D7.8.6/1112-0815/E
12/18
00B2
Eight Days Alarm History of Sensor
Module Failure Warning
13
0
1
BIT0 - Today
BIT1 - Today-1
……………
BIT7 - Today-7:
0 - Not present 1 Present
00B4
Eight Days Alarm History of High
Discharge Temperature Alarm
15
0
1
BIT0 - Today
BIT1 - Today-1
……………………………..
BIT7 - Today-7
0 - Not present 1 Present
00B6
Eight Days Alarm History of Locked
Rotor Alert
17
0
1
BIT0 - Today
BIT1 - Today-1
……………………………..
BIT7 - Today-7
0 - Not present 1 Present
00B7
Eight Days Alarm History of Missing
Phase Alert
18
0
1
BIT0 - Today
BIT1 - Today-1
……………………………..
BIT7 - Today-7
0 - Not present 1 Present
00B9
Eight Days Alarm History of
Compressor Low Voltage Alert
20
0
1
BIT0 - Today
BIT1 - Today-1
……………………………..
BIT7 - Today-7
0 - Not present 1 Present
00BC
Eight Days Alarm History of Voltage
Imbalance Alarm
23
0
1
BIT0 - Today
BIT1 - Today-1
……………………………..
BIT7 - Today-7
0 - Not present 1 Present
00C0
Eight Days Alarm History of Motor
Overheat Alarm
27
0
1
BIT0 - Today
BIT1 - Today-1
……………………………..
BIT7 - Today-7
) 0 - Not present 1 Present
00C1
Eight Days Alarm History of Protection
Trip Alarm
28
0
1
BIT0 - Today
BIT1 - Today-1
……………………………..
BIT7 - Today-7
0 - Not present 1 Present
00C6
Eight Days Alarm History of High
Discharge Temperature Lockout
33
0
1
BIT0 - Today
BIT1 - Today-1
……………………………..
BIT7 - Today-7
0 - Not present 1 Present
00C7
Eight Days Alarm History of Locked
Rotor Lockout
35
0
1
BIT0 - Today
BIT1 - Today-1
……………………………..
BIT7 - Today-7
0 - Not present 1 Present
00C9
Eight Days Alarm History of Missing
Phase Lockout
36
0
1
BIT0 - Today
BIT1 - Today-1
……………………………..
BIT7 - Today-7
0 - Not present 1 Present
00CD
Eight Days Alarm History of Insufficient
Oil Pressure Lockout
40
0
1
BIT0 - Today
BIT1 - Today-1
……………………………..
BIT7 - Today-7
0 - Not present 1 to 42 - Present
00D1
Eight Days Alarm History of Control
Module Failure Lockout
44
0
1
BIT0 - Today
BIT1 - Today-1
……………………………..
BIT7 - Today-7
0 - Not present 1 to 46 - Present