C6.1.10/0118-0318/E
48
Parameters
Description
Range
Factory setting
ZXDI
ZXDE
ZXDI
G16
doP
Duration to calculate the average difference between
the diP and doP
0 to 100 min
5
L2
G17
dPr
Defrost type
EL (0-EL)
in (1-IN)
Pulse (2-PLS)
EL
L2
G18
tdA
Interval between defrost cycles
0 to 120 h
4
L2
G19
tdF
Maximum length for defrost
0 to 255 min
20
L2
G20
idF
Duration of pulse defrost
0 to G19
15
L2
G21
MdF
Defrost termination temperature
-40°C to 110°C
10
L2
G22
dPd
Defrost delay time
0 to 255 min
0
L2
G23
dtE
Defrost interval mode
nu (0-NU)
in (1-IN)
rtC (2-rtC)
Intelligent (3-INT)
Not used
L2
G24
dSd
Display during defrost
dEF = Defrost;
Set = Setpoint case temp;
it = Case temp;
rt = Display in standard operation
dEF (0-DEF)
Set (1-SET)
it (2-IT)
rt (3-RT)
dEF
L2
G25
EdF
Maximum display delay after defrost
0 to 255 min
0
L2
G26
dFd
Drip time
0 to 120 min
1
L2
G27
dAd
Defrost at power-on
No (0-NO) - Yes (1-YES)
NO
L2
G28
Fdt
Workday defrost start 1
0 to 23h50 minutes; nu
0:00
L2
G29
dPo
Workday defrost start 2
0 to 23h50 minutes; nu
4:00
L2
G30
Ld1
Workday defrost start 3
0 to 23h50 minutes; nu
8:00
L2
G31
Ld2
Workday defrost start 4
0 to 23h50 minutes; nu
12:00
L2
G32
Ld3
Workday defrost start 5
0 to 23h50 minutes; nu
16:00
L2
G33
Ld4
Workday defrost start 6
0 to 23h50 minutes; nu
20:00
L2
G34
Ld5
Holiday defrost start 1
0 to 23h50 minutes; nu
0:00
L2
G35
Ld6
Holiday defrost start 2
0 to 23h50 minutes; nu
4:00
L2
G36
Sd1
Holiday defrost start 3
0 to 23h50 minutes; nu
8:00
L2
G37
Sd2
Holiday defrost start 4
0 to 23h50 minutes; nu
12:00
L2