Code
Description
Cause
Action
Reset
E82
Probe configuration error
Dif ferent probes (P3,
P4, P5, P6, P7) have
the same configuration.
For example,
A13 = Ambient temp
(NTC 10 K),
A15 = Ambient temp
(NTC 10 K)
Correct the configuration
Board must be reset
E83
DI conf iguration error
Dif ferent digital inputs
DI (DI1, DI2, DI3) have
the same configuration.
For example,
R04 = Door switch,
R07 = Door switch
Correct the configuration
Board must be reset
E84
Compressor configuration error
Case 0: digital
compressor relay is
conf igured, no digital
solenoid configuration;
Case 1: digital
compressor relay is
conf igured, no digital
solenoid configuration;
Case 2: no digital
compressor relay
conf iguration, digital
solenoid is configured;
Case 3: C05 = 3, digital
compressor relay and
digital solenoid are
conf igured
Correct the configuration
Board must be reset
E85
Injection probe configuration error
Not used
E86
EEPROM R/W error (manual)
HW problem in the
board
Change the board
E87
Fan f ailure
Fan alarm contact
(digital input DI7) open
F6(F7)
Check reason for fan alarm contact
opening (mechanical issue, electrical
issue)
Automatically: as soon the alarm contact closes
again
Table 26: Alarm code overview