12
D6.3.4/0715-0716/E
3
Installation
WARNING
High pressure!
Injury to skin and eyes possible!
Be careful when
opening connections on a pressurized item.
3.1
Compressor handling
3.1.1 Delivery
Please check whether the delivery is correct and complete. Deficiencies should be reported
immediately in writing.
Standard delivery:
Suction and discharge shut-off valves
Oil charge, oil sight glass
Mounting kit
Motor protector
Holding charge up to 2.5 bar(g) (dry air)
3.1.2 Transport and storage
WARNING
Risk of collapse! Personal injuries!
Move compressors only with
appropriate mechanical or handling equipment according to weight. Keep in
the upright position. Stack pallets on top of each other when not exceeding
300 kg. Stacking higher than the recommended maximum can cause
accidents. Do not stack single boxes on top of each other. Keep the
packaging dry at all times.
Compressors are individually packed and may be delivered on pallets depending on quantity and
size. Cooling fans are delivered in separate cartons. Accessories may be mounted or delivered
loose. Solenoid valves are never mounted.
Figure 5: Transport
Figure 6: Storage
3.1.3 Positioning and securing
IMPORTANT
Handling damage! Compressor malfunction!
Only use the lifting eyes
whenever the compressor requires positioning. Using discharge or suction
connections for lifting may cause damage or leaks.
If possible, the compressor should be kept vertical during handling.