Appendix 1: Parameter list level 1 (Pr1)
Parameter
Description
Range
Factory settings
OMTE
OLE
OLTE
C01
Compressor cut-in pressure
setpoint
C02 to C04
-
1
-
C02
Compressor cut-out pressure
setpoint
C03 to C01
-
0.5
-
C07
Ref rigerant selection for
regulation
R404A (0-404) - R134A (2-134) - R407A (5-07A)
R407F (6-07F) - R448A (7-48A) - R449A (8-49A)
8-R449A
C16
Digital compressor setpoint
C03 to C04
2.6
-
1.0
C17
Proportional band for
compressor regulation
0.1 to 9.9 bar; 0.1 to 99.9 PSI;
0.1°C to 25.5°C
2.0
-
1.0
C21
Cycle time for digital
compressor
10 to 40 sec
10
-
10
(20 for OLTE-82D)
C24
Minimum capacity for digital
compressor
0 to C25 %
10
-
10
(30 for OLTE-82D)
C27
Time with digital compressor at
PMi before switching off another
load
0 to 255 sec
10
-
5
D29
Low-pressure alarm value
A02 to A03
0.8
-
-
E66
Delta temperature condenser
f loating setpoint
0.0 to 25.5 °C
8.0
8.0
8.0
N01
Current minute
0 to 59
-
-
-
N02
Current hour
0 to 23
-
-
-
N03
Day of month
1 to 31
-
-
-
N04
Month
1 to 12
-
-
-
N05
Year
0 to 99
-
-
-
T18
Access to Pr2 level
(0÷999)
3 2 1
Table 25: Parameters level 1