Starting the evacuation function:

 

The evacuation mode will start when pressing the 

ENB

 key only if all 3 of the following conditions are met:

 

 

Suction pressure probe 

P1 value < SPF6

 

 

Gas cooler (condenser) pressure probe 

P2 value < SPF6

 

 

Flash tank pressure probe 

P3 value < SPF6

 

NOTE: SPF6 = Pressure setpoint to stop evacuation mode (factory-set to 10 bar).

 

The 

ENB

  key  will  remain  visible  all  the  time.  If  the  evacuation  function  is  enabled  but  one  of  the  above 

conditions is not met, the following message will be displayed: 

  "Enabling condition for Evacuation Mode not met, waiting for it" 

Subsequently: 

1) 

The HP and BP valves open directly 100% (the evacuation mode has priority over the  valves override 
function). 

2) 

The compressor is switched off (safety timers are ignored). 

3) 

The fan is switched off, while auxiliary outputs are not influenced (safety timers are ignored). 

4) 

The alarms are disabled except for the communication alarms. 

Stopping the evacuation function: 

The evacuation mode will be deactivated when 

1) 

One of the 3 pressures probes 

P1, P2 & P3 > SPF6

 

or

 

2) 

the 

DISB

 key is pressed. 

When the evacuation function is stopped, the controller returns to its previous status, ie, Off or regulation. 

NOTE: As long as the evacuation function is active, the evacuation label will flash on the main display 
– see Figure 5 below. After pressing the EXIT key, the previous screen will be displayed again. 

 

Figure 5 

NOTE:  If  one  of  the  3  probes  (suction  pressure,  gas  cooler  pressure  or  flash  tank  pressure)  is  not 
configured or in error, the evacuation mode cannot be executed. 

 

 

Summary of Contents for Copeland EazyCool CO2

Page 1: ...sure side piping has been finalized and the electrical supply has been connected by qualified personnel please follow the steps below in preparation for commissioning Safety Verification of necessary safety devices in the system Visual inspection of the refrigerant pipes and especially of all connections Visual inspection of the electrical wiring of the supply line Checking the refrigeration unit ...

Page 2: ...to be opened closed in order to carry out the pressure tests For the evacuation process it is recommended that all shut off devices be opened and evacuated from both sides via the connections on the suction side and the connection on the liquid receiver The shut off valves at the discharge port on the suction side of the compressor at the outlet of the liquid receiver and the shut off valve in the...

Page 3: ...his serves to avoid incorrect measurements resulting from the pressure gradient along the connecting lines to the pump IMPORTANT Care must be taken that all components solenoids expansion devices regulators shut off valves etc in the refrigeration cycle which separate a part of the installation when de energized are manually opened to guarantee successful evacuation in the whole piping system NOTE...

Page 4: ...ity over the valves override function 2 The compressor is switched off safety timers are ignored 3 The fan is switched off while auxiliary outputs are not influenced safety timers are ignored 4 The alarms are disabled except for the communication alarms Stopping the evacuation function The evacuation mode will be deactivated when 1 One of the 3 pressures probes P1 P2 P3 SPF6 or 2 the DISB key is p...

Page 5: ...ressors F1 and fans F3 must be switched on and the release for the frequency inverter SB1 must be activated Figure 7 Enabling compressors fans frequency inverter The refrigeration unit starts automatically First the gas cooler fans start up then the compressor switches on and starts controlling according to suction pressure The filling process via the suction side can be completed The system shoul...

Page 6: ... OFF 8 Use the UP and DOWN keys to adjust GC78 to the desired value 9 Press SET to apply the setting 10 Press EXIT to leave the menu GC20 Medium pressure flashtank setpoint Setpoint for the pressure in the liquid receiver in normal control mode GC78 Bypass medium pressure vessel Pressure with compressor OFF Maximum pressure in the liquid receiver during standstill of the refrigeration unit When th...

Page 7: ...on compressor setpoint SETC1 SPF1 The lowest pumpdown setpoint will always be applied The following diagram illustrates the controller logic Figure 8 Controller logic for the pumpdown function NOTE The pumpdown setpoint will never be lower than what parameter RC02 allows 18 C 0 C Controller will perform pumpdown down to 18 C Ambient condition TAmb 20 C SPF5 20K Compressor setpoint SETC1 10 C SPF1 ...

Reviews: