 'off' periods. 
System  faults,  such  as  low  or  loss  of  indoor  air-flow, 
loss 

of 

outdoor 

air-flow, 

and 

low/overcharge 

conditions  should  all  be  evaluated  to  ensure  the 
compressor  and  service  technician  are  protected 
against any adverse condition. 

NOTICE  The tests outlined above are for common 
applications of compressors in this family. Please 
consult 

with 

Application 

Engineering 

on 

applications  outside  of  those  outlined  above  for 
the appropriate application tests. 

ASSEMBLY LINE PROCEDURES 

Installing the Compressor 

 

Use care and the appropriate material handling 
equipment when lifting and moving compressors. 
Personal safety equipment must be used. 
 

Copeland  Scroll  compressors  leave  the  factory 
dehydrated,  with  a  dry  air  holding  charge.  If 
compressors are stored in a cold ambient (i.e. outside 
during  the  winter),  the  suction  and  discharge  plugs 
should  not  be  removed  until  the  compressor  has  had 
sufficient  time  to  warm  up  to  the  plant  ambient 
temperature.  The  suggested  warm  up  time  is  one 
hour  per  4°F  (2°C)  difference  between  outdoor  and 
indoor  temperature.  It  is  suggested  that  the  larger 
suction  plug  be  removed  first  to  relieve  the  internal 
pressure.  Removing the  smaller discharge  plug could 
result in a spray of oil out of this fitting since some oil 
accumulates  in  the  head  of  the  compressor  after 
Emerson’s run test. The inside of both fittings  should 
be  wiped  with  a  lint  free  cloth  to  remove  residual  oil 
prior  to  brazing.  A  compressor  containing  POE  oil 
should never be left open longer than 20 minutes. 

Assembly Line Brazing Procedure 

 

Personal safety equipment must be used during 
brazing operation. Heat shields should be used to 
prevent overheating or burning nearby 
temperature sensitive parts. Fire extinguishing 
equipment should be accessible in the event of a 
fire. 

 

Figure 4 

discusses the proper procedures for brazing 

the  suction  and  discharge  lines  to  a  scroll 
compressor. 

 

NOTICE  It  is  important  to  flow  nitrogen  through 
the  system  while  brazing  all  joints  during  the 
system  assembly  process.

  Nitrogen  displaces  the 

air and prevents the formation of copper oxides in the 
system.  If  allowed  to  form,  the  copper  oxide  flakes 
can  later  be  swept  through  the  system  and  block 
screens  such  as  those  protecting  capillary  tubes, 
expansion  valves,  and  accumulator  oil  return  holes. 
Any  blockage  of  oil  or  refrigerant  may  damage  the 
compressor resulting in failure. 

Pressure Testing 

 

Never pressurize the compressor to more than 475 
psig (33 bar) for leak checking purposes. Never 
pressurize the compressor from a nitrogen 
cylinder or other pressure source without an 
appropriately sized pressure regulating and relief 
valve.

 

The  pressure  used  on  the  line  to  meet  the  U.L.  burst 
pressure requirement must not be higher than 475 psig 
(33  bar).  Higher  pressure  may  result  in  permanent 
deformation  of  the  compressor  shell  and  possible 
misalignment or bottom cover distortion. 

Assembly Line System Charging Procedure 

Systems should be charged with liquid on the high side 
to  the  extent  possible.  The  majority  of  the  charge 
should  be  pumped  in  the  high  side  of  the  system  to 
prevent  low  voltage  starting  difficulties,  hipot  failures, 
and  bearing  washout  during  the  first-time  start  on  the 
assembly line. If additional charge is needed, it should 
be  added  as 

liquid

 to  the low  side  of the  system  with 

the  compressor  operating.  Pre-charging  on  the  high 
side  and  adding  liquid  on  the  low  side  of  the  system 
are  both  meant  to  protect  the  compressor  from 
operating with abnormally low suction pressures during 
charging. 

NOTICE:

 

Do  not  operate  the  compressor 

without enough system charge to maintain at least 
55  psig  (3.8  bar)  suction  pressure.  Do  not  operate 

Summary of Contents for Copeland Scroll ZPV066

Page 1: ... Lengths High Refrigerant Charge 7 Discharge Check Valve 8 Suction and Discharge Tube Design 8 Compressor Mounting 8 Discharge Mufflers 8 Airborne Sound Control 8 Expansion Devices 9 Reversing Valves 9 Accumulators 9 Off Cycle Migration Control 9 Manifolded Compressors 10 Manifolded Applications 10 Application Tests 11 General Application Tests 11 Assembly Line Procedures Installing the Compressor...

Page 2: ...ssor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which if not avoided could result in...

Page 3: ...rants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury WARNING BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be used Failure to follow...

Page 4: ...quirements please see the Emerson EVC Drive user guide Ensure correct wiring at both the compressor and drive connections prior to starting the compressor to avoid a mis wire or powered reverse situation These situations may cause compressor damage The variable speed compressor must be paired with the appropriate variable speed drive Do not connect the power supply directly to the compressor Nomen...

Page 5: ...e includes motor protection features for the compressor The drive sets the maximum current limit low voltage fold back which allows the compressor to ride through low voltage situations which helps keep the compressor running to avoid nuisance trips The drive also includes lost rotor avoidance and locked rotor detection The lost rotor avoidance uses a custom algorithm to evade a speed error by red...

Page 6: ... by the discharge line thermistor If operating the compressor below 1800 RPM an oil boost cycle is required Refer to the note in the operating envelope For applications where the voltage is below the rated minimum voltage the drive speed may be limited The limitation may also be affected by the ambient temperature High Pressure Control A high pressure control must be used in all applications A hig...

Page 7: ...systems to prevent solid particulate contamination oil dielectric strength degradation ice formation oil hydrolysis and metal corrosion It is the system designer s responsibility to make sure the filter drier is adequately sized to accommodate the contaminants from system manufacturing processes that leave solid or liquid contaminants in the evaporator coil condenser coil and interconnecting tubin...

Page 8: ...nt frequency or b evaluate the risk and life of the piping system when the compressor is allowed to run at frequencies that are coincident with natural frequencies of the piping system To do part b strain gauging the system piping is required For assistance in evaluating strain gauging results contact Application Engineering In order to properly determine if a design is appropriate for a given app...

Page 9: ...me outdoor ambient and system charge The reversing valve solenoid should be wired so that the valve does not reverse when the system is shut off by the operating thermostat in the heating or cooling mode If the valve is allowed to reverse at the system shutoff suction and discharge pressures are reversed to the compressor This will result in pressures equalizing through the compressor which can ca...

Page 10: ...lication guidelines as single compressors outlined in this bulletin The refrigerant charge limit for manifolded compressors is shown in Table 4 A manifolded circuit with charge over the limit must have a crankcase heater or stator heating applied to both compressors Oil levels in the individual sight glasses will vary depending on whether one or more compressors in the manifolded set are operating...

Page 11: ...s run test The inside of both fittings should be wiped with a lint free cloth to remove residual oil prior to brazing A compressor containing POE oil should never be left open longer than 20 minutes Assembly Line Brazing Procedure Personal safety equipment must be used during brazing operation Heat shields should be used to prevent overheating or burning nearby temperature sensitive parts Fire ext...

Page 12: ...est times Copeland Scroll compressors are designed for use with refrigerant and testing with nitrogen may result in a situation where the compressor does not develop a pressure differential no pump condition When testing with nitrogen the compressor must be allowed to cool for several minutes between tests Unbrazing System Components Before attempting to braze it is important to recover all refrig...

Page 13: ...d service practice when charging a system with a scroll compressor to charge liquid refrigerant into the high side only It is not good practice to dump liquid refrigerant from a refrigerant cylinder into the crankcase of a stationary compressor If additional charge is required charge liquid into the low side of the system with the compressor operating CAUTION Do not start the compressor while the ...

Page 14: ... 2017 Emerson Climate Technologies Inc 14 AE4 1414 ...

Page 15: ... 2017 Emerson Climate Technologies Inc 15 AE4 1414 ...

Page 16: ...round tube as necessary to heat tube evenly Add braze material to the joint while moving torch around joint to flow braze material around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final result Fiel...

Page 17: ... 2017 Emerson Climate Technologies Inc 17 AE4 1414 ...

Page 18: ... 2017 Emerson Climate Technologies Inc 18 AE4 1414 ...

Page 19: ... 2017 Emerson Climate Technologies Inc 19 AE4 1414 ...

Page 20: ... 2017 Emerson Climate Technologies Inc 20 AE4 1414 Figure 9 Start Up Procedure Figure 10 Shut Down Procedure ...

Page 21: ... 01 10 32 x 8mm Long Taptite Screw Molded Plug 529 0099 00 8 Gauge Wire 42 Leads Discharge Line Thermistor Molex Connector 085 0211 00 Fits 7 8 Tube Thermistor Clip 032 0688 04 7 8 Clip Suction Discharge Discharge Rotalock O Ring Seal 020 0028 02 Suction Rotalock O Ring Seal 020 0028 03 Discharge Rotalock Service Valve 7 8 998 0510 90 Suction Rotalock Service Valve 1 1 8 998 0510 99 Discharge Rota...

Page 22: ...Recommended Switching Frequency Hertz 6 000 6 000 Table 3 Emerson Compressor Drive Selection Drive Model Compressor Model Rated Voltage Drive Voltage Input Range Drive Nominal Power EVC1150B J1 124 ZPV0662E 5E9 230 200 240 15kW EVC1150B K2 124 ZPV0662E 4E9 380 380 480 EVC1150B K1 124 ZPV0662E 7E9 460 380 480 EVC1150B L1 124 ZPV0662E 7E9 575 500 575 EVC1185B J1 124 ZPV0962E 5E9 230 200 240 18kW EVC...

Page 23: ...active and the speed is above 3600 RPM decelerate 3600 RPM for a default of three minutes After two minutes and the command has not changed shut down the compressor 4 If envelope control is not active and the speed is below 3600 RPM maintain current speed for a default of three minutes After two minutes and the command has not changed shut down the compressor The contents of this publication are p...

Reviews: