background image

WARNING: 

To avoid fire, shock, and serious personal injury, follow these instructions.

Safety Instructions

1. Read your owner’s manual carefully and keep it for future reference.

2. Before servicing or cleaning unit, switch power off at service panel and lock service panel disconnecting

means to prevent power from being switched on accidentally. When the service disconnecting means cannot
be locked, securely fasten a warning device, such as a tag, to the service panel.

3. Be careful of the fan and blades when cleaning, painting, or working near the fan. Always turn off the power to

the ceiling fan before servicing.

4. Do not put anything into the fan blades while they are turning.

5. Do not operate reversing switch until fan blades have come to a complete stop.

Additional Safety Instructions for Installation

1. To avoid possible shock, be sure electricity is turned off at the fuse box before wiring, and do not operate fan

without blades.

2. The installation is to be in accordance with the National Electrical Code, “ANSI/NFPA 70-1999” and Local

Electrical Codes. Use the National Electrical Code if Local Codes do not exist. The ceiling fan must be
grounded as a precaution against possible electrical shock. Electrical installation should be made or approved
by a licensed electrician.

3. The outlet box and joist must be securely mounted and capable of reliably supporting at least 50 pounds. Use

only U.L. outlet boxes listed as “Acceptable for Fan Support”, and use the mounting screws provided with the
outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support
and may need to be replaced. Consult a qualified electrician if in doubt.

4. The downrod furnished with the fan provides the minimum recommended floor to fan blade clearance for an

8-foot ceiling.

5. The fan must be mounted with the fan blades at least 7 feet from the floor to prevent accidental contact with the

fan blades.

6. Follow the recommended instructions for the proper method of wiring your ceiling fan. If you do not know

enough about electrical wiring, have your fan installed by a licensed electrician.

NOTE:

This fan is NOT suitable for use with solid-state speed controls.

WARNING:

This product is designed to use only those parts supplied with this product and/or any accessories

designated specifically for use with this product by Emerson Electric Co. Substitution of parts or accessories not
designated for use with this product by Emerson Electric Co. could result in personal injury or property damage.

WARNING:

To reduce the risk of personal injury, do not bend the blade flange when installing the blade flanges,

balancing the blades or cleaning the fan. Do not insert foreign objects in between rotating fan blades.

WARNING:

To reduce the risk of electrical shock, this fan must be installed with an isolating wall control/switch.

2

WARNING

!

DATE CODE:

The date code of this fan may be found on

the box, stamped in ink on a white label.

You should record this data above and keep

it in a safe place for future use.

U.L. Model No.: CF701

Summary of Contents for BUILDER UNIPACK CF701BS

Page 1: ...s of the nearest authorized service center You will be responsible for all insurance freight or other transportation charges to our factory or authorized service center Your Emerson Air Comfort Ceiling Fan should be properly packed to avoid damage in transit since we will not be responsible for any such damage What Is Not Covered The glass globes and light bulbs of your ceiling fan are not covered...

Page 2: ...Acceptable for Fan Support and use the mounting screws provided with the outlet box Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced Consult a qualified electrician if in doubt 4 The downrod furnished with the fan provides the minimum recommended floor to fan blade clearance for an 8 foot ceiling 5 The fan must be mounted ...

Page 3: ...ach step As each step is completed place a check mark in the box This will insure that all steps have been completed and will be helpful in finding your place should you be interrupted Before assembling your ceiling fan refer to section on proper method of wiring your fan page 7 If you feel you do not have enough wiring knowledge or experience have your fan installed by a licensed electrician Do n...

Page 4: ...g up on the hanger ball securely tighten the two setscrews in the motor coupling Figure 1 NOTE The setscrews must be properly installed as described above or fan wobble could result 5 The fan comes with blue black and white leads that are 42 long Measure up approximately 6 to 9 inches above top of hanger ball downrod assembly Cut off excess leads and strip back insulation 1 2 inch from end of lead...

Page 5: ...ITCH CUP SWITCH CUP CONNECTOR Figure 4 SPRING LOCKWASHER SCREWS SWITCH CUP CONNECTOR WIRE CONNECTORS WHITE WIRES SWITCH HOUSING ASSEMBLY BLACK WIRE NUT FAN SWITCH CHAIN BLUE WIRE LIGHT FITTER BOWL CAP Figure 5 12 Engage the connector of the switch housing assembly with the motor connector Figure 6 The two connectors are keyed and color coded and must be mated correctly color to color before they c...

Page 6: ...U L Model No CF701 15 Install two 60 watt maximum candelabra base light bulbs into the light fitter sockets Figure 8 16 Remove the finial nut and outer bowl cap from the light fitter Figure 8 17 Pass the fan switch chain through the cut slotted hole in the bowl cap Figure 8 To avoid possible fire hazard do not exceed wattage indicated on the fitter WARNING THREADED NIPPLE BOWL CAP LIGHT FITTER OUT...

Page 7: ...ews supplied with outlet box Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced Consult a qualified electrician if in doubt WARNING The outlet box and joist must be securely mounted and capable of supporting at least 50 lbs Use only a U L outlet box listed as Acceptable for Fan Support WARNING OUTLET BOX HANGER BRACKET HANGE...

Page 8: ...ion of the light by gently pulling on the light switch pull chain 3 Check the operation of the fan by gently pulling on the speed control switch pull chain The operation sequence is as follows 1st pull High 2nd pull Medium 4 Your fan is shipped from the factory with the reversing switch positioned to circulate air downward If airflow is desired in opposite direction turn the fan off and wait for t...

Page 9: ...witch position is all the way to one side 2 Fan sounds noisy 1 Blades not attached to fan 1 Attach blades to fan before operating 2 Screws securing fan blade flanges to motor hub 2 Check to make sure the screws which attach the fan are loose flanges to the motor hub are tight WARNING Make sure main power is turned off 3 Wire connectors inside switch housing rattling 3 Check to make sure wire conne...

Page 10: ...763102 ORB 763102 WW 8 Blade Set of 5 763100 13 763100 14 763100 7 Parts Bag Containing 763901 763901 1 763901 2 9 Wire Connector 3 10 Hairpin Clip 1 11 Clevis Pin 1 12 Wood Ball Pendant 2 13 Coupling 2 14 Threaded Stud 8 32 x 1 1 4 2 15 Lockwasher 8 32 2 16 Knurled Knob 8 32 2 17 Screw Flange M6 x 12mm with Lockwasher 11 18 Screw Blade M5 x 6mm 16 19 Wiring Harness 763920 3 763920 2 763920 4 20 F...

Page 11: ...tain all parts have been removed HOW TO ORDER REPAIR PARTS WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMATION PART NUMBER PART DESCRIPTION NAME OF ITEM MODEL NUMBER For repair parts phone 1 800 654 3545 7 8 3 2 10 11 9 17 18 14 1 15 16 19 6 21 13 20 12 22 5 13 12 4 ...

Page 12: ...Air Comfort Products DIVISION OF EMERSON ELECTRIC CO 8100 W Florissant St Louis MO 63136 U L Model No CF701 Form No BP7392 Printed in China 03 09 Part No F40BP73920000 ...

Reviews: