4
C6.2.19/0507-0708/E
ZP154K* to ZP182K*
ZP235K* to ZP385K*
20
25
30
35
40
45
50
55
60
65
70
-35 -30 -25 -20 -15 -10
-5
0
5
10
15 20
25
Evaporating Temperature to (
o
C)
C
o
n
d
e
n
s
in
g
T
e
m
p
e
ra
tu
re
tc
(
o
C
)
R410A
ZP154
20
25
30
35
40
45
50
55
60
65
70
-30
-25
-20
-15
-10
-5
0
5
10
15
20
Evaporating Temperature to (
o
C)
C
o
n
d
e
n
s
in
g
T
e
m
p
e
ra
tu
re
tc
(
o
C
)
R410A
10K Suction Superheat
25
o
C Suction Gas Return
Figure 2: Application envelopes for compressors ZP23K* to ZP385K* with R410A
NOTE:
For application envelopes with R134a and R22, please refer to Copeland
®
Brand
Products Selection Software.
3
Installation
WARNING
High pressure! Injury to skin and eyes possible!
Be careful when
opening connections on a pressurized item
3.1
Compressor handling
3.1.1 Transport and storage
WARNING
Risk of collapse! Personal injuries!
Move compressors only with
appropriate mechanical or handling equipment according to weight. Keep in
the upright position. Stack pallets on top of each other when not exceeding
300 kg. Do not stack single boxes on top of each other. Keep the packaging
dry at all times.
Figure 3
3.1.2 Positioning and securing
IMPORTANT
Handling damage! Compressor malfunction!
Only use the lifting eyes
whenever the compressor requires positioning. Using discharge or suction
connections for lifting may cause damage or leaks.
For models ZR94K* to ZR380K* and ZP90K* to ZP385K*,
because oil might spill out of the
suction connection located low on the shell, the suction connection plug must be left in place
until the compressor is set into the unit. If possible, the compressor should be kept vertical
during handling. The discharge connection plug should be removed first before pulling the
suction connection plug to allow the dry air pressure inside the compressor to escape. Pulling
the plugs in this sequence prevents oil mist from coating the suction tube making brazing
Summary of Contents for Copeland Scroll ZP23K Series
Page 24: ... ...