D7.8.6/1112-0815/E
16/18
6.3.3 Holding register (command 0x03, 0x06, 0x10)
Address
(Hex)
Contents
Qty Min
Max
Unit Default Scale
Data Description
Start Start
0000 0010
Customer Name
17
'x'
000A 000F
0011 0014
Customer ID
4
'x'
0015 0024
Customer Location
16
'x'
001A 001F
0025 0036
Compressor Model Number
18
'x'
002A 002F
0037 0042
Compressor Serial Number
12
'x'
003A 003F
0051 0059
Module Part Number
12
'x'
005A 005C
005D 005F
Module Serial Number
12
'x'
0060 0069
0085
Alert Trigger Parameters
Configuration
20
-70
585.35
°F
309
1/100
DLT temp trip set point value, Unit : 0.01°F
Set point = (Word - 7000)/100(°F)
0086
-70
585.35
°F
266
1/100
DLT temp trip reset point value,
Unit : 0.01°F
Reset point =( Word -7000)/100(°F)
008C
0
65535
V
230
Compressor Nominal Voltage
008D
0
65535
Hz
60
Compressor Nominal Frequency
008E
2
8
%
5
Voltage Imbalance Setting
0x02 - 2% 0x03 - 3%
0x04 - 4% 0x05 - 5%
0x06 - 6% 0x07 - 7%
0x08 - 8% Others - NA
00B4
Lockout Status Configuration1
1
0
1
BIT0 - High Discharge Temperature Lockout
Status
BIT3 - Miss Phase Lockout Status
BIT5 - Rack Controller Lockout Status
BIT6 - Part Winding Delay Lockout Status
1 - Enable 0 - Disable
00D2
Sensor Module Required
0x01
– No Sensor Module is equipped
0x02
– Sensor Module is equipped
Table 11: Holding register